Research paperFree to read2024

Experimental study of the performance of liquid cooling tank used for single-phase immersion cooling data center

Case Studies in Thermal Engineering (Elsevier BV) · Xueqiang Li, Shentong Guo et al.

A 2024 Case Studies in Thermal Engineering study of a GPU-server single-phase immersion tank: inlet coolant from 20 to 50 °C raises outlet by 30 °C but mean GPU temperature by only 21 °C.

On this page

Overview

The study stresses that when several servers share one single-phase immersion tank, coolant must reach each server evenly, so tank performance, especially temperature uniformity across GPUs, is decisive for operation. A liquid cooling tank was designed and the effects of coolant inlet temperature, flow rate and server load ratio were tested experimentally.

Lowering inlet temperature and GPU load ratio and raising flow rate all reduce average GPU temperature. Lower dynamic viscosity and higher thermal conductivity also help heat exchange. When inlet temperature rose from 20 to 50 °C, outlet temperature rose by 30 °C, while average GPU temperature rose by only 21 °C.

The designed tank showed good temperature uniformity, with deviation within 5 °C and square deviation in the range 1.0 to 1.5. The findings apply directly to tank sizing and coolant supply temperature selection.

Key points

  1. Inlet temperature from 20 to 50 °C raised outlet temperature by 30 °C.
  2. Over the same range, average GPU temperature rose by only 21 °C.
  3. Lower inlet temperature and load ratio and higher flow rate reduce average GPU temperature.
  4. Lower dynamic viscosity and higher thermal conductivity improve heat exchange.
  5. GPU-to-GPU temperature deviation stayed within 5 °C.
  6. Square deviation was in the range 1.0 to 1.5.

Using it in design

  • Use the observed ratio (about 21 per 30 over 20 to 50 °C) when choosing tank supply temperature.
  • Define an acceptance limit for server-to-server temperature deviation in the tank, such as 5 °C.
  • Make viscosity and thermal conductivity comparison criteria in coolant selection.
  • Verify per-server flow distribution at the tank inlet.

Who should read it

Engineers designing single-phase immersion tanks and setting coolant supply conditions.

Publication details

Authors
Xueqiang Li; Shentong Guo; Haiwang Sun; Shen Yin; Shengchun Liu; Zhiming Wang
Publisher
Case Studies in Thermal Engineering (Elsevier BV)
Year
2024
Document language
English
Source type
Scientific
Access
Free to read
Licence
CC BY 4.0: share with attribution
Original licence note

Publisher-deposited Crossref licence metadata: http://creativecommons.org/licenses/by/4.0/ (OpenAlex: cc-by); landing page blocks automated fetch, abstract read via Crossref/OpenAlex. Round 1 ingestion retains bibliographic metadata only; no local full text is redistributed.

Citation

Xueqiang Li; Shentong Guo; Haiwang Sun; Shen Yin; Shengchun Liu; Zhiming Wang (2024). Experimental study of the performance of liquid cooling tank used for single-phase immersion cooling data center. Case Studies in Thermal Engineering (Elsevier BV). https://doi.org/10.1016/j.csite.2024.105386

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.