Schneider Electric WP 80 (2022) is a planning guide for small, numerous and mostly unstaffed network-edge data centres. It is a decision framework by site type, not a sizing reference.
On this page
Overview
The paper splits the network edge into three classes: legacy telco rooms, distributed cloud sites and future multi-access edge computing (MEC) sites. Table 1 gives typical rack densities for each: legacy telco below 5 kW/rack, distributed cloud 3-30 kW/rack and MEC 3-20 kW/rack. All three are typically a few racks with no medium voltage, limited low voltage and UPS, and no genset. Power type also varies: -48 V DC for telco, AC for distributed cloud, and AC, -48 V DC or hybrid for MEC.
The authors list seven scaling challenges, among them diverse equipment, limited space, harsh outdoor environments, poor PUE, lack of on-site staff and cyber exposure. Three environments are defined: IT, commercial and office, and industrial and harsh. Harsh sites may need NEMA 4 and IP 65 rated enclosures. On efficiency, today's edge sites run an annual PUE of about 2.0 because of legacy loads near 1 kW per rack, against as low as 1.1 for core cloud.
Recommended practice starts with lithium-ion rather than VRLA batteries behind UPSs and rectifiers: typically 10 years of life, embedded monitoring and tolerance of temperatures above 40 °C. Critical sites should have redundant power and cooling for concurrent maintainability. Air or liquid cooling is chosen by density and environment, prefabricated modules and wall-mount enclosures are paired with physical security, and the paper expects IEC 62443-aligned cybersecurity plus DCIM and sustainability software.
The text also relays Schneider forecasts: 7.5 million new micro data centres by 2025 and, by 2040, a peak-power footprint that could reach 192 GW with energy above 1,679 TWh. Citing integrator data, it adds that pre-configured integrated solutions can cut field engineering cost by 25% to 40%. These are vendor and cited-source projections, and as a vendor white paper the document is best read as guidance rather than neutral evidence.
Key points
- Typical rack density: legacy telco below 5 kW/rack, distributed cloud 3-30 kW/rack, MEC 3-20 kW/rack.
- Power: telco -48 V DC, distributed cloud AC, MEC AC/-48 V DC/hybrid; distributed cloud may use inverters with 2-4 hours of battery.
- Harsh environments may need NEMA 4 and IP 65 enclosures.
- Today's network-edge sites run an annual PUE around 2.0, versus as low as 1.1 for core cloud; 5G edge uses three times the energy of 4G on average.
- Lithium-ion batteries: typically 10 years life, embedded monitoring, tolerance above 40 °C.
- Integrated pre-configured solutions can cut field engineering 25-40% and maintenance 7%, and raise order processing speed 20%.
- By 2040 edge peak power could reach 192 GW and energy over 1,679 TWh (Schneider forecast).
Using it in design
- Add site type (legacy telco, distributed cloud, MEC), environment class and power type (AC, -48 V DC, hybrid) to the project template.
- Require an IP65/NEMA 4 rated enclosure and self-contained cooling for any harsh-environment site.
- Warn when rack density falls outside the typical band of the chosen site type.
- For genset-free sites, make battery runtime an explicit input and default to lithium-ion.
Who should read it
Design engineers and infrastructure owners planning many small, unstaffed edge or telco sites.
Related standards
- IEC 62443
- ANSI/TIA-942
- IEC 60529
- NEMA 250
- NEBS
- ETSI EN 300 019
Publication details
- Authors
- Paul Lin; Steven Carlini; Victor Avelar; Andres Vasquez
- Publisher
- Schneider Electric
- Year
- 2022
- Document number
- WP 80
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Citation
Paul Lin; Steven Carlini; Victor Avelar; Andres Vasquez (2022). Best Practices to Deploy Sustainable and Resilient Data Centers at Scale at the Network Edge. Schneider Electric. WP 80. https://download.schneider-electric.com/files?p_Doc_Ref=SPD_WP80_EN
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.