Simulation Study of Influencing Factors of Immersion Phase-Change Cooling Technology for Data Center Servers

Energies (MDPI AG) · Tiantian Zhao, Rongfeng Sun et al.

This study combines CFD (boiling and condensation) with a validation experiment to examine two-phase immersion cooling of server chips: the fluorinated fluid HFE-7100 boils on the chip and condenses on a water-cooled condenser plate.

CC BY 4.0: share with attribution

On this page

Overview

Immersion phase-change cooling uses the latent heat of the cooling liquid by putting it in direct contact with the heat-generating chip, and can meet the cooling needs of today's high-heat-flux data centres. A cited reference states that above 100 W/cm² heat flux, air cooling and heat-pipe cooling are no longer applicable. The study varies condenser cooling-water inlet temperature and velocity and the spacing between server boards, tracking chip temperature, temperature spread and a uniformity coefficient.

FC-40 and FC-77 have boiling points too high to boil while the chip stays below its 85 °C safe limit, and HFE-7000 boils even at idle, raising condenser water-pump energy, so all three were excluded and HFE-7100 was used. Against experiment at 20 °C cooling-water inlet and 1 m/s, the model's steady chip surface temperature differed by no more than 2.5 °C. Flow-rate cases used a cooling-water inlet temperature of 24 °C with velocities of 0.6, 0.8, 1 and 1.2 m/s; steady chip temperature was only weakly affected by flow rate, while time to stabilise fell as flow increased.

Increasing board spacing from 5 mm to 15 mm cut maximum temperature by 5.06%, reduced temperature difference from 16.5 °C to 11 °C and lowered the uniformity coefficient by 52.6%. Going from 15 mm to 25 mm spacing reduced maximum temperature by only 1.07%, with temperature difference falling from 11 °C to 10.3 °C, so 15 mm was judged optimal. Lower water inlet temperature mainly lowers steady chip temperature, while higher flow mainly shortens the transient.

Limits: a single fluid (HFE-7100), specific power conditions and a small-scale model; results do not transfer directly to other fluids or server geometries. Boiling point is decisive in fluid selection: a fluid is needed that boils below the chip safe limit but does not boil continuously at idle.

Key points

  1. FC-40 and FC-77 have boiling points too high to boil while the chip stays below its 85 °C safe limit; HFE-7000 boils even at idle; all three were excluded and HFE-7100 was used.
  2. Against experiment at 20 °C cooling-water inlet and 1 m/s, the model's steady chip surface temperature differed by no more than 2.5 °C.
  3. Flow-rate cases used a cooling-water inlet temperature of 24 °C with velocities of 0.6, 0.8, 1 and 1.2 m/s; steady chip temperature was only weakly affected by flow rate, while time to stabilise fell as flow increased.
  4. Increasing board spacing from 5 mm to 15 mm cut maximum temperature by 5.06%, reduced temperature difference from 16.5 °C to 11 °C and lowered the uniformity coefficient by 52.6%.
  5. Going from 15 mm to 25 mm spacing reduced maximum temperature by only 1.07% (temperature difference 11 °C to 10.3 °C), so 15 mm was judged optimal.
  6. A cited reference states that above 100 W/cm² heat flux, air cooling and heat-pipe cooling are no longer applicable.

Using it in design

  • Select the two-phase immersion fluid by boiling point: it must boil below the 85 °C chip limit but not boil continuously at idle and raise condenser pump energy (HFE-7100 was chosen).
  • Keep server board spacing at about 15 mm; 5 to 15 mm cut maximum temperature by 5.06%, 15 to 25 mm only 1.07%.
  • Use condenser water inlet temperature as the variable for steady chip temperature and flow rate for transient time.

Who should read it

Cooling engineers and researchers designing two-phase immersion fluid and board spacing.

Document contents

  1. 1. Introduction
  2. 2. Establishment of a Simulation Model (2.1 Selection of Cooling Liquid, 2.2 Physical Model, 2.3 Numerical Model: VOF model, turbulence models, evaporation-condensation model; 2.5 Grid Independence Verification, 2.6 Model Validation, 2.7 Evaluation Index)
  3. 3. Results and Discussion (3.2 The Effect of Different Cooling Water Inlet Flow Rates on Cooling Performance)
  4. 4. Conclusions

Read the document

immersion-phase-change-server-simulation-2023.pdf

PDF · 1.1 MB · English

CC BY 4.0: share with attribution

The document is provided unaltered because its licence permits redistribution.

Publication details

Authors
Tiantian Zhao; Rongfeng Sun; Xukai Hou; Jikai Huang; Wenguang Geng; Jianguo Jiang
Publisher
Energies (MDPI AG)
Year
2023
Volume
16
Issue
12
Pages
4640
Document language
English
Source type
Scientific
Access
Open licence (downloadable)
Licence
CC BY 4.0: share with attribution
Licence evidence
www.mdpi.com
Original licence note

PDF p.1 states the article is open access under the Creative Commons Attribution (CC BY 4.0) licence; MDPI publishes all articles under CC BY 4.0.

Citation

Tiantian Zhao; Rongfeng Sun; Xukai Hou; Jikai Huang; Wenguang Geng; Jianguo Jiang (2023). Simulation Study of Influencing Factors of Immersion Phase-Change Cooling Technology for Data Center Servers. Energies (MDPI AG). 16(12), 4640. https://doi.org/10.3390/en16124640

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.