Technical guideFree to read2011

Air Corrosivity in U.S. Outdoor-Air-Cooled Data Centers is Similar to That in Conventional Data Centers (LBNL-4951E)

Lawrence Berkeley National Laboratory · Henry C. Coles, Tae Won Han et al.

An LBNL field study comparing the corrosion risk from airborne contaminants in outdoor-air (economizer) cooled data centres and closed recirculating facilities using copper and silver coupons.

On this page

Overview

Published in 2011 by Henry Coles, Tae Won Han, Phillip Price, Ashok Gadgil and William Tschudi, this LBNL report (LBNL-4951E) is a field study of the corrosion risk from airborne contaminants in outdoor-air-cooled data centres. It compares economizer facilities that use outside air with closed, recirculating ones. The report is freely readable and sets out to answer with data one of the main reservations about the spread of outdoor-air cooling in the US.

The method rests on corrosion classification coupons. Copper and silver coupons were exposed for 30 days. They were placed in three locations: outside (before filtration), in supply air after the filters, and inside the server rooms. This arrangement makes it possible to see separately the raw quality of the outside air and the effect of filtration and of the facility's own conditions.

The study evaluated 19 data centres in the US and 2 in India. The headline finding is stated in the title: corrosivity in US outdoor-air-cooled data centres is similar to that in conventional closed data centres. In other words, for the US sample it could not be shown that using an economizer by itself markedly raises corrosion risk. The study's limits are also clear: the result is bounded by the facilities examined and the 30-day exposure, and it applies mainly to the US; the two Indian sites sit outside the generalisation in the title. Coupon monitoring is therefore sensible in other climates and pollution conditions. Related documents include ANSI/ISA-71.04 and the ASHRAE TC 9.9 contamination white paper.

Key points

  1. 19 data centres in the US and 2 in India were evaluated.
  2. Copper and silver corrosion classification coupons were exposed for 30 days.
  3. Coupons were placed outside (before filtration), in supply air after filters and inside server rooms.
  4. Finding: corrosivity in US outdoor-air-cooled data centres is similar to conventional closed data centres.
  5. The study compares economizer and closed-circuit facilities.
  6. Report LBNL-4951E, 2011; freely readable.
  7. Related documents: ANSI/ISA-71.04 and the ASHRAE TC 9.9 contamination white paper.

Using it in design

  • Assess contamination risk and corrosion-coupon monitoring when considering an air-side economiser.
  • Link to the ASHRAE contamination guidance already in the library.
  • Include coupon placement at outside air, post-filter supply and server room locations in the monitoring plan.
  • Do not generalise the result directly to regions outside the sample, such as India; ask for local measurement.

Who should read it

Mechanical designers evaluating economizer cooling and preparing air-quality, corrosion and contamination monitoring plans.

Related standards

  • ANSI/ISA-71.04
  • ASHRAE TC 9.9 contamination white paper

Publication details

Authors
Henry C. Coles; Tae Won Han; Phillip N. Price; Ashok J. Gadgil; William F. Tschudi
Publisher
Lawrence Berkeley National Laboratory
Year
2011
Document number
LBNL-4951E
Document language
English
Source type
Government / public
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

LBNL (contractor-operated DOE laboratory) resource; not US-Gov public domain. Cited only.

Citation

Henry C. Coles; Tae Won Han; Phillip N. Price; Ashok J. Gadgil; William F. Tschudi (2011). Air Corrosivity in U.S. Outdoor-Air-Cooled Data Centers is Similar to That in Conventional Data Centers (LBNL-4951E). Lawrence Berkeley National Laboratory. LBNL-4951E. https://eta-publications.lbl.gov/sites/default/files/lbnl-4951e.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.