TFD-1170 Intelligent Addressable Natural Gas and LPG Detector Installation and User Manual (Rev. 07)

Original title TFD-1170 Akıllı Adresli Doğal Gaz ve LPG Dedektörü: Kurulum ve Kullanım Kılavuzu

Teknim Elektronik

Teknim Rev. 07 manual dated 30/07/2026: the TFD-1170 is a 24 V externally powered natural gas and LPG detector for addressable fire alarm loops, to TS EN 50194-1, alarming at 12% LEL natural gas and 7% LEL LPG.

On this page

Overview

The manual gives installation, wiring, test and use information for the Teknim TFD-1170 addressable natural gas and LPG detector. The device connects to Teknim addressable fire detection systems and runs on a 24 V external supply; it works only with TFP-121x, TFP-211x, TFP-213x and TFP-221x addressable fire alarm panels. It is addressed with the TFCM-1801 programming module, and scenarios built in the system configuration software can have output modules control optional devices such as solenoid valves.

The specification table lists TS EN 50194-1, device type A, protection class IPX2D, 3 minute stabilisation time, alarm level of 12% LEL for natural gas and 7% LEL for LPG, 85 dB internal buzzer, operating range -10 to +55 degrees C, up to 95% RH and a 5 year device life. Loop input is 18 V to 32 V; the sensor supply is 24 V with 50 mA quiescent and 60 mA maximum alarm current. LED and buzzer codes distinguish alarm, sensor fault, start-up and normal operation.

Mounting guidance selects location by gas density: ceiling for natural gas, near floor for LPG. The detector must be at least 1.5 m horizontally from the gas source, where gas is most likely to accumulate, and at least 1.5 m from ventilation or extractors. Test uses a suitable natural gas or LPG test spray, and the detector alarms within 10 seconds. Frequent testing shortens life and lowers sensitivity. The manual recommends maintenance twice a year, lists actions in an alarm and names substances such as alcohol and thinner that cause false alarms.

Key points

  1. Standard TS EN 50194-1, device type A; alarm concentration is set according to EN 50194-1 criteria.
  2. Alarm level: 12% LEL for natural gas and 7% LEL for LPG.
  3. In alarm the 85 dB internal buzzer and red, yellow and green LEDs operate; a yellow LED indicates sensor fault.
  4. Supplies: loop input 18 V to 32 V, sensor on 24 V external supply; quiescent current 50 mA (24 V), maximum alarm current 60 mA.
  5. Protection class IPX2D, operating temperature -10 to +55 degrees C, up to 95% RH.
  6. Stabilisation time is 3 minutes; with test gas the detector alarms within 10 seconds.
  7. Device life is 5 years; periodic maintenance twice a year is recommended.
  8. The product works only with Teknim TFP-121x, TFP-211x, TFP-213x and TFP-221x addressable fire alarm panels; addressing uses the TFCM-1801 module.
  9. Mounting: at least 1.5 m horizontally from the gas source and from ventilation and extractors; ceiling for natural gas, floor level for LPG.

Using it in design

  • In auxiliary areas with natural gas or LPG (for example boiler, generator or kitchen zones), include the detectors in the addressable fire alarm loop and add the 50 mA sensor quiescent current to the loop current budget.
  • Set detector height by gas type: ceiling for natural gas, near floor for LPG; keep at least 1.5 m from ventilation openings.
  • In alarm scenarios, link gas shutoff through an output module and solenoid valve in the fire alarm system software matrix.
  • Put the 5 year device life into the replacement plan and twice-yearly maintenance into the operating schedule; keep functional gas testing limited.
  • State panel compatibility in the specification: this detector works only with the listed Teknim panel series.

Who should read it

Electrical and fire detection designers adding gas detection to an addressable fire alarm system, and technicians who commission and maintain it.

Document contents

  1. General information
  2. Technical specifications
  3. LEDs, buzzer and test button
  4. Device location selection, mounting and connection
  5. Terminals
  6. Test
  7. What to do in an alarm condition
  8. Failure situations requiring service, maintenance and cleaning
  9. Transportation, human health and environment

Publication details

Authors
Teknim Elektronik
Publisher
Teknim Elektronik
Year
2026
Document number
HM.Z.KLV.4534, Rev. 07
Document language
Turkish
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Official public manufacturer documentation inspected. No redistribution permission established. Metadata and original brief summaries only; local downloads are research evidence, not a redistribution package.

Citation

Teknim Elektronik (2026). TFD-1170 Akıllı Adresli Doğal Gaz ve LPG Dedektörü: Kurulum ve Kullanım Kılavuzu. Teknim Elektronik. HM.Z.KLV.4534, Rev. 07. https://www.teknim.com/Uploads/Document/dcb8bd08-19fc-4df0-bccb-6d14e0915205.pdf?v-637172839758011380=

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Standards pre-assessment in SoSo CAD

Run TS EN 50600 and Tier pre-checks on the model, with missing inputs and items for engineering review listed separately.

Selected rule packs and findings in the SoSo CAD standards panel

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.