Types of Prefabricated Modular Data Centers
Schneider Electric · Wendy Torell
This 2017 Schneider Electric white paper classifies factory-built data center modules by three attributes: functional block, form factor and configuration.
On this page
Overview
The functional block is power, cooling or IT space. A power module holds switchgear/switchboards, ATS, UPS with batteries, transformers and panelboards, with standby generators usually a separate module. Cooling module types are chiller plant (air-cooled chiller, pumps/drives, storage tank, dry/evaporative cooler), DX plant, indirect air (air-to-air heat exchanger, evaporative, DX backup) and direct air (filters, evaporative, DX backup).
Form factor is ISO container, non-ISO enclosure or skid. ISO container footprints are 20 x 8 ft (6.10 x 2.44 m) and 40 x 8 ft (12.2 x 2.44 m), at 8 ft 6 in (2.591 m) or high-cube 9 ft 6 in (2.896 m). Practical container capacity is about 500 kW for power or cooling plant and about 200-250 kW for IT space. Skid-mounted modules often cost up to 40% less than equivalent enclosure designs but are generally indoor-only, and are not logical for IT space because they lack air separation.
Configuration is semi-prefabricated, fully prefabricated or micro/all-in-one. An all-in-one (power, cooling, IT) module is limited to about 150 kW in an ISO footprint, and beyond 2 or 3 micro data center modules on a site (about 500 kW) they become cost prohibitive. Walk-in enclosures must provide lighting, fire protection, security and a means of egress.
The paper distinguishes pre-engineered designs (documented and specified) from prefabricated ones (also factory assembled and tested). Use cases include retrofit capacity shortfalls, multi-tenant step-and-repeat growth, and edge or temporary sites.
Key points
- Three attributes: functional block, form factor, configuration.
- ISO containers are 20 x 8 ft and 40 x 8 ft, 8 ft 6 in or 9 ft 6 in high-cube.
- Practical ISO capacity: about 500 kW power/cooling plant, about 200-250 kW IT space.
- Skid modules cost up to 40% less than enclosures, are generally indoor-only and unsuited to IT space.
- All-in-one modules reach about 150 kW in an ISO footprint; beyond 2-3 units (about 500 kW) per site they are cost prohibitive.
- Walk-in enclosures need lighting, fire protection, security and egress.
- Pre-engineered means documented; prefabricated also means factory assembled and tested.
Using it in design
- For module selection, record functional block, form factor, indoor/outdoor rating, walk-in flag, shipping sections, footprint and height.
- Review ISO power or cooling modules above about 500 kW and IT modules above about 250 kW separately; do not assume a skid is suitable as IT space.
- Suggest semi- or fully prefabricated options when an all-in-one exceeds 150 kW or 2-3 units per site.
- Select the prefabricated approach for the use case: a capacity shortfall, multi-tenant operation, or an edge or temporary facility.
Who should read it
Designers choosing among prefabricated module types and their capacity ceilings.
Related standards
- ISO 668
- ISO 1496-1
- UL 2755
- NFPA 101
Publication details
- Authors
- Wendy Torell
- Publisher
- Schneider Electric
- Year
- 2017
- Document number
- WP 165
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Citation
Wendy Torell (2017). Types of Prefabricated Modular Data Centers. Schneider Electric. WP 165. https://download.schneider-electric.com/files?p_Doc_Ref=SPD_WTOL-97GLP9_EN
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.