Electric Fire Pump Controllers, GFX Model Installation and Maintenance Manual (V2024.04)
Original title Elektrikli Yangın Pompası Kontrolörleri: GFX Modeli İçin Kurulum ve Bakım Kılavuzu
Tornatech
Tornatech manual V2024.04 (Turkish edition): the GFX electric fire pump controller is IP 55 for 4 to 40 degrees C ambient, live parts at least 305 mm above the floor, and wiring sized for at least 125% of motor full load current.
On this page
Overview
The manual describes installation, commissioning and maintenance of the Tornatech GFX electric fire pump controller, which runs an electric-motor-driven fire pump. The controller starts the pump manually from a local button or automatically by sensing a pressure drop in the fire suppression system; it is supplied with a pressure transducer. The pump can be stopped manually from the local stop button or automatically after a field-programmable timer. Technical data include 50/60 Hz, 4 to 40 degrees C ambient, altitude up to 2,000 m, 5 to 80% relative humidity, pollution degree 3, IP 55 and 10 W standby consumption.
The installation section gives placement and connection rules. The controller should be as near the motor as practicable and in its line of sight, and protected from water escaping from the pump. Live parts must be at least 12 in (305 mm) above floor level, and working clearances must follow NFPA 70 Article 110 or local code. Wall mounting needs at least four anchors and at least 6 in (152 mm) clearance around the unit. System pressure connects through a 1/2 in NPT port with a sensing line per NFPA 20. Power wiring must comply with NFPA 20 and NFPA 70 Article 695 and is typically sized for at least 125% of motor full load current.
The operation section describes start methods (automatic, manual, remote manual, remote automatic sprinkler valve start, emergency, sequential and test) and stop methods (manual, automatic, emergency). Automatic stop is off by default, needs authority having jurisdiction approval and, when enabled, stops the motor 10 minutes (adjustable) after pressure recovers. Sequential start prevents simultaneous starting of multiple pumps. Commissioning is done only by an authorised field acceptance provider. Maintenance calls for at least one test start cycle per month and at least one preventive maintenance per year under NFPA 25; the document is supported over a 10-year service life.
Key points
- Technical data: 50/60 Hz, 4 to 40 degrees C standard ambient, altitude up to 2,000 m, 5 to 80% RH, pollution degree 3, IP 55, 10 W standby.
- Live parts must be at least 305 mm (12 in) above the floor; wall mounting needs 152 mm (6 in) clearance around the unit and at least four anchors.
- The controller is installed indoors, not designed for outdoor use, and placed as near the motor as practicable and in its line of sight.
- Power wiring is typically sized for at least 125% of fire pump motor full load current and follows NFPA 20 and NFPA 70 Article 695.
- System pressure connects through a 1/2 in NPT male port on the left outer side; the sensing line is piped per NFPA 20.
- Start methods: automatic (pressure drop), manual, remote manual, remote automatic (sprinkler valve), emergency, sequential and test.
- Automatic stop is disabled by default; if enabled with authority approval it stops the motor 10 minutes (adjustable) after pressure recovers.
- Emergency stop is always possible through the main disconnect on the door.
- Maintenance: at least one test start cycle per month and one preventive maintenance per year (NFPA 25); the document is supported over a 10-year service life.
Using it in design
- In the fire pump room layout, place the controller near the motor, protected from leaks and with live parts at least 305 mm above the floor; set flood allowance in basement pump rooms accordingly.
- Size the supply cable for 125% of motor full load current and state compliance with NFPA 20 and NFPA 70 Article 695 (or local code) in the specification.
- In multi-pump arrangements, set sequential start delays together with the generator pick-up scenario.
- Obtain authority approval before enabling the automatic stop function, which is off by default.
- Add the monthly test start and annual preventive maintenance steps to the maintenance programme and the commissioning acceptance checklist.
Who should read it
Electrical and mechanical engineers and technicians who select, install, commission and maintain electric fire pump controllers in data centres and other facilities.
Document contents
- Important safety information
- Introduction
- Technical data
- Installation (storage, environment, EMC, handling, FCC and RSS)
- Location and mounting (floor, wall)
- System pressure and electrical connections
- Operator interface
- Starting and stopping methods
- Commissioning
- Maintenance
- Patents
Publication details
- Authors
- Tornatech
- Publisher
- Tornatech
- Year
- 2024
- Document number
- V2024.04
- Document language
- Turkish
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Official publisher material inspected. No document-specific commercial redistribution permission established; retain metadata and original short summaries only.
Citation
Tornatech (2024). Elektrikli Yangın Pompası Kontrolörleri: GFX Modeli İçin Kurulum ve Bakım Kılavuzu. Tornatech. V2024.04. https://www.tornatech.com/pdf/Manuals/tr/GFX-TR.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.