Experimental study of the performance of liquid cooling tank used for single-phase immersion cooling data center
Case Studies in Thermal Engineering (Elsevier BV) · Xueqiang Li, Shentong Guo et al.
A 2024 Case Studies in Thermal Engineering study of a GPU-server single-phase immersion tank: inlet coolant from 20 to 50 °C raises outlet by 30 °C but mean GPU temperature by only 21 °C.
On this page
Overview
The study stresses that when several servers share one single-phase immersion tank, coolant must reach each server evenly, so tank performance, especially temperature uniformity across GPUs, is decisive for operation. A liquid cooling tank was designed and the effects of coolant inlet temperature, flow rate and server load ratio were tested experimentally.
Lowering inlet temperature and GPU load ratio and raising flow rate all reduce average GPU temperature. Lower dynamic viscosity and higher thermal conductivity also help heat exchange. When inlet temperature rose from 20 to 50 °C, outlet temperature rose by 30 °C, while average GPU temperature rose by only 21 °C.
The designed tank showed good temperature uniformity, with deviation within 5 °C and square deviation in the range 1.0 to 1.5. The findings apply directly to tank sizing and coolant supply temperature selection.
Key points
- Inlet temperature from 20 to 50 °C raised outlet temperature by 30 °C.
- Over the same range, average GPU temperature rose by only 21 °C.
- Lower inlet temperature and load ratio and higher flow rate reduce average GPU temperature.
- Lower dynamic viscosity and higher thermal conductivity improve heat exchange.
- GPU-to-GPU temperature deviation stayed within 5 °C.
- Square deviation was in the range 1.0 to 1.5.
Using it in design
- Use the observed ratio (about 21 per 30 over 20 to 50 °C) when choosing tank supply temperature.
- Define an acceptance limit for server-to-server temperature deviation in the tank, such as 5 °C.
- Make viscosity and thermal conductivity comparison criteria in coolant selection.
- Verify per-server flow distribution at the tank inlet.
Who should read it
Engineers designing single-phase immersion tanks and setting coolant supply conditions.
Publication details
- Authors
- Xueqiang Li; Shentong Guo; Haiwang Sun; Shen Yin; Shengchun Liu; Zhiming Wang
- Publisher
- Case Studies in Thermal Engineering (Elsevier BV)
- Year
- 2024
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- CC BY 4.0: share with attribution
Original licence note
Publisher-deposited Crossref licence metadata: http://creativecommons.org/licenses/by/4.0/ (OpenAlex: cc-by); landing page blocks automated fetch, abstract read via Crossref/OpenAlex. Round 1 ingestion retains bibliographic metadata only; no local full text is redistributed.
Citation
Xueqiang Li; Shentong Guo; Haiwang Sun; Shen Yin; Shengchun Liu; Zhiming Wang (2024). Experimental study of the performance of liquid cooling tank used for single-phase immersion cooling data center. Case Studies in Thermal Engineering (Elsevier BV). https://doi.org/10.1016/j.csite.2024.105386
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.