Technical guideFree to read2013

5 reasons - other than safety - to use arc-flash resistant switchgear

ABB

A short ABB Data Centers paper making the case for arc-resistant LV and MV switchgear in data centres even though consensus codes do not require it, framing the choice as lifecycle cost rather than capex.

On this page

Overview

Arc-resistant switchgear costs about 10-15% more than standard gear and is not required by the consensus standards for commercial electrical systems. The paper justifies the premium with reasons beyond personnel safety: maintenance without Category 3 or 4 PPE, no need for a separate active arc-detection system, faster recovery because damage stays in one cubicle, insurer incentives and growing consultant recommendations.

The cost argument is that once the price of an active fault/arc-detection system is added to non-resistant gear, total cost is roughly equal. On layout, code-minimum rooms may have as little as five feet between equipment, so an arc in one non-resistant unit can take adjacent gear out of service. Some consulting engineers ask clients to sign a waiver if they decline arc-resistant gear for new installations.

The paper cites an NFPA/IEEE estimate of arc-flash injuries to more than 2,000 workers per year. It is a short advocacy piece: figures are given by citation and no calculation method is included.

Key points

  1. Arc-resistant switchgear costs about 10-15% more and is not required by consensus standards for commercial systems.
  2. Maintenance on arc-resistant gear can be done without Category 3 or 4 PPE.
  3. Adding an active arc-detection system to non-resistant gear brings total cost roughly level.
  4. A cited NFPA/IEEE estimate puts arc-flash injuries at more than 2,000 workers per year.
  5. Code-minimum rooms may have five feet between equipment, so an arc can take adjacent non-resistant gear out of service.
  6. Some consulting engineers ask clients to sign a waiver if they decline arc-resistant gear.

Using it in design

  • Add an 'arcResistant' field to the switchgear catalog with classification (for example IEC 62271-200 IAC / IEC TR 61641 / IEEE C37.20.7).
  • Recommend arc-resistant gear or active arc mitigation for main MV/LV boards in Tier III+ projects and show the roughly 10-15% capex delta in cost comparisons.
  • Warn in layout checks when switchgear line-ups without arc containment are closely spaced in the same room.

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Review your power design in SoSo CAD

Inspect supply paths, equipment loads and UPS failure scenarios in one model.

Request a demo
Single-line diagram in the SoSo CAD power and capacity workspace

Who should read it

Electrical designers selecting main switchgear and decision makers weighing the cost case for arc-resistant equipment.

Related standards

  • NFPA 70E
  • IEEE 1584
  • IEEE C37.20.7

Publication details

Authors
ABB
Publisher
ABB
Year
2013
Document number
9AKK106103A1703
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only — the publisher’s terms apply to the original document

Citation

ABB (2013). 5 reasons - other than safety - to use arc-flash resistant switchgear. ABB. 9AKK106103A1703. https://library.e.abb.com/public/fafcaf6eff59fda3c1257de80046fc4a/ABB-815-WPO_DataCenterArcFlash.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.