MPR-60S Series Network Analyser User Guide (ENTES, Turkish)

Original title MPR-60S Serisi Şebeke Analizörü Kullanım Kılavuzu

ENTES

ENTES MPR-60S is a panel-mounted network analyser measuring voltage, current, power, energy, demand and THD on 3P4W, 3P3W and Aron systems, with Modbus RTU (RS-485) and 1 MB of record memory.

On this page

Overview

The guide describes the use of ENTES's DSP-based universal network analyser series MPR-60S (variants MPR60S, -10, -20, -21, -40, -41). The unit shows all measured parameters on a 3.6-inch backlit LCD, measures on 3-phase plus neutral, 3-phase without neutral and Aron systems and lets current and voltage transformer ratios be set (voltage transformer 1 to 4000.0; current transformer 1 to 5000). Total harmonic distortion (THD) of voltage and current is shown on bars at the left of the screen and ESC switches between THD V and THD I.

The guide covers features, installation (dimensions, ambient conditions, electrical connection, PC connection), the Modbus RTU protocol (functions, cable, record tables, error codes, MPR-SW software, 16- and 32-bit data tables), the general menu (network, date and time, RS-485, pulse outputs, digital inputs, display, instantaneous values, energy, demand), parameters, formulas, analogue outputs and technical specifications. Safety warnings include an FF-type 1 A fuse, panel-only mounting and de-energising before connection. If phase order is reversed the screen warns and two phases are swapped.

Specifications: measurement inputs are voltage 1 to 300 VAC (L-N), 2 to 500 VAC (L-L) and current 0.005 to 5.5 A; accuracy is 0.5% for voltage and current, 1% for active power and 2% for reactive and apparent power (±2 digits); measurement class CAT III; demand period 15 minutes; Modbus RTU 1200 to 38400 bps, address 1 to 247; data logging of 28 parameters and 15,000 rows; energy log of 1,000 rows (every 15 minutes). Two relay outputs (5 A, 1250 VA) and, on various models, pulse outputs, digital inputs and 0/4-20 mA or 0/2-10 V analogue outputs are provided. Operation is -5 to +50 °C, enclosure IP54 and weight 0.75 kg.

Key points

  1. Measured connection types: 3P4W, 3P3W and Aron; voltage transformer ratio 1 to 4000.0, current transformer ratio 1 to 5000.
  2. Measurement inputs: 1 to 300 VAC (L-N), 2 to 500 VAC (L-L), 0.005 to 5.5 A; CAT III.
  3. Accuracy: voltage and current 0.5% ±2 digits; active power 1%; reactive and apparent power 2%.
  4. Energy and demand: demand period 15 minutes; energy range 0 to 99,999,999 kWh/kVArh.
  5. Communication Modbus RTU (RS-485), 1200 to 38400 bps, address 1 to 247; parity none, even or odd.
  6. Data log: 28 parameters, 15,000 rows; energy log 1,000 rows; 1 MB internal memory.
  7. Two relay outputs (2 NO, 5 A, 1250 VA); 0/4-20 mA analogue output on MPR60S-40/41, 0/2-10 V on -20/21; active/reactive energy pulse outputs on MPR60S and -21/41.
  8. Operation -5 to +50 °C; enclosure IP54, terminals IP00; weight 0.75 kg; FF-type 1 A fuse.

Using it in design

  • For power-quality monitoring, connect the THD V and THD I view and the Modbus RTU tables (16- and 32-bit) to the energy monitoring system.
  • Add the measurement accuracy (power 1%, reactive 2%) to the uncertainty of energy-efficiency and PUE calculations.
  • Set the current transformer ratio (1 to 5000) and voltage transformer ratio (1 to 4000) to the actual metering point of the panel.
  • Use the relay outputs for threshold alarms; check the phase-order warning before connecting.
  • Use demand (15 minutes) and energy records in facility capacity planning to track peak demand.

Who should read it

Electrical engineers and operations teams measuring energy and power quality in data-centre and facility electrical panels.

Document contents

  1. Features
  2. Installation
  3. Modbus RTU protocol
  4. General menu
  5. Technical specifications
  6. Standards and explanations

Publication details

Authors
ENTES
Publisher
ENTES
Year
Year not stated
Document number
A5531b
Document language
Turkish
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Public publisher source inspected. Free reading is not commercial redistribution permission; metadata and original short summaries only.

Citation

ENTES MPR-60S Serisi Şebeke Analizörü Kullanım Kılavuzu. ENTES. A5531b. https://www.entes.com.tr/uploads/files/1679049681-mpr6x-kullanim-kilavuzu-tr-r3.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.