Engine and Generator Room Ventilation and Temperature Control
Original title Motor ve Jeneratör Odası Havalandırması ve Sıcaklık Kontrolü
İSKİD / Sönmez Global · Nejat Babür
A 2021 presentation by Nejat Babür of Sönmez Global for İSKİD: keep generator room summer temperature below 40 C, expect 15-18% capacity loss at 49 C, size the radiator fan for 125-175 Pa external pressure, and calculate ventilation airflow from the heat load.
On this page
Overview
The presentation lists three aims of generator-room ventilation: supply enough engine combustion air, remove heat from the engine and equipment, and exhaust gases and odours that may escape from the engine, fuel and exhaust. The critical design parameters are ambient temperature, ventilation airflow, air cleanliness (filtration), and outdoor airflow effects and placement; noise is excluded.
Temperature criteria: in summer the engine room temperature should stay below 40 C depending on the manufacturer's engine capacity and fuel type; electrical and electronic equipment is expected to run at up to 40 C and light fittings lose performance above it. In winter the minimum can fall to 5 C, but 10-15 C is recommended for health and comfort. On power loss, the optimum ambient is 8-23 C for gas turbines and 10-40 C for internal combustion engines; a 15-18% capacity drop is expected at 49 C and it accelerates above 50 C; gas turbines lose about 1% efficiency per 10 C above ISO conditions.
On the calculation side the total heat load is the sum of engine, generator, auxiliary equipment and heat recovery sources; room airflow follows from that heat, a permitted temperature rise of 8.5-12.5 K and air specific heat of 1.005 kJ/kgK, with combustion air flow and a routing factor added. The radiator fan is selected for at most 125-175 Pa external pressure; filters, sound attenuation and dampers must be included. The presentation also shows four ventilation orientation types, a faulty orientation, container ventilation (pressurised, extraction and combined), winter control and evaporative cooling.
Key points
- The aims of ventilation are combustion air, heat removal and exhausting leaked gases and odours.
- Summer engine room temperature is held below 40 C; electrical and electronic equipment runs at up to 40 C.
- In winter the minimum can fall to 5 C; 10-15 C is recommended for human health.
- Optimum ambient is 10-40 C for internal combustion engines and 8-23 C for gas turbines; 15-18% capacity loss at 49 C and a rapid drop above 50 C.
- Gas turbines lose about 1% efficiency per 10 C above ISO values, a 5-10% power output loss.
- The radiator fan is selected for at most 125-175 Pa external pressure; filter, sound attenuation and damper losses must be included.
- In the airflow calculation the permitted temperature rise is 8.5-12.5 K (ambient not above 40 C) and air specific heat is 1.005 kJ/kgK.
- Indirect evaporative cooling is about 65-70% effective and direct spray cooling about 90%; spray cooling adds 7% power on a gas turbine.
- Dampers should be quick acting and fail open; wind tunnel or CFD modelling can be used on large projects.
Using it in design
- Calculate the generator-room heat load by source (engine, alternator, auxiliaries, heat recovery) and set airflow from an 8.5-12.5 K temperature rise.
- Compare the radiator fan external pressure limit (125-175 Pa) with filter, silencer and damper losses.
- Where summer design temperature can exceed 40 C, especially 49 C, reflect the capacity derating in generator selection or evaluate evaporative cooling.
- Place intake and discharge louvres with regard to prevailing wind, air-cooled chillers and cooling towers, and HVAC outdoor air intake, avoiding re-ingestion of hot air.
- In winter, hold room temperature in range by adjusting fan speed and, with the engine stopped, using heaters.
Who should read it
Mechanical and electrical engineers designing generator room and container ventilation.
Document contents
- Importance of ventilation in the generator room
- Critical design parameters of the generator room
- Air cleaning and placement effects
- Temperature criteria in the generator room
- Relationship between temperature and power loss
- Ambient load and airflow calculation
- Ventilation models
- Container ventilation
- Temperature control in winter
- Cooling the engine room
- Temperature control in summer
- Example applications
Publication details
- Authors
- Nejat Babür
- Publisher
- İSKİD / Sönmez Global
- Year
- 2021
- Document number
- Kojenerasyon Sistemlerinde Soğutma ve Havalandırma semineri sunumu
- Document language
- Turkish
- Source type
- Expert / community
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Yayıncının açık PDF dosyası okundu. Açık erişim yeniden dağıtım izni anlamına gelmez; yalnızca künye, özgün kısa özet ve sayfa atıfları kaydedildi.
Citation
Nejat Babür (2021). Motor ve Jeneratör Odası Havalandırması ve Sıcaklık Kontrolü. İSKİD / Sönmez Global. Kojenerasyon Sistemlerinde Soğutma ve Havalandırma semineri sunumu. https://iskid.org.tr/wp-content/uploads/2021/06/NEJAT-BABUR_-Sunum_Motor-ve-Jenerator-Odalari-Havalandirma-ve-Sicaklik-Kontrolu-min.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.