ML-1180 Maxlogic Intelligent Addressable Aspirating Smoke Detector
Original title ML-1180 / ML-1180.SCI Akıllı Adresli Aktif Hava Örneklemeli Hassas Duman Dedektörü: Satış Destek Dokümanı
Mavili Elektronik A.Ş.
A Mavili sales support document: the EN 54-20 Class A, B and C compliant ML-1180 offers 150 m and 60 holes on a single pipe, 0.0001 obs/m resolution and 4 alarm levels, connected to an addressable panel.
On this page
Overview
The document presents the ML-1180 and short-circuit isolator ML-1180.SCI aspirating smoke detectors. The unit monitors ambient air continuously, raises an alarm when the smoke level passes a threshold, and aims to separate dust and other false alarm sources from smoke with mathematical modelling. It is stated to comply with EN 54-20 (Class A, B and C) and EN 54-17 and works with MAXLOGIC addressable panels.
Technical values set the piping design: 150 m and at most 60 holes on a single pipe, 250 m total on two pipes (125 m and 30 holes each), 400 m on four pipes (100 m and 15 holes each). The sampling pipe is 21 mm inside and 25 mm outside diameter. Measuring range is 0.005 to 20 obs/m, resolution 0.0001 obs/m, detection uses light scattering and fan speed is adjustable from 1 to 10.
There are four alarm levels (Alert, Pre-Alarm, Fire 1, Fire 2), each with a delay of 0 to 255 seconds. The unit has 4 programmable alarm relays and 2 fault relays (100 mA, 30 V); up to 127 detectors can share a loop. For conventional connection, a 470 ohm alarm resistor and 6K8 ohm end-of-line resistor are added. Supply is 24 V DC nominal with a maximum quiescent current of 925 mA.
It is a product sheet; hole counts and pipe lengths by sensitivity class are device-specific. In a real design the pipe network, sensitivity and transport time must be verified with the manufacturer's design tool and EN 54-20 requirements.
Key points
- Complies with EN 54-20 Class A, B and C sensitivity classes and EN 54-17; working range 0 to 20 obs/m, resolution 0.0001 obs/m.
- Piping: single pipe 150 m and at most 60 holes; two pipes 250 m (125 m and 30 holes each); four pipes 400 m (100 m and 15 holes each).
- Sampling pipe 21 mm inside and 25 mm outside diameter; conduit per EN 61386-1 at least Class 1131.
- Four alarm levels: Alert, Pre-Alarm, Fire 1, Fire 2; each can have a separate delay of 0 to 255 seconds.
- Alarm 1 range 0.010 to 2.0 obs/m, Alarm 2 range 0.020 to 20.0 obs/m, Alert and Pre-Alarm 0.005 to 2.0 obs/m.
- Supply nominal 24 V DC (18 to 30 V); quiescent current at most 925 mA, power 22.2 W (fan speed 10).
- Operating temperature -10 to +55 degrees C, IP30, weight 3.8 kg; up to 127 detectors on one loop.
- Optional accessories include heaters, dirt and dust filters, a magnetic filter and water traps.
Using it in design
- Design the sampling pipe network to single, dual or four-pipe limits (150, 250, 400 m and hole counts) and verify transport time with the vendor tool.
- Set Alert and Pre-Alarm thresholds for high sensitivity in the data hall and tie Fire 1 and Fire 2 to the suppression scenario, writing the delay assigned to each level.
- Map alarm and fault relay outputs to the panel and suppression control; remember the 470 ohm and 6K8 ohm resistors in conventional connection.
- Choose an EN 54-4 and EN 54-14 compliant power supply and budget total detector power (about 22 W each).
- Add filters, heaters and water traps to the specification for dusty or humid environments.
Who should read it
Fire alarm engineers designing data centre aspirating smoke detection and commissioning teams.
Document contents
- General features
- Technical specifications
- Models
- Optional accessories
- Piping system (single, dual and four-pipe designs)
- Electrical connections
- Remote control inputs, zone inputs and dry contact relay outputs
- Loop and power supply connection diagrams
Related standards
- EN 54-20
- EN 54-17
Publication details
- Authors
- Mavili Elektronik A.Ş.
- Publisher
- Mavili Elektronik A.Ş.
- Year
- Year not stated
- Document number
- MM.SDD.595 Rev.No:2; 9 pages
- Document language
- Turkish
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Public publisher source inspected on 2026-11-16. No document-specific redistribution permission established. Document year not stated. Sensitivity units are inconsistently written between the overview and technical table; no sensitivity default is imported.
Citation
Mavili Elektronik A.Ş. ML-1180 / ML-1180.SCI Akıllı Adresli Aktif Hava Örneklemeli Hassas Duman Dedektörü: Satış Destek Dokümanı. Mavili Elektronik A.Ş.. MM.SDD.595 Rev.No:2; 9 pages. https://mavili.com.tr/Belgeler/StsDstkDkmn/ML-1180_sdd.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.