Managing Non-Linear Loads for Emergency Generators

Rehlko · Fuad Ahmed (Rehlko), Alain deLeon (Rehlko)

A Rehlko G26-24 application note: a six-pulse UPS with 28.9% ITHD can produce 15.4% VTHD even with linear load at only 50% of alternator capacity; the remedy is to cut harmonics at the load first.

On this page

Overview

Rehlko's 2025 application note G26-24 covers harmonic distortion from UPS rectifiers, VFDs, chargers and other non-linear loads fed by standby generators. Effects include voltage notching, false zero crossings, neutral overheating and paralleling problems.

Example: a six-pulse UPS with 28.9% ITHD can produce 15.4% VTHD even when the linear load is only 50% of alternator capacity, while a small LED ballast at 167% ITHD gives only 3.1% VTHD. Sub-transient reactance (Xd'') governs the generator's response to harmonic currents; a lower Xd'' reduces voltage distortion.

Distorted voltage waveforms can prevent smooth automatic paralleling and increase neutral current in balanced three-phase systems. The recommended order is to reduce harmonics at the load first (filters, 12/18-pulse or low-ITHD equipment) and then size the generator.

Key points

  1. Example: a six-pulse UPS at 28.9% ITHD can produce 15.4% VTHD (with linear load at 50% of alternator capacity).
  2. A small LED ballast at 167% ITHD gives only 3.1% VTHD; ITHD alone does not set the distortion, load power matters too.
  3. Sub-transient reactance Xd'' governs the generator's response to harmonic currents; low Xd'' reduces voltage distortion.
  4. Distorted voltage hampers automatic paralleling and increases neutral current in balanced three-phase systems.
  5. Effects: voltage notching, false zero crossings, neutral overheating, paralleling problems.
  6. Mitigations: alternator oversizing, low Xd'', passive/active filters, low-ITHD equipment.

Using it in design

  • Collect UPS and drive ITHD values before sizing the generator and check VTHD against the alternator Xd''.
  • Write the load-side reduction strategy (12/18-pulse rectifier, active filter, low ITHD) into the specification before sizing the generator.
  • Request a low-Xd'' or oversized alternator option as a separate line in the quotation.
  • Verify synchronisation behaviour under distorted voltage in factory and site tests of paralleled generator systems.

Who should read it

Electrical engineers sizing UPS-loaded generator systems, and commissioning teams.

Related standards

  • IEEE 519
  • ISO 8528-3

Publication details

Authors
Fuad Ahmed (Rehlko); Alain deLeon (Rehlko)
Publisher
Rehlko
Year
2025
Document number
G26-24
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Vendor white paper; no open licence. Year from PDF metadata (Jun 2025).

Citation

Fuad Ahmed (Rehlko); Alain deLeon (Rehlko) (2025). Managing Non-Linear Loads for Emergency Generators. Rehlko. G26-24. https://techcomm.rehlko.com/techcomm/pdf/Rehlko_G26-24_Managing_Non-Linear_Loads_for_Emergency_Generators.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.