EMK-01 Power Quality Analyser User Manual (Turkish)

Original title EMK-01 Güç Kalitesi Analizörü Kullanım Kılavuzu

ENTES

ENTES's EMK-01 Class A analyser manual: it measures LV and MV network quality to EN 50160 per IEC 61000-4-30 Class A, with 40 kHz sampling, 25 us transients, 1 GB memory and a 144 x 144 mm panel format.

On this page

Overview

ENTES's 2020 Turkish manual covers installation, connection, settings and operation of the EMK-01 Class A power quality analyser. The device is designed to measure LV and MV network quality to EN 50160, and its measurement technology is stated to follow IEC 61000-4-30 Class A. It is used on 2-, 3- and 4-wire networks and in TN and TT systems. On safety it conforms to EN 61010-1 and has an overvoltage category of 600 V CAT III.

The measured parameters are tabulated: phase-neutral voltage 2-600 V, phase-phase voltage 4-1000 V (accuracy +/-0.1%), current 0.001-6 A (+/-0.1%), frequency 40-70 Hz (+/-10 mHz), power factor and cos phi (+/-1%), THD, voltage and current harmonics, interharmonics and harmonic groups (Class 1), short- and long-term flicker (Pst, Plt, Class A), low- and high-voltage events, voltage and current unbalance, K factor, active, reactive and apparent power and energy (Class 0.2) and temperature (+/-1 C). Transient resolution is 25 us and event resolution 10 ms.

The installation section asks for wall mounting in fixed-switchgear panels, vertically, with at least 60 mm clear above and below and 20 mm at the sides; connection sections cover earthing, supply, voltage and current measuring inputs, Ethernet (LAN, WiFi, NAT), USB, the temperature sensor and digital inputs. As a safety instruction, current transformer terminals must be short-circuited before the CT measuring circuit is opened. Settings cover connection type, nominal voltage, flicker, transformer ratios, communications (web server, Modbus TCP, FTP, RS485), NTP, e-mail, transients, sag/swell and alarms.

The technical specification gives supply of 24-60 V AC/DC or 85-250 V AC/DC (option), consumption under 8 VA, sampling rate of 40 kHz, 1 GB memory, 15 supply-interruption events, a 5.6 inch VGA TFT display, 2 inputs/outputs, 10/100 Mbit Ethernet, operating temperature of -25 to +70 C, size of 144 x 144 x 75 mm, weight of 1350 g and protection IP20 rear and IP54 front. Class A compliance is the manufacturer's claim; measurements should be assessed together with the datasheet accuracy figures.

Key points

  1. EN 50160 quality measurement; IEC 61000-4-30 Class A, IEC 61000-4-7, IEC 61000-4-15 and IEC 61557-12 are the related standards.
  2. TN/TT networks; 2-, 3- and 4-wire connection; phase-neutral 2-600 V, phase-phase 4-1000 V, current 0.001-6 A; 600 V CAT III.
  3. Accuracy: voltage and current +/-0.1%, frequency +/-10 mHz, active power +/-0.4%, active energy Class 0.2, temperature +/-1 C.
  4. Sampling rate 40 kHz; transient resolution 25 us; event resolution 10 ms; memory 1 GB; 15 supply-interruption events.
  5. Measurements: harmonics and interharmonics (Class 1), Pst/Plt flicker (Class A), sag/swell, unbalance, K factor.
  6. Communications: Ethernet 10/100, Modbus TCP, web server, FTP, RS485 Modbus RTU (9.6-115 kBd), USB Type B, e-mail and NTP.
  7. Supply 24-60 V or 85-250 V AC/DC; consumption under 8 VA; 2 digital inputs/outputs (24 VDC, 100 mA).
  8. Size 144 x 144 x 75 mm, panel cut-out 136.5 x 136.5 mm, 1350 g; IP54 front; operating -25 to +70 C.

Using it in design

  • Define the power quality measurement points (UPS input, output, PDU, generator) and choose the CT ratio against the device's 0.001-6 A input range.
  • For evidence gathering, write the EN 50160 reporting requirement and the IEC 61000-4-30 Class A claim into the specification separately, and have the claim backed by a certificate or test report.
  • In a data centre use harmonic, flicker and sag/swell events in UPS and generator transfer analysis; use the transient record (25 us) to study lightning and switching events.
  • Leave 60 mm above and below and 20 mm at the sides in the panel; panel cut-out is 136.5 x 136.5 mm.
  • Connect Modbus TCP and e-mail alarms to the BMS/DCIM and provide NTP time synchronisation on all devices.

Who should read it

Engineers designing power-quality monitoring in data-centre electrical systems, energy managers and commissioning teams.

Document contents

  1. Introduction
  2. Safety instructions
  3. Box contents
  4. Device description
  5. Measured parameters
  6. Installation
  7. Connection
  8. Device settings
  9. Operation
  10. Web interface
  11. Software update
  12. Technical specifications

Publication details

Authors
ENTES
Publisher
ENTES
Year
Year not stated
Document language
Turkish
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Public publisher source inspected. Free reading is not commercial redistribution permission; metadata and original short summaries only.

Citation

ENTES EMK-01 Güç Kalitesi Analizörü Kullanım Kılavuzu. ENTES. https://www.entes.com.tr/uploads/files/1700459459-EMK-01%20Turkish%20User%20Manual.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.