Withstand and Close-On Ratings for Transfer Switches
Rehlko · Mike Little (Rehlko)
A Rehlko white paper (G26-23) explaining the four WCR types under UL 1008, how they constrain protective device selection and selective coordination, and the effect of the 2014 7th edition.
On this page
Overview
The document notes that the many short-circuit ratings quoted for transfer switches can be confusing, and explains the withstand and close-on rating (WCR) so engineers can specify the right equipment. WCR measures two abilities: withstanding fault current for a specified time while staying functional, and closing into a fault and continuing to operate. The selection process is presented in five steps: understand the damage caused by high fault currents, study the power system, apply selective coordination and fault isolation, identify the required WCR for the ATS, and conclude.
Fault currents can thermally damage conductor and transformer insulation, protective devices and switch contacts, and large magnetic forces can bend busbars, separate contacts or pull out cables. A power system study computes fault currents at each bus for normal, contingency and future configurations. Two identical 200 A ATSs in different places can need very different WCRs: one near the service entrance 35 kA, one on a remote branch only 10 kA. An overrated WCR adds cost and enclosure size.
The four types are described as follows. Specific breaker (series) ratings are tested with a particular molded-case breaker between the ATS and the source, and only breakers on the label or specification sheet may be used. Time-based ('any breaker') ratings are obtained by applying fault current for 0.050 seconds (0.025 seconds below 400 A) and permit use with any UL 489 breaker with an instantaneous trip. Short-time ('30-cycle') ratings carry fault current for up to 0.5 seconds, suit selective coordination but give the lowest WCR level and can make the ATS two to three times more expensive. Fuse ratings use current-limiting fuses clearing in about 0.008 seconds and reach the highest WCR (up to 200 kA in many cases), but fuses are not resettable or adjustable for coordination.
The document also explains how the UL 1008 7th edition, in force from 1 November 2014, shortened specific-breaker lists: only breakers actually tested, or whose whole instantaneous trip curve lies below the tested breaker's clearing time, may be listed. Designers therefore move to time-based ratings where possible, and because those are lower for a given frame, the ATS frame may need to be larger. It is a general guide, not specific to one product family.
Key points
- WCR covers two abilities: withstanding fault current for a specified time while remaining functional, and closing into a fault and continuing to operate.
- Two identical 200 A ATSs can need different WCRs: 35 kA near the service entrance and 10 kA on a remote branch; the power system study sets them.
- Four WCR types: specific breaker (series), time-based ('any breaker'), short-time and fuse ratings.
- Time-based ratings come from applying fault current for 0.050 s (0.025 s below 400 A) and work with UL 489 breakers that have an instantaneous trip.
- 480 V examples (specific breaker / time-based): 200-230 A 25,000 / 10,000 A; 400 A 42,000 / 35,000 A; 800-1200 A 65,000 / 50,000 A; 1600-2000 A 125,000 / 100,000 A.
- Short-time ratings (30 cycles, 0.5 s) serve selective coordination, give the lowest WCR level and can cost two to three times more; a 500 kcmil cable carries about 39,000 A for 0.5 s versus over 100,000 A for 0.05 s.
- Fuses clear in about 0.008 s and give the highest WCR, up to 200 kA in many cases, but are not resettable or adjustable for coordination.
- The UL 1008 7th edition (1 November 2014) shortened specific-breaker lists; many designers move to time-based ratings and may need a larger frame.
- A power system study evaluates fault currents at each bus for normal, contingency and future configurations and the capability of upstream and downstream devices.
Using it in design
- For each ATS location, take the available short-circuit current from the fault study and set the WCR separately; do not assume the same WCR for ATSs of the same current class.
- If upstream breakers use short-time delay for selective coordination, state the short-time WCR requirement in the specification and verify the cost and that the whole distribution system matches it.
- Confirm devices on a specific-breaker list from the label or data sheet; if a breaker is not listed, rely on the time-based rating.
- Before resolving an insufficient WCR by upsizing the ATS frame or choosing specific breakers or fuses, work out the space and cost impact.
- Match the specification to the power system study before commissioning to avoid impermissible disconnect and ATS combinations and wrong switch purchases.
Who should read it
Electrical engineers working on protection coordination and ATS specifications.
Document contents
- Introduction
- I. Understand damages caused by high fault currents
- II. Study the power system
- III. Apply selective coordination and fault isolation
- IV. Identify the required WCR for the ATS
- Understanding the four WCR types: specific breaker, time-based, short-time, fuses
- How is a WCR obtained
- V. Conclusion
Related standards
- UL 1008
- NFPA 70 (NEC) 700.32
- IEC 60947-6-1
Publication details
- Authors
- Mike Little (Rehlko)
- Publisher
- Rehlko
- Year
- 2025
- Document number
- G26-23
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Vendor white paper; no open licence. Year from PDF metadata (Jan 2025).
Citation
Mike Little (Rehlko) (2025). Withstand and Close-On Ratings for Transfer Switches. Rehlko. G26-23. https://techcomm.rehlko.com/techcomm/contentful/Rehlko_G26-23_Withstand%20and%20Close-On%20Ratings%20for%20Transfer%20Switches.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.