Technical guideFree to readYear not stated

Horizontal and Vertical Firefighting Booster Set: User's Manual

Original title Yatay ve Dik Pompalı Yangın Hidroforu: Kullanım Kılavuzu

ETNA

Etna's May 2020 bilingual manual describing a firefighting booster set with jockey, electric main and diesel pumps, its staged start logic, the 1.5 to 5 bar pressure range, and installation and connection rules.

On this page

Overview

The manual gives basic information for installing, using and maintaining horizontal and vertical firefighting booster sets with an alternative (diesel) power supply for power failure, intended for firefighting systems in villas, apartments, fuel stations, warehouses and small industrial plants. The text is in Turkish and English side by side.

The product is defined as follows: the horizontal set has one diesel, one electric and one jockey pump; the vertical set has one diesel and one electric pump. Pumps come as a set with suction and discharge manifolds, vibration absorbing joints, ball valves, check valves, independent pressure switches and a control panel with a weekly test timer. A malfunction triggers a visual and audible alarm.

The operating principle is staged: when pressure drops the jockey pump starts first; if it cannot meet demand and pressure keeps falling the main pump starts; with greater demand the diesel pump also starts automatically. The schematic shows pressure between 1.5 bar and 5 bar, with the set installed between a reserve tank and the user lines and drawing from the tank rather than the mains.

It is a short product manual defined for residential and small commercial use and makes no claim of compliance with a standard such as NFPA 20. For large data centre fire pump design, manufacturer selection and standard compliance must be verified separately.

Key points

  1. The horizontal set has 1 diesel, 1 electric and 1 jockey pump; the vertical set has 1 diesel and 1 electric pump.
  2. Start order: jockey pump first, main pump if pressure keeps falling, diesel pump if demand increases.
  3. The schematic connection shows a pressure range of 1.5 bar to 5 bar.
  4. The set comes with manifolds, joints, ball valves, check valves, independent pressure switches and a control panel with a weekly test timer.
  5. The diesel pump uses two 12 V DC 36 A batteries; without the neutral connection the battery will not charge.
  6. The exhaust outlet is directed outside the building and the exhaust pipe insulated to avoid injury.
  7. The set stands on a level concrete floor on 4 rubber supports; larger industrial models are bolted and doweled; it must be protected from weather and frost.
  8. Negative suction is not recommended; a float switch gives dry-running protection.

Using it in design

  • Set and document start and stop pressure stages for the jockey, electric main and diesel pump (for example the 1.5 bar lower limit) consistent with the hydraulic calculation.
  • Prepare a pump room layout that shows the diesel exhaust routed outdoors and the location of fuel tank, battery and charger.
  • Include positive suction (tank level above the pump) and a float switch arrangement with dry-running protection.
  • Tie the weekly test timer to the building maintenance schedule and alarm notification.
  • Assess separately whether a data centre needs a fire pump set meeting a recognised standard instead of this residential and small commercial set.

Who should read it

Mechanical engineers selecting small and medium fire pump sets and commissioning and maintenance teams.

Document contents

  1. General
  2. Applications
  3. Product features
  4. Operational principles
  5. Handling
  6. Installation
  7. Schematic booster set connection method
  8. Suction
  9. Electrical connections
  10. Diesel engine
  11. Priming
  12. Operating the diesel pump and battery and panel components

Publication details

Authors
ETNA
Publisher
ETNA
Year
Year not stated
Document language
Turkish
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Official publisher material inspected. No document-specific commercial redistribution permission established; retain metadata and original short summaries only.

Citation

ETNA Yatay ve Dik Pompalı Yangın Hidroforu: Kullanım Kılavuzu. ETNA. https://www.etna.com.tr/uploads/source/KullanimKlavuzu/etna_YATAY_KO_KullanimKlavuzu05_2020.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Standards pre-assessment in SoSo CAD

Run TS EN 50600 and Tier pre-checks on the model, with missing inputs and items for engineering review listed separately.

Selected rule packs and findings in the SoSo CAD standards panel

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.