A Comparative CFD Study of Two Air Distribution Systems with Hot Aisle Containment in High-Density Data Centers
Energies (MDPI AG) · Jinkyun Cho, Jesang Woo et al.
A CFD comparison for a Korean reference hall with ducted hot-aisle containment (HAC) and 100 racks (40 at 16 kW, 60 at 8.8 kW) served by six perimeter CRAHs: raised-floor (down-flow) supply versus hard-floor supply in which the CRAHs blow straight into open cold aisles.
CC BY 4.0: share with attribution
On this page
Overview
The study asks how the thermal performance of raised-floor and hard-floor air distribution differs with HAC in high-density data centres, and how that difference changes when a cooling unit fails. The IT room has 40 A-type racks at 16 kW and 60 B-type racks at 8.8 kW, 1830 mm cold aisles and 1220 mm hot aisles, ducted HAC, six CRAHs (234,000 m³/h total) supplying 15 °C and a 15 °C server delta-T. Both layouts were tested with all six units running and with the unit serving the high-density rows failed (N-1).
Under normal cooling, mean inlet temperatures were 16.5 °C (raised floor) and 16.9 °C (hard floor), but maximum inlet temperatures were 20.6 °C and 30.2 °C. Only 97% of racks met the ASHRAE recommended range on the hard floor, with failures in the racks nearest the CRAHs. Maximum rack recirculation ratio was 25.7% on the raised floor versus 50% on the hard floor, meaning some hard-floor racks received only half their required airflow. On the hard floor, supply velocities of 10 m/s or more persisted to the eighth rack position, versus the fourth with a raised floor, which explains the starvation of near-CRAH racks.
With one CRAH failed (N-1), the remaining five kept almost normal conditions on the raised floor. On the hard floor, more racks had recirculation above 40-50%, with inlet temperatures of about 26.1-30.4 °C. The authors report that raised-floor HAC improved air distribution efficiency by 28% over hard-floor HAC, equivalent to a 40% reduction in racks with recirculation above 20%.
Limits: the model is not validated against field measurements, and results depend on one reference hall geometry, CRAH layout and 15 °C supply. The conclusion is that HAC systems with a raised floor have higher cooling efficiency than those with a hard floor.
Key points
- IT room: 40 A-type racks at 16 kW and 60 B-type racks at 8.8 kW, 1830 mm cold aisles, 1220 mm hot aisles, ducted HAC, six CRAHs (234,000 m³/h total) supplying 15 °C, 15 °C server delta-T.
- Under normal cooling, mean inlet temperatures were 16.5 °C (raised floor) and 16.9 °C (hard floor); maximum inlet temperatures were 20.6 °C and 30.2 °C; only 97% of racks met the ASHRAE recommended range on the hard floor.
- Maximum rack recirculation ratio was 25.7% on the raised floor versus 50% on the hard floor; some hard-floor racks received only half their required airflow.
- On the hard floor, supply velocities of 10 m/s or more persisted to the eighth rack position, versus the fourth with a raised floor.
- With one CRAH failed (N-1), the remaining five kept almost normal conditions on the raised floor; on the hard floor more racks had recirculation above 40-50%, with inlet temperatures of about 26.1-30.4 °C.
- The authors report raised-floor HAC improved air distribution efficiency by 28% over hard-floor HAC, equivalent to a 40% reduction in racks with recirculation above 20%.
Using it in design
- In high-density HAC halls, prefer a raised floor to hard-floor supply; on a hard floor high-velocity jets can starve the racks nearest the CRAHs and draw hot air back into them.
- Run cooling unit failure (N-1) as a separate scenario in thermal verification and report recirculation ratio and maximum inlet temperature by rack.
- For hard-floor supply, add CRAH discharge velocity and rack distance (10 m/s jets persisting to the eighth rack) to the design check.
Who should read it
Cooling designers choosing between raised-floor and hard-floor air distribution for high-density data halls.
Document contents
- 1. Introduction
- 2. Methodology (2.1 Analytic Validity of CFD Simulation for Data Centers, 2.3 Basic Analysis Model: IT server room, server, hot aisle containment; 2.4 CFD Analysis Alternatives)
- 3. Numerical Analysis Results (3.1 Normal Cooling Conditions (ALT-1 and ALT-2): temperature distribution, airflow distribution, inlet temperature, recirculation ratio, operational net cooling power; 3.2 Cooling fault conditions: same measures)
- 5. Conclusions
Related standards
- ASHRAE TC 9.9 Thermal Guidelines for Data Processing Environments
Read the document
hac-air-distribution-comparison-2020.pdf
CC BY 4.0: share with attribution
The document is provided unaltered because its licence permits redistribution.
Publication details
- Authors
- Jinkyun Cho; Jesang Woo; Beungyong Park; Taesub Lim
- Publisher
- Energies (MDPI AG)
- Year
- 2020
- Volume
- 13
- Issue
- 22
- Pages
- 6147
- Document language
- English
- Source type
- Scientific
- Access
- Open licence (downloadable)
- Licence
- CC BY 4.0: share with attribution
- Licence evidence
- www.mdpi.com
Original licence note
PDF p.1: open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license.
Citation
Jinkyun Cho; Jesang Woo; Beungyong Park; Taesub Lim (2020). A Comparative CFD Study of Two Air Distribution Systems with Hot Aisle Containment in High-Density Data Centers. Energies (MDPI AG). 13(22), 6147. https://doi.org/10.3390/en13226147
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.