White paperCitation2011

WP#35 - Water Usage Effectiveness (WUE): A Green Grid Data Center Sustainability Metric

The Green Grid · Michael Patterson, Dan Azevedo et al.

The Green Grid paper (WP 35, 2011) that defines Water Usage Effectiveness (WUE) as the water companion to PUE and CUE.

On this page

Overview

The paper introduces Water Usage Effectiveness (WUE) as the water companion to PUE and CUE. WUE divides annual site water use by IT equipment energy and is expressed in L/kWh. A source-based variant, WUEsource, adds the off-site water consumed in generating the electricity. The full text requires sign-in; this page relies on public summaries.

Site water includes cooling-tower or evaporative make-up water and humidification; potable use by occupants is commonly excluded. For WUEsource, off-site water is added as the energy water intensity factor times total energy. The gap between a facility's site and source WUE therefore shows where the water is actually consumed.

Used together with PUE and CUE, it makes energy-water-carbon trade-offs visible, particularly for evaporative cooling: a cooling choice that lowers PUE can raise WUE. The record gives no calculation procedure, typical values or thresholds; the paper is a definition and scope document.

Key points

  1. WUE = annual site water usage (L) / IT equipment energy (kWh), in L/kWh.
  2. WUEsource adds off-site water used to generate the electricity (energy water intensity factor x total energy).
  3. Site water includes cooling-tower/evaporative make-up and humidification.
  4. Potable use by occupants is commonly excluded.
  5. With PUE and CUE it exposes energy-water-carbon trade-offs, notably for evaporative cooling.

Using it in design

  • In the water assessment, compute WUE_site = annual make-up + humidification water (L) / IT kWh from the hourly cooling model (evaporation ~ heat rejected, cycles of concentration for blowdown).
  • Add an optional WUE_source using a regional EWIF (L/kWh) catalog.
  • Report WUE next to PUE to make the evaporative versus dry-cooler trade-off explicit.

Who should read it

Design and sustainability teams selecting cooling systems and reporting water use.

Related standards

  • ISO/IEC 30134-9
  • EN 50600-4-9

Publication details

Authors
Michael Patterson; Dan Azevedo; Christian Belady; Jack Pouchet
Publisher
The Green Grid
Year
2011
Document number
WP 35
Document language
English
Source type
Industry body
Access
Citation only
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document

Citation

Michael Patterson; Dan Azevedo; Christian Belady; Jack Pouchet (2011). WP#35 - Water Usage Effectiveness (WUE): A Green Grid Data Center Sustainability Metric. The Green Grid. WP 35. https://www.thegreengrid.org/en/resources/library-and-tools/238-WP%2335---Water-Usage-Effectiveness-%28WUE%29%3A-A-Green-Grid-Data-Center-Sustainability-Metric

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.