CONTEG CoolTeg G CW chilled water in-row cooling units datasheet
Original title CONTEG coolteg g cw datasheet, current download accessed 2026-11-16
CONTEG
CONTEG CoolTeg G CW is a chilled-water in-row unit working with +6 to +30 °C water; the CW30 gives 40.4 kW with a 4-row coil and 47.4 kW with a 6-row coil nominal.
On this page
Overview
The datasheet describes the chilled-water G CW member of the CoolTeg in-row cooling family. Units sit between IT racks, deliver cold air directly to the server front, need no raised floor and suit contained hot aisle, contained cold aisle, open aisle and mini data-centre layouts. The maker states capacity up to 81 kW and an operating water temperature of +6 to +30 °C.
The table compares three models. CW30 (300 mm wide): 40.4 kW (net 39.4) with a 4-row coil and 47.4 kW (net 46.4) with a 6-row coil; CW30 Super C: 52.8 / 59.9 kW (net 50.3 / 57.4); Plus CW60 (600 mm wide): 80.7 kW (net 75.9). Nominal condition is 35 °C return air, without condensation, and 6/12 °C water. For CW30 water flow is 5700 / 6440 l/h, air flow 6600 / 6500 m3/h, supply 230 V single phase; Plus CW60 is 11000 l/h, 13000 m3/h and 400 V 3-phase.
Height runs from 2006 to 2456 mm (42U to 52U), depth 1000 or 1200 mm (iSEVEN) and 1008/1208 mm (PREMIUM racks), and weights are 163-194 kg for CW30 and 248-280 kg for Plus CW60. Pipe connections are 5/4 inch (CW30) and 6/4 inch (CW60) female. Mini data-centre units ship without filters and only in 1208 mm depth. The CW30 values in the current table are given separately for four-row and six-row coils; they must not be confused with those of the older Plus CW table.
Key points
- CW30: 40.4 kW (4-row) and 47.4 kW (6-row); net 39.4 and 46.4 kW.
- CW30 Super C: 52.8 / 59.9 kW; Plus CW60: 80.7 kW (net 75.9 kW).
- Nominal condition: 35 °C return air, 6/12 °C water; operating water +6 to +30 °C.
- CW30 water flow 5700 / 6440 l/h, air flow 6600 / 6500 m3/h; Plus CW60 11000 l/h and 13000 m3/h.
- CW30 230 V single phase, 6.3-6.7 A running current; Plus CW60 400 V 3-phase, 6.7 A.
- Width 300 mm (CW30) and 600 mm (CW60); height 42-52U; depth 1000/1200 mm.
- One display manages 16 units; TCP/IP standard, Modbus optional; four temperature sensors and humidity sensors.
Using it in design
- Compare net capacity (after fan heat) with the rack-row load; state 4-row versus 6-row coil in the order code.
- Raise the operating water temperature seasonally to increase free-cooling hours; check the 30 °C upper limit.
- In contained-aisle layouts match unit depth to the rack series (iSEVEN 1000/1200, PREMIUM 1008/1208 mm).
- Sum water flows for pipe size and pump capacity; show the 5/4 and 6/4 inch connections on detail drawings.
- For the mini data-centre option add the no-filter delivery and 1208 mm depth constraint to the cabinet specification.
Who should read it
Mechanical engineers designing in-row chilled-water cooling and contained-aisle planners.
Document contents
- CoolTeg cooling units
- Description and four cooling systems
- CoolTeg G CW technical table
- CoolTeg G CW30 detail sheet
- CoolTeg G CW30 Super C and Plus CW60
- Order code and accessories
Publication details
- Authors
- CONTEG
- Publisher
- CONTEG
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
CONTEG CONTEG coolteg g cw datasheet, current download accessed 2026-11-16. CONTEG. https://www.conteg.com/userfiles/coolteg-g-cw-datasheet-conteg-en-cb95cda2.pdf?v=hlodlzufaq
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.