Research paperFree to read2025

Study of flow and heat transfer characteristics of tandem cold plates for data center cooling

Case Studies in Thermal Engineering (Elsevier BV) · Jinbo Li, Xue Luo et al.

A 2025 Case Studies in Thermal Engineering paper on two CPU cold plates in series: the narrow-channel plate cuts thermal resistance 29% but raises pressure drop 141%, and wide+narrow is the best pairing.

On this page

Overview

The study analyses the thermal-hydraulic performance of tandem cold plates in different combinations by numerical simulation and experiment, motivated by rising chip power density in data centres. LCP1 is the wide-channel plate and LCP2 the narrow-channel plate.

Narrow-channel LCP2 reduces thermal resistance (Rt) by 29% compared with LCP1 but increases pressure drop (ΔP) by 141%. The LCP1+2 order, wide plate first and narrow second, performs best: against two wide plates (LCP1+1) it lowers maximum chip temperature by 3.49 °C, cuts total thermal resistance by 15% and doubles the thermal performance index (TPI).

As inlet temperature or load rate rises, increasing flow rate reduces the temperature difference between the two CPUs and improves uniformity. Simulation deviates from experiment by no more than 2.32%. The results support pump head and flow sizing for multi-socket cold-plate servers.

Key points

  1. Narrow-channel plate: thermal resistance down 29%, pressure drop up 141% versus the wide-channel plate.
  2. The LCP1+2 order (wide then narrow) gave the best thermal performance.
  3. Versus LCP1+1: maximum chip temperature down 3.49 °C, total thermal resistance down 15%, TPI doubled.
  4. Higher flow rate reduces the CPU-to-CPU temperature difference as inlet temperature or load rises.
  5. Simulation matched experiment within 2.32%.

Using it in design

  • For multi-socket servers, consider a wide-then-narrow plate order when choosing tandem plates.
  • Carry the narrow channel's thermal gain and its pressure-drop increase of up to 141% into pump and CDU sizing.
  • Leave flow margin at high load and high inlet temperature to limit the socket-to-socket temperature difference.
  • Ask the cold-plate supplier for ΔP and Rt data in series operation.

Who should read it

Thermal engineers designing cold-plate server cooling and mechanical designers sizing pumps and CDUs.

Publication details

Authors
Jinbo Li; Xue Luo; Man Wang; Chaowei Chen; Chen Yang; Zheng Zhang; Gongming Xin
Publisher
Case Studies in Thermal Engineering (Elsevier BV)
Year
2025
Document language
English
Source type
Scientific
Access
Free to read
Licence
CC BY 4.0: share with attribution
Original licence note

Publisher-deposited Crossref licence metadata: http://creativecommons.org/licenses/by/4.0/ (OpenAlex: cc-by); landing page blocks automated fetch, abstract read via Crossref/OpenAlex. Round 1 ingestion retains bibliographic metadata only; no local full text is redistributed.

Citation

Jinbo Li; Xue Luo; Man Wang; Chaowei Chen; Chen Yang; Zheng Zhang; Gongming Xin (2025). Study of flow and heat transfer characteristics of tandem cold plates for data center cooling. Case Studies in Thermal Engineering (Elsevier BV). https://doi.org/10.1016/j.csite.2025.106590

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.