Maxlogic Intelligent Addressable System Smoke Damper Module (ML-1356, ML-1357, ML-1358)
Original title Maxlogic Akıllı Adresli Sistem Duman Damper Modülü: Satış Destek Dokümanı
Mavili Elektronik A.Ş.
A Mavili sales support document: an EN 54-18 addressable module with two position feedback inputs and one damper output controls smoke dampers; travel time is set to 60, 90, 150 or 270 seconds.
On this page
Overview
The document presents the ML-1356, ML-1357 and ML-1358 smoke damper modules of the Maxlogic addressable fire system. The module has two damper position-monitoring inputs and one damper output; damper open, closed and fault states are monitored and controlled. Remote control inputs and on-module Open and Close buttons allow manual control, and the module is programmed through cause-and-effect scenarios.
Models differ by damper supply voltage: 24 V DC for ML-1356, 24 V AC for ML-1357 and 230 V AC for ML-1358. Each comes in a short-circuit isolator (SCI) version. Modules comply with EN 54-18 and the isolator versions also with EN 54-17. Damper control output capacity is 5 A and operating voltage from the loop is 18-33 V DC.
The system overview tabulates normal and fire states: normally fresh air (AHU) and exhaust (EF) ducts are open, smoke exhaust (DEF) and pressurisation (PF) ducts closed. In fire, the AHU closes in the fire zone, DEF and EF open and stairs are pressurised; other zones keep AHU open and close DEF and EF.
It is a product sales support document with panel-specific display messages and model data. For data centre designers, its value is showing how smoke dampers connect to the fire panel with monitored feedback.
Key points
- The module has 2 damper position inputs and 1 damper output and monitors and controls open, closed and fault states.
- Damper voltage is 24 V DC for ML-1356, 24 V AC for ML-1357 and 230 V AC for ML-1358; control output capacity is 5 A.
- It complies with EN 54-18; short-circuit isolator (SCI) models also comply with EN 54-17.
- Damper travel time is set to 60, 90, 150 or 270 seconds (tolerance 30 s); a damper that does not move within it is shown as a fault.
- Open and short circuit faults on the damper output, remote input and position input are detected and shown at the panel by zone and address.
- Opening the module cover is reported as a damper fault.
- In the isolator model, current through a short circuit is below 45 mA.
- In the fire zone AHU closes, DEF and EF open and the pressurisation duct (PF) opens; other zones keep AHU open and DEF and EF closed.
- Level 1 and level 2 delay assignments let dampers open and close with a delay.
Using it in design
- Connect smoke dampers to the fire panel through addressable modules with open, closed and fault feedback, and set travel time (60 to 270 s) to the damper actuator.
- Write the AHU, DEF, EF and PF damper state table for fire zone and other zones into the cause-and-effect matrix.
- Check actuator load against supply voltage (24 V DC, 24 V AC, 230 V AC) and the 5 A output capacity.
- Add short-circuit isolator modules on the loop and halogen-free cable to the specification.
- Confirm damper fault messages (output, remote input, position input) are reflected in maintenance procedure and monitoring software.
Who should read it
Electrical and mechanical engineers designing fire alarm and smoke control systems and commissioning teams.
Document contents
- Product features
- Indicators
- Models
- Technical specifications
- Technical specifications for the short-circuit isolator model
- Overview of system operation (normal state, fire state)
- Panel status indications and fault messages
Related standards
- EN 54-18
- EN 54-17
Publication details
- Authors
- Mavili Elektronik A.Ş.
- Publisher
- Mavili Elektronik A.Ş.
- Year
- Year not stated
- Document number
- MM.SDD.503 Rev.No:3; ML-1356.X / ML-1357.X / ML-1358.X
- Document language
- Turkish
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Public publisher source inspected on 2026-11-16. No document-specific redistribution permission established. Revision identified but publication year not established.
Citation
Mavili Elektronik A.Ş. Maxlogic Akıllı Adresli Sistem Duman Damper Modülü: Satış Destek Dokümanı. Mavili Elektronik A.Ş.. MM.SDD.503 Rev.No:3; ML-1356.X / ML-1357.X / ML-1358.X. https://mavili.com.tr/Belgeler/StsDstkDkmn/ML-135X.X_sdd.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.