Simulation Study of Influencing Factors of Immersion Phase-Change Cooling Technology for Data Center Servers
Energies (MDPI AG) · Tiantian Zhao, Rongfeng Sun et al.
This study combines CFD (boiling and condensation) with a validation experiment to examine two-phase immersion cooling of server chips: the fluorinated fluid HFE-7100 boils on the chip and condenses on a water-cooled condenser plate.
CC BY 4.0: share with attribution
On this page
Overview
Immersion phase-change cooling uses the latent heat of the cooling liquid by putting it in direct contact with the heat-generating chip, and can meet the cooling needs of today's high-heat-flux data centres. A cited reference states that above 100 W/cm² heat flux, air cooling and heat-pipe cooling are no longer applicable. The study varies condenser cooling-water inlet temperature and velocity and the spacing between server boards, tracking chip temperature, temperature spread and a uniformity coefficient.
FC-40 and FC-77 have boiling points too high to boil while the chip stays below its 85 °C safe limit, and HFE-7000 boils even at idle, raising condenser water-pump energy, so all three were excluded and HFE-7100 was used. Against experiment at 20 °C cooling-water inlet and 1 m/s, the model's steady chip surface temperature differed by no more than 2.5 °C. Flow-rate cases used a cooling-water inlet temperature of 24 °C with velocities of 0.6, 0.8, 1 and 1.2 m/s; steady chip temperature was only weakly affected by flow rate, while time to stabilise fell as flow increased.
Increasing board spacing from 5 mm to 15 mm cut maximum temperature by 5.06%, reduced temperature difference from 16.5 °C to 11 °C and lowered the uniformity coefficient by 52.6%. Going from 15 mm to 25 mm spacing reduced maximum temperature by only 1.07%, with temperature difference falling from 11 °C to 10.3 °C, so 15 mm was judged optimal. Lower water inlet temperature mainly lowers steady chip temperature, while higher flow mainly shortens the transient.
Limits: a single fluid (HFE-7100), specific power conditions and a small-scale model; results do not transfer directly to other fluids or server geometries. Boiling point is decisive in fluid selection: a fluid is needed that boils below the chip safe limit but does not boil continuously at idle.
Key points
- FC-40 and FC-77 have boiling points too high to boil while the chip stays below its 85 °C safe limit; HFE-7000 boils even at idle; all three were excluded and HFE-7100 was used.
- Against experiment at 20 °C cooling-water inlet and 1 m/s, the model's steady chip surface temperature differed by no more than 2.5 °C.
- Flow-rate cases used a cooling-water inlet temperature of 24 °C with velocities of 0.6, 0.8, 1 and 1.2 m/s; steady chip temperature was only weakly affected by flow rate, while time to stabilise fell as flow increased.
- Increasing board spacing from 5 mm to 15 mm cut maximum temperature by 5.06%, reduced temperature difference from 16.5 °C to 11 °C and lowered the uniformity coefficient by 52.6%.
- Going from 15 mm to 25 mm spacing reduced maximum temperature by only 1.07% (temperature difference 11 °C to 10.3 °C), so 15 mm was judged optimal.
- A cited reference states that above 100 W/cm² heat flux, air cooling and heat-pipe cooling are no longer applicable.
Using it in design
- Select the two-phase immersion fluid by boiling point: it must boil below the 85 °C chip limit but not boil continuously at idle and raise condenser pump energy (HFE-7100 was chosen).
- Keep server board spacing at about 15 mm; 5 to 15 mm cut maximum temperature by 5.06%, 15 to 25 mm only 1.07%.
- Use condenser water inlet temperature as the variable for steady chip temperature and flow rate for transient time.
Who should read it
Cooling engineers and researchers designing two-phase immersion fluid and board spacing.
Document contents
- 1. Introduction
- 2. Establishment of a Simulation Model (2.1 Selection of Cooling Liquid, 2.2 Physical Model, 2.3 Numerical Model: VOF model, turbulence models, evaporation-condensation model; 2.5 Grid Independence Verification, 2.6 Model Validation, 2.7 Evaluation Index)
- 3. Results and Discussion (3.2 The Effect of Different Cooling Water Inlet Flow Rates on Cooling Performance)
- 4. Conclusions
Read the document
immersion-phase-change-server-simulation-2023.pdf
CC BY 4.0: share with attribution
The document is provided unaltered because its licence permits redistribution.
Publication details
- Authors
- Tiantian Zhao; Rongfeng Sun; Xukai Hou; Jikai Huang; Wenguang Geng; Jianguo Jiang
- Publisher
- Energies (MDPI AG)
- Year
- 2023
- Volume
- 16
- Issue
- 12
- Pages
- 4640
- Document language
- English
- Source type
- Scientific
- Access
- Open licence (downloadable)
- Licence
- CC BY 4.0: share with attribution
- Licence evidence
- www.mdpi.com
Original licence note
PDF p.1 states the article is open access under the Creative Commons Attribution (CC BY 4.0) licence; MDPI publishes all articles under CC BY 4.0.
Citation
Tiantian Zhao; Rongfeng Sun; Xukai Hou; Jikai Huang; Wenguang Geng; Jianguo Jiang (2023). Simulation Study of Influencing Factors of Immersion Phase-Change Cooling Technology for Data Center Servers. Energies (MDPI AG). 16(12), 4640. https://doi.org/10.3390/en16124640
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.