Technical guideFree to read2013

AEG Protect STS brochure EN08/2013V1, dimensions and weights p.6

AEG Power Solutions

A six-page AEG Power Solutions brochure dated August 2013 for the Protect STS static transfer switch family: 19 models from 63 A to 1000 A in 2, 3 and 4 pole versions, automatic transfer in under 6 ms between synchronised sources, and efficiency above 99%.

On this page

Overview

The brochure describes thyristor-based static transfer switches (STS) that move a load between two independent AC sources. The target application is data and telecommunication centres: the two sources and their input lines stay completely separate, and the load can be fed from two UPS systems of different ratings and types. According to the document an STS transfers about 20 times faster than a conventional automatic transfer switch (ATS), typically within a quarter cycle, while retransfer to the preferred source typically takes 100 microseconds.

Operation is summarised in three modes. In preferred source mode the load runs from the selected source and moves to the other when voltage leaves the acceptable range. In automatic retransfer mode the load returns to the preferred source after a delay set by DIP switches once that source is healthy again. In manual mode the connections are chosen by hand. The control panel has LED indicators and three buttons, and the control unit uses fail-safe CMOS logic, three redundant internal power supplies and redundant SCR drivers.

The specification table states the limits a designer needs: 3 x 400 V phase-to-phase rated voltage, TN-C and TN-S systems, 50 Hz, and an input voltage tolerance of -25% to +20%. Overload capacity is stepped from 125% for 1 hour up to 1500% for 20 ms. Short-circuit strength of the thyristor switches ranges from 3 kA to 28 kA for 20 ms depending on rated current, and the fuse interrupting capacity is 50 kA. The neutral is dimensioned for 200% of nominal current.

The dimension and weight table on the last page can be used directly for layout. The 63 A models are also offered as 19 inch rack units: the 2 pole rack model measures 483 x 267 x 415 mm and weighs 22 kg. Cabinet models start at 800 mm width, and the largest unit, the 4 pole 1000 A model, measures 1800 x 2240 x 806 mm and weighs 1200 kg. The 2013 brochure states that its data carry no binding guarantee and that firm values are confirmed by the manufacturer at enquiry stage.

Key points

  1. Rated currents: 2 pole 63, 150, 250, 400 A; 3 and 4 pole 63, 150, 250, 400, 630, 1000 A; the 63 A models also come as 2, 3 and 4 pole 19 inch rack versions.
  2. With synchronised lines and phase error within limits, automatic transfer takes less than 6 ms and manual transfer less than 0.2 ms.
  3. Without synchronisation, the transfer delay is set by DIP switch to 13, 17, 25 or 50 ms.
  4. Overload capacity: 125% for 1 hour, 400% for 5 s, 800% for 0.4 s, 1000% for 0.2 s, 1500% for 20 ms.
  5. Thyristor short-circuit strength (20 ms): 3 kA at 63 A, 8 kA at 150 A, 15 kA at 250 and 400 A, 28 kA at 630 A; fuse interrupting capacity 50 kA.
  6. Transfer thresholds are set by DIP switch: overvoltage +6% to +20%, undervoltage -8% to -24%, synchronised phase limit ±8° to ±24°.
  7. The output overcurrent switching interlock can be set to 3 In, 4.5 In, 6 In, 7.5 In, 9 In or no interlock.
  8. Efficiency is above 99%; maximum crest factor 3.5, load power factor range 0.5 to 1 (lagging or leading).
  9. Operating temperature 0 to 40 °C, maximum altitude 1000 m, protection IP20, acoustic noise below 55 dBA.
  10. Cooling is natural on the 63 A model and forced with redundant built-in fans from 150 A upward.

Using it in design

  • When tying two UPS outputs together through an STS, compare the transfer time (under 6 ms synchronised, 13 to 50 ms unsynchronised) with the hold-up time of the IT power supplies.
  • Check the prospective short-circuit current at the STS input against the model's thyristor strength (3 to 28 kA for 20 ms) and the 50 kA fuse interrupting capacity.
  • Set the overcurrent interlock threshold (3 In to 9 In) together with the downstream protection settings so that a faulted load is not carried over to the second source.
  • Use the cabinet sizes and masses for layout: the 400 A 3 pole model is 1200 x 1950 x 506 mm and 365 kg, the 1000 A 4 pole model 1800 x 2240 x 806 mm and 1200 kg.
  • For harmonic-rich IT loads, size the neutral cable to match the neutral path rated for 200% of nominal current.
  • For sites above 1000 m or ambient temperatures above 40 °C, request derating factors from the manufacturer.

Who should read it

Electrical engineers designing dual-fed distribution, specifiers of static transfer switches, and teams laying out electrical rooms.

Document contents

  1. Key features
  2. Application
  3. Control panel
  4. Operating modes
  5. Applied standards
  6. Block diagram of Protect STS control unit
  7. Protect STS specification
  8. Alarms and communication interface
  9. Environmental
  10. Dimensions and weights

Publication details

Authors
AEG Power Solutions
Publisher
AEG Power Solutions
Year
2013
Document number
EN08/2013V1
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

AEG Power Solutions (2013). AEG Protect STS brochure EN08/2013V1, dimensions and weights p.6. AEG Power Solutions. EN08/2013V1. https://artronic.com.tr/Upload/ProductBrochure/31c9c92b33514d9c88c792389dd1eb0f-AEG_STS_Protect_STS_EN.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.