VESDA Channel Partner Sales Guide: Applications
Original title VESDA Channel Partner Sales Guide - Applications (Data Centers and others)
Xtralis / Honeywell · Xtralis (Honeywell)
Xtralis application guide for VESDA aspirating smoke detection across warehouses, data centres, heritage, power generation, heavy industry, correctional and cold storage; sensitivity range 0.005% to 20% obs/m and pre-suppression action in data centres.
On this page
Overview
The guide is a short sales document presenting the Xtralis VESDA active air sampling smoke detection system for seven application areas: warehouse and logistics, data centres, heritage buildings, power generation, heavy industry, correctional facilities and cold storage. For each it gives reasons for VESDA, qualifying questions and features and benefits. It is a manufacturer's document and contains no independent performance comparison.
The data-centre section notes that air-conditioning airflow can carry smoke away from ceiling detectors, high heat density raises HVAC exchange rates and dilutes smoke, HVAC filtration removes smoke particles, and smoke may hide inside fully enclosed cabinets. The proposed answer is to place sampling holes across return-air grilles, under raised floors, near high-risk cabling and inside equipment cabinets. Multiple alarm thresholds allow staged response: the first alarm sends an SMS to the facility manager, the second shuts down equipment power, and the third notifies fire services and activates voice evacuation.
The guide states VESDA can be used in coincident detection schemes for suppression actuation, avoiding duplicate detection. It adds that ASAT is an FM-approved tool for calculating VESDA alarm thresholds for suppression actuation. General features include a sensitivity range of 0.005% to 20% obs/m (0.0015 to 6% obs/ft), detectors that can be installed at ground level, a clean-air barrier protecting the optics, and FM Class 1 Div 2 rating for hazardous areas.
Key points
- Applications covered: warehouse and logistics, data centres, heritage, power generation, heavy industry, correctional and cold storage.
- VESDA sensitivity range is given as 0.005% to 20% obs/m (0.0015 to 6% obs/ft).
- Data-centre challenges: air-conditioning airflow carries smoke from detectors, high heat density raises air exchange and dilutes smoke, HVAC filtration removes smoke particles, smoke may hide inside closed cabinets.
- Suggested sampling points: return-air grilles, under raised floors, near high-risk cabling and inside equipment cabinets.
- Multiple alarm thresholds, for example first alarm SMS to the facility manager, second shuts down equipment power, third notifies fire services and starts voice evacuation.
- Can be used in coincident detection schemes for code-compliant suppression actuation, avoiding duplicate detection systems.
- ASAT is named as an FM-approved tool for calculating VESDA alarm thresholds for suppression actuation.
- Detectors can be installed at ground level; a clean-air barrier protects the optics, allowing calibration-free operation without drift compensation.
- FM Class 1 Div 2 rating is stated for hazardous areas.
Using it in design
- In the data hall, plan sampling pipe not only at the ceiling but across return-air grilles, under raised floors and in cable-dense areas; use airflow direction as the smoke path.
- For closed or actively chilled cabinets, consider capillary tubes for in-cabinet sampling.
- Define alarm stages (manager notification, equipment power shutdown, fire service and evacuation) with acceptance criteria and map them into the fire alarm matrix.
- If suppression actuation uses coincident detection, document the threshold calculation with the FM-approved tool.
- For generator and electrical rooms, where equipment may smoulder a long time, consider sampling pipes close to equipment enclosures.
Who should read it
Engineers who design and specify fire detection systems, and operators of data-centre and industrial facilities.
Document contents
- Warehouse and Logistics
- Data Centers
- Heritage
- Power Generation
- Heavy Industry
- Correctional
- Cold Storage
Related standards
- EN 54-20
- NFPA 72
Publication details
- Authors
- Xtralis (Honeywell)
- Publisher
- Xtralis / Honeywell
- Year
- 2023
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Vendor guide; no open licence stated
Citation
Xtralis (Honeywell) (2023). VESDA Channel Partner Sales Guide - Applications (Data Centers and others). Xtralis / Honeywell. https://xtralis.com/file/598
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.