AUE, AUD, AUED Series Fire-Fighting Booster Sets: User Manual
Original title AUE, AUD, AUED Serisi Yangınla Mücadele Hidroforları: Kullanım Kılavuzu
Teknopomp
Teknopomp's 24-page manual covering installation and commissioning of electric and diesel fire pump sets, and the automatic operation and weekly test logic of an NFPA 20 compliant diesel panel (two batteries, 200 fault records).
On this page
Overview
The manual is written for users of Teknopomp AUE, AUD and AUED series fire booster sets. Sections cover safety precautions, warranty, factory testing, safe operating conditions, installation rules, technical information, the electrical control panel, starting and stopping, fault causes and remedies, and the diesel fire panel and its automatic operation.
The installation rules contain practical design criteria: the set goes in an enclosed room, away from heat sources such as boilers and burners, with walking space for maintenance; if fed from a tank, the horizontal distance between tank and set is at most 10 metres; the suction line is at least equal to or one size larger than the pump inlet; the set is not connected directly to the mains, with valves at inlet and outlet, a check valve at the outlet and flexible connections.
The diesel panel section states NFPA 20 compliance. The panel runs on 220 V AC mains and two 12 V DC batteries, two rectifiers keep batteries charged, and dry-contact outputs suit building automation. The system treats a pressure drop as a fire call and cranks from battery 1, then battery 2 if no run signal arrives. The automatic test runs on one or two real-time days a week, tries up to 6 starts, uses a bypass solenoid valve during the test and records the last 200 faults.
The document is a manufacturer manual with series-specific settings and LED descriptions, an operating instruction rather than a general standard. Its value for designers is showing how fire pump control interfaces (dry contacts, test logic, battery supervision) connect to building automation and operating procedure.
Key points
- The diesel fire panel is described as compliant with NFPA 20 and runs on 220 V AC mains and two 12 V DC batteries.
- Two rectifiers keep the batteries continuously charged; the panel has a voltmeter and ammeter for each battery.
- Dry-contact outputs suit building automation; run and fault states are monitored on a graphic-display PLC.
- A pressure drop is accepted as a fire call: the panel cranks from battery 1 first, then battery 2 if no run signal arrives.
- The automatic test is set to run on 1 or 2 real-time days per week; it tries 6 starts and raises a fault and stops if the engine does not run.
- During the test a 12 V DC bypass solenoid valve bypasses the water; after the test period the engine runs on for the set delay, then stops.
- The panel stores information on the last 200 faults.
- In a fire call, low oil pressure and high temperature alarms do not stop the engine; only overspeed does.
- If battery voltage drops to 10 V or below the system cannot start; in long outages voltage must be watched or the test used to recharge.
Using it in design
- Define the diesel fire pump panel's dry-contact outputs (running, fault, battery) for the building management system and fire panel in the specification.
- Coordinate the weekly automatic test day and time with data centre maintenance windows and write the bypass line opening during test into the operating procedure.
- Plan the pump room enclosed, free of frost and heat sources, with maintenance space; check the tank-to-pump horizontal distance (at most 10 m) and suction line size.
- Include battery supervision and the long mains outage case (10 V limit) in the emergency operating plan.
- Assess pump set noise level (referenced to ISO 3744) and placement for room acoustics and personnel safety.
Who should read it
Mechanical and fire engineers designing fire pump rooms and the maintenance and commissioning teams that run them.
Document contents
- Important safety precautions
- General: warranty and testing
- Safe operating conditions
- Installation rules
- Technical information
- Electrical control panel features
- Starting and stopping the pump
- Fault causes and remedies
- Diesel fire panel features
- Description of the automatic system
- Manual operation
- Panel settings pages and general fault information
Publication details
- Authors
- Teknopomp
- Publisher
- Teknopomp
- Year
- Year not stated
- Document language
- Turkish
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Official public manufacturer documentation inspected. No redistribution permission established. Metadata and original brief summaries only; local downloads are research evidence, not a redistribution package.
Citation
Teknopomp AUE, AUD, AUED Serisi Yangınla Mücadele Hidroforları: Kullanım Kılavuzu. Teknopomp. https://www.teknopomp.com/wp-content/uploads/2021/06/Yangin-Grubu-Kilavuzu.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
