Technical guideFree to read2024

Selecting Between a 3-Pole and 4-Pole ATS

Rehlko · Mike Pincus (Rehlko)

A Rehlko white paper (G26-16, 12/24) explaining how the grounding scheme determines ATS pole count, with ground-fault current paths shown in three figures.

On this page

Overview

The document says that choosing between a three-pole and four-pole automatic transfer switch (ATS) depends on the grounding scheme of the system. Its starting point is the ground-fault protection (GFP) requirements of NFPA 70 (NEC) and local codes. The text separates system ground, equipment ground and system neutral ground, and ties the choice to whether the emergency power system is a separately derived system.

With a three-pole ATS the neutral is continuous through the whole system (solid neutral) and is bonded to ground at one point only, at the utility service. The generator has no neutral-to-ground link, only its equipment ground. With no fault, the ground-fault sensor at the service compares phase current with neutral return current and the breaker does not trip because the sum is zero. With the generator running and a phase-to-ground fault at the load, current returns through ground to the neutral-ground bond at the service entrance and then through the neutral to the generator; the generator's sensor sees the outgoing phase current and the returning neutral current, the net sum is zero, and the generator breaker does not detect the fault or trip. The same current is sensed on the utility side, so the service entrance breaker may trip unintentionally.

With a four-pole ATS the neutral is also switched and each source's neutral is bonded to ground at its own source, so each source is separately derived. The generator must have its own neutral-to-ground link. Whichever source feeds the load, ground fault current returns through ground directly to that source and its sensor sees the fault. The NEC definition of a separately derived system is quoted in substance: a system whose conductors have no direct connection to another system's conductors other than through earth, metal enclosures, metallic raceways or equipment grounding conductors.

The final section stresses that in systems with more than one ATS the same configuration (three or four pole) must be used throughout, which is essential for the integrity of the ground-fault scheme. The same grounding rules apply with multiple generators and paralleling switchgear. The document is a conceptual guide with no numerical fault-current calculation or product selection, and recommends consulting an authorised manufacturer representative.

Key points

  1. Pole count is determined by the grounding scheme and by whether the emergency power system is separately derived.
  2. Three-pole ATS (solid neutral): the neutral is bonded to ground at one point, the utility service; the generator has equipment ground but no neutral-ground link.
  3. With a three-pole ATS on generator power, a load ground fault gives the generator sensor a net zero current so it does not trip, while the utility-side sensor sees the current and may trip the service breaker unintentionally.
  4. Four-pole ATS (switched neutral): each source's neutral is bonded to ground at its own source and the generator becomes a separately derived source.
  5. With a four-pole ATS, fault current returns through ground directly to the source currently supplying the load and is detected.
  6. In systems with more than one ATS, the same configuration (three or four pole) must be used throughout.
  7. The same grounding rules apply with multiple generators and paralleling switchgear.

Using it in design

  • Before deciding ATS pole count, determine on the single-line diagram whether the emergency source will be separately derived and where the neutral-ground bond will be.
  • If a three-pole ATS is chosen, the generator must have no neutral-ground bond; verify the ground-fault protection scheme for this case, since a generator fault goes undetected and the utility breaker may trip unintentionally.
  • If a four-pole ATS is chosen, add a neutral-ground bond at the generator and test during commissioning that ground-fault detection works on each source.
  • In schemes with several ATSs, specify all with the same pole count and apply the same grounding logic in parallel generator design.
  • Confirm local code (NEC and others) ground-fault protection requirements at specification stage.

Who should read it

Electrical engineers designing the grounding and ground-fault protection scheme of standby power systems.

Document contents

  1. Introduction
  2. Regulation considerations
  3. Understanding ground faults assuming various conditions
  4. Using a three-pole transfer switch: solid neutral, no fault, ground fault induced
  5. Using a four-pole transfer switch: separately derived system, switching the neutral
  6. Final thoughts

Related standards

  • NFPA 70 (NEC) 250.30
  • NFPA 70 (NEC) 230.95
  • UL 1008

Publication details

Authors
Mike Pincus (Rehlko)
Publisher
Rehlko
Year
2024
Document number
G26-16
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Vendor white paper; no open licence. Year from PDF metadata (Dec 2024).

Citation

Mike Pincus (Rehlko) (2024). Selecting Between a 3-Pole and 4-Pole ATS. Rehlko. G26-16. https://techcomm.rehlko.com/techcomm/contentful/G26-16_Selecting%20Between%20a%203-Pole%20and%204-Pole%20ATS_WP.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.