Research paperFree to read2014

Air Conditioning Planning of a Data Center for Universities with CFD Analysis

Original title Üniversitelere Yönelik Bir Veri Merkezinin CFD Analizi ile İklimlendirme Planlaması

Bilecik Şeyh Edebali Üniversitesi Fen Bilimleri Dergisi · Uğur Yüzgeç, Arif Günel

A 2014 paper by Yüzgeç and Günel compares hot- and cold-aisle containment by CFD in a Bilecik Şeyh Edebali University data centre; cold-aisle containment needs less cooling power at 2-5 kW per rack.

On this page

Overview

The paper is a research article in the Bilecik Şeyh Edebali University Journal of Science (2014). It opens by stating that ineffective cooling takes about 30-50% of data-centre total consumption, and argues that CFD (computational fluid dynamics) analysis is necessary for airflow design in medium and large data centres.

The application covers the university's hosting and network rooms. Cooling is planned with redundancy using free-cooling-capable air-cooled precision units and in-row units: the network room has two 36 kVA (28.8 kW) in-row units backing each other, and the hosting room has four in-row units (3 duty, 1 standby) whose three duty units total 108 kVA (86.4 kW). Outdoors there are two 160 kVA (128 kW) chillers, with duty and standby A and B lines and supply tanks. From Bilecik's 1960-2012 temperature data, outdoor-air cooling is possible for at least 200 days a year.

The CFD scenarios cover first-day (40 kW/45 kVA; 0.75 kW per network rack, 2 kW per hosting rack) and last-day load, with airflow 8000 m3/h and 22 °C supply. At first-day load, hot-aisle containment has the network cooler at 7.5 kW and hosting coolers at 11.2 kW, while cold-aisle containment needs 3.75 and 8.3 kW. At last-day load hot containment needs 12.8 and 21.6 kW and cold containment 12 and 16.1 kW.

The authors conclude that cold-aisle containment cools more efficiently at every load. The work rests on simulation of a single facility; there is no measured operating data and the results are specific to this in-row layout.

Key points

  1. Ineffective cooling takes about 30-50% of data-centre total consumption.
  2. In the hosting room three of four 36 kVA (28.8 kW) in-row units are duty and one is standby; the three duty units total 108 kVA (86.4 kW).
  3. With indoor units totalling 144 kVA (115.2 kW), a 160 kVA (128 kW) chiller was chosen, installed as one duty and one standby.
  4. Precision-cooling zones are set to 24 °C, ±1 °C and 45-55% relative humidity.
  5. Bilecik data (1960-2012) allow outdoor-air cooling for at least 200 days a year.
  6. At first-day load, hot containment needs 7.5 kW (network) and 11.2 kW (hosting); cold containment 3.75 and 8.3 kW.
  7. At last-day load, hot containment needs 12.8 and 21.6 kW; cold containment 12 and 16.1 kW.
  8. In CFD the cold aisle supply was 22-25 °C and the hot side 36-38 °C; cold-aisle containment proved more efficient.

Using it in design

  • In a new design, decide hot versus cold containment by comparing them in CFD at the target rack density, running first-day and last-day load as separate scenarios.
  • With in-row cooling, close the aisle with glass on top and doors at the ends, and use blanking panels inside racks.
  • Build redundancy at in-row level (3 duty + 1 standby) and separately at outdoor unit, supply line and tank level.
  • Derive free-cooling days from the annual outdoor temperature distribution and tie the choice of free-cooling units to that data.
  • Control cooling units on server inlet temperature; return air should not be the reference.

Who should read it

Mechanical engineers planning data-centre air conditioning, campus IT managers and designers deciding aisle containment with CFD.

Document contents

  1. Introduction
  2. Stages of Data Centre Air Conditioning
  3. A Data Centre Air-Conditioning Application (cold aisle and CFD analysis)
  4. Conclusions
  5. References

Publication details

Authors
Uğur Yüzgeç; Arif Günel
Publisher
Bilecik Şeyh Edebali Üniversitesi Fen Bilimleri Dergisi
Year
2014
Document number
1(2), 37–44
Document language
Turkish
Source type
Scientific
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Tam metin yayıncının veya üniversitenin açık kaynağından okundu. Açık erişim, ticari yeniden dağıtım izni olarak yorumlanmadı; yalnızca bağlantı, metadata ve özgün kısa özet tutulur. Başlık ve 2014 yılı PDF künyesinden alındı; DergiPark başlığı daha kısa ve yükleme/yayımlama tarihi 2 Temmuz 2016. Metindeki kVA ile soğutma kapasitesi ifadeleri genel mühendislik kuralı olarak aktarılmadı.

Citation

Uğur Yüzgeç; Arif Günel (2014). Üniversitelere Yönelik Bir Veri Merkezinin CFD Analizi ile İklimlendirme Planlaması. Bilecik Şeyh Edebali Üniversitesi Fen Bilimleri Dergisi. 1(2), 37–44. https://dergipark.org.tr/en/download/article-file/207527

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.