Technical guideFree to read2024

Discover ebm-papst for data centers

Original title Discover ebm-papst for Data Centers

ebm-papst

The ebm-papst data center brochure covers EC fans in CRAH, FanGrid, dry cooler and in-row cooling; 3-phase active PFC gives THD(I) ≤ 5% and power factor of 0.998, with a 37.6% cost difference in a 3 MW example.

On this page

Overview

The brochure opens by stating that cooling takes a large share of data center energy and that the maker's EC fans raise cooling capacity while reducing energy use. The first sections cover digitalization: visualization of standard parameters (temperatures, speed, power), preventive maintenance with vibration sensors that detect and suppress resonant speed ranges, and predictive maintenance in which sensor data on fan components gives remaining life.

The harmonic minimization section explains that speed-controlled drives inherently produce current harmonics, which cause problems with an inadequately sized supply. External passive filters are offered ready-matched for electronics from 4 to 12 kW with 5% to 9% THD(I) at rated output. Integrated 3-phase active PFC gives THD(I) ≤ 5% over a broad power range, about 2% at rated output, and power factor up to 0.998, keeping harmonics low at part load too.

A worked example for a 3 MW IT data center with 220 fans shows that standard fans require oversized transformers and generators because of voltage and current harmonics, while active PFC fans allow them to be downsized. The active PFC fan premium is €66,000, total system cost is €1,380,595 versus €2,213,095, a saving of €832,500 (37.6%); space, construction and cable and switchgear sizing are not included.

Later sections are by application: RadiPac centrifugal fans (RadiPac C Perform with over 4 percentage points higher efficiency, up to 20,000 m³/h and over 2,000 Pa), parallel multi-fan FanGrid modules (if one fan fails the others make up the airflow; fans placed too close influence each other and spacing should grow with airflow), CRAH/AHU, CRAC, dry coolers and chillers, AxiBlade, cooling towers, in-row cooling, MODBUS control and FanScout monitoring. The document is a manufacturer brochure.

Key points

  1. 3-phase active PFC: THD(I) ≤ 5% over a broad power range, about 2% at rated output, power factor up to 0.998.
  2. External passive filters are offered for 4 to 12 kW electronics with 5% to 9% THD(I) at rated output; at full load passive filter solutions are > 5% and integrated active PFC < 2%.
  3. 3 MW IT, 220-fan example: €1,380,595 with active PFC against €2,213,095 with standard fans; saving €832,500 (37.6%).
  4. The fan premium is €66,000; the saving comes from downsizing the transformer and generator.
  5. RadiPac C Perform: over 4 percentage points higher efficiency, up to 20,000 m³/h, over 2,000 Pa.
  6. In FanGrid, parallel fans provide redundancy; if one fails the others compensate for the missing airflow.
  7. Fans installed too close influence each other; spacing should increase as airflow grows.
  8. Preventive maintenance uses vibration sensors to detect critical speed ranges; predictive maintenance gives remaining life and automatic fault messages.
  9. Fan data tables list 3~380-480 V, 50/60 Hz and permitted ambient of -40 to +40 °C.

Using it in design

  • Ask for THD(I) at full and part load separately when selecting fan drives, and include harmonics in transformer, generator and UPS sizing.
  • Compare active PFC and passive filter options on installation space, wiring and filter power consumption (4 to 12 kW class for passive filters).
  • In multi-fan (FanGrid) design set fan spacing to avoid installation losses and calculate the airflow remaining after a single fan failure for N+1 redundancy.
  • For CRAH/AHU fan selection check the characteristic curve (Pa, m³/h) and the type's power and current against your operating point.
  • For BMS integration add MODBUS and fan monitoring data (temperature, speed, power, vibration) to the point list.

Who should read it

Mechanical engineers designing CRAH, AHU, dry coolers and FanGrids, and electrical designers assessing fan electronics and harmonics.

Document contents

  1. Digitalization and connectivity
  2. Visualization
  3. Preventive maintenance
  4. Predictive maintenance
  5. Harmonic minimization: external passive filters
  6. 3-phase active PFC
  7. RadiPac
  8. Use of EC fans in data centers
  9. FanGrid
  10. Computer room air handlers (CRAH) and air handling units (AHU)
  11. Computer room air conditioning (CRAC)
  12. Dry coolers, chillers, condensers, overhead heat exchangers
  13. AxiBlade
  14. Cooling tower
  15. InRow cooling
  16. Data center infrastructure management (MODBUS, FanScout)

Publication details

Authors
ebm-papst
Publisher
ebm-papst
Year
2024
Document number
2024-05 · FAF
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Public manufacturer document or page inspected. No document-specific redistribution permission established; retain metadata and original short summaries only.

Citation

ebm-papst (2024). Discover ebm-papst for Data Centers. ebm-papst. 2024-05 · FAF. https://ebmpapst.com/content/dam/ebm-papst/loc/americas/us/local-literature/Datacenter_Brochure.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.