CONTEG CoolTeg G XC direct expansion in-row cooling units with integrated compressor datasheet

Original title CONTEG coolteg g xc datasheet, current download accessed 2026-11-16

CONTEG

CONTEG CoolTeg G XC is a direct-expansion in-row unit with the compressor inside the cabinet: 24.7 kW nominal for Plus XC30 and 43.8 kW for G XC40, with -40 to +55 °C outdoor range.

On this page

Overview

The datasheet presents the XC members of the CoolTeg family: the compressor is in the indoor unit, connected to an outdoor condenser, so no water piping is needed in the data centre. The maker notes the compressor is safely inside the facility, outdoor-unit noise is low and the refrigerant is R410A. Capacity is up to 44 kW; Plus XC30 is given a 10-100% capacity regulation range.

The table compares two models. Plus XC30: nominal 24.7 kW (net 23.8), running current 13.43 A, maximum current 25.9 A, maximum fan power 0.85 kW, compressor 5.45 kW, air flow 4000 m3/h, 300 mm wide. G XC40: nominal 43.8 kW (net 40.5), 18.1 A, 25.9 A, fans 3.1 kW, compressor 11.7 kW, 9800 m3/h, 400 mm wide. The condition is 35 °C return air, 35 °C outdoor (45 °C condensing) and clean filters; compressor power is for 45 °C condensing and 10 °C evaporation.

Height is 2006-2456 mm for 42U-52U, depth 1000/1200 mm (iSEVEN) or 1008/1208 mm (PREMIUM), weight 194-214 kg for XC30 and 262-307 kg for XC40. Refrigerant pipes are 12 mm liquid / 16 mm gas on XC30 and 16 mm / 22 mm on XC40. Mini data-centre units are offered without filters and only in 1208 mm depth. The sheet lists the XC30 and XC40 model names, different casing options and fan-power ceilings together, so the model code and casing must be read together when selecting.

Key points

  1. Plus XC30: 24.7 kW nominal (net 23.8); G XC40: 43.8 kW nominal (net 40.5).
  2. Nominal condition: 35 °C return air, 35 °C outdoor, 45 °C condensing, clean filters.
  3. Compressor power 5.45 kW (XC30) and 11.7 kW (XC40); maximum fan power 0.85 and 3.1 kW.
  4. Maximum current 25.9 A on both; 400 V 3-phase.
  5. Air flow 4000 and 9800 m3/h; width 300 and 400 mm.
  6. Refrigerant pipes: XC30 12/16 mm, XC40 16/22 mm (liquid/gas); R410A.
  7. Operating range -40 to +55 °C; no water piping inside the data centre.

Using it in design

  • Verify the site maximum ambient against the 45 °C condensing assumption when selecting the outdoor condenser, and compare noise with the limit.
  • List compressor and fan power as separate lines in electrical distribution; use the 25.9 A maximum current for cable and protection selection.
  • Check liquid and gas line sizes and indoor-to-outdoor length on the refrigerant piping drawing.
  • Carry rack-series depth match (1000/1200 or 1008/1208 mm) and the 1208 mm limit for mini data centres into the specification.
  • For small and medium halls that want no chiller, consider direct expansion in place of water as an alternative.

Who should read it

In-row cooling designers who want no water piping and engineers of small and medium data halls.

Document contents

  1. CoolTeg cooling units
  2. Description and four cooling systems
  3. CoolTeg G XC technical table
  4. CoolTeg Plus XC30 detail sheet
  5. CoolTeg G XC40 detail sheet
  6. Order code and accessories

Publication details

Authors
CONTEG
Publisher
CONTEG
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

CONTEG CONTEG coolteg g xc datasheet, current download accessed 2026-11-16. CONTEG. https://www.conteg.com/userfiles/coolteg-g-xc-datasheet-conteg-en-71ec762e.pdf?v=cddcz6jdyg

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.