Sustainability Benefits of Prefabricated Data Centers: Core and Shell Carbon Reduction

Schneider Electric · Suraj Manohar Desai, Mahesha Munanjanappa et al.

A Schneider Electric white paper comparing the construction-phase (core and shell) embodied carbon of a traditional stick-built electrical room with an equivalent set of prefabricated power modules.

On this page

Overview

The paper concentrates on a narrow, measurable question: for the same electrical capacity, does an electrical room built on site or a set of prefabricated power modules made in a factory and shipped produce less carbon? The comparison covers only construction-phase (core and shell) embodied carbon; operating energy is outside the evaluation. Four emission sources are counted: above-ground site clearing, freight, on-site construction activity and materials.

The main result is that prefabricated power modules cut core-and-shell construction carbon by about 80% at deployment compared with a stick-built electrical room, which corresponds to an embodied-carbon multiplier of roughly 0.2 for the modular option. The paper also tests whether the advantage fades: even if module enclosures are replaced every 20 years, cumulative embodied carbon stays more than 50% lower after 60 years.

This shows that the modular route carries an end-of-life replacement burden, but that burden does not erase the saving at deployment. The limit is scope: only the electrical room is compared, so nothing is concluded for the whole building or for cooling infrastructure. The authors present prefabrication as a carbon-reduction lever; cost, schedule and operating-performance comparisons are not what this paper is about.

Key points

  1. Prefabricated power modules cut core-and-shell construction carbon by about 80% at deployment.
  2. With enclosures replaced every 20 years, cumulative embodied carbon stays more than 50% lower after 60 years.
  3. Four emission sources: above-ground site clearing, freight, on-site construction and materials.
  4. The comparison is a stick-built electrical room against equivalent prefabricated power modules.
  5. Scope is construction-phase embodied carbon only.

Using it in design

  • Add a construction-method option for electrical rooms: stick-built or prefabricated module.
  • Use an embodied-carbon multiplier of about 0.2 for the prefabricated option at deployment.
  • Default the enclosure service life to 20 years and include replacement within a 60-year horizon in lifecycle carbon calculations.
  • Show the cumulative curves of the two methods side by side in the carbon report.

Who should read it

Project managers choosing an electrical-room construction method and sustainability engineers computing embodied carbon.

Related standards

  • EN 15978
  • ISO 21930

Publication details

Authors
Suraj Manohar Desai; Mahesha Munanjanappa; Wendy Torell; Ray Lizotte
Publisher
Schneider Electric
Year
2026
Document number
WP 240
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document

Citation

Suraj Manohar Desai; Mahesha Munanjanappa; Wendy Torell; Ray Lizotte (2026). Sustainability Benefits of Prefabricated Data Centers: Core and Shell Carbon Reduction. Schneider Electric. WP 240. https://download.schneider-electric.com/files?p_Doc_Ref=SPD_WP240_EN

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cost studies in SoSo CAD

Calculate equipment cost, energy cost and total cost of ownership (TCO) from the design’s quantities and your own price assumptions.

CAPEX and TCO estimates in the SoSo CAD cost workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.