Technical guideFree to read2020

Data Center Power Systems

Aksa Power Generation

Aksa's two-page data-centre brochure summarises Uptime tier concepts as they apply to engine generators and lists models with paired Standby and DCC (data-centre continuous) ratings.

On this page

Overview

The brochure restates the tier table in terms of generator capacity, redundancy (N, N+1, N after any failure), distribution paths and concurrent maintainability. Aksa's data-centre generator range reaches 3,000 kVA standby.

The rating rules are these: Tier III/IV generators must support the design load for unlimited hours at site conditions, while Tier I/II may use any rating up to nameplate. For prime ratings, option 1 is 70% of nameplate with no hour limit and option 2 gives larger capacity but needs a manufacturer letter; standby can be used for Tier III/IV only with a manufacturer letter. Derating for ambient temperature and elevation may be required in addition.

The model tables (Cummins- and Perkins-engined sets from roughly 500 to 3,000 kVA) show typical DCC-to-standby ratios. Cummins examples (standby/DCC kVA) are AC 2000 2000/1875 (QSK60-G3), AC 2500 2500/2250 (QSK60-G8) and AC 3000 3000/2750 (QSK78-G9). Perkins examples are AP 1650 1650/1500 (4012-46TAG2A) and AP 2500 2500/2250 (4016-61TRG3). The document is marketing-level but carries usable rating data.

Key points

  1. Data-centre generator range up to 3,000 kVA standby.
  2. Tier III/IV generators must support design load for unlimited hours; Tier I/II may use any rating up to nameplate.
  3. Prime: option 1 at 70% of nameplate, no hour limit; option 2 larger capacity with manufacturer letter; standby for Tier III/IV only with manufacturer letter.
  4. Cummins pairs (standby/DCC kVA): 2000/1875 (QSK60-G3), 2500/2250 (QSK60-G8), 3000/2750 (QSK78-G9).
  5. Perkins pairs: 1650/1500 (4012-46TAG2A), 2500/2250 (4016-61TRG3).
  6. Site derating for ambient temperature and elevation may be additionally required.

Using it in design

  • Keep both standby and DCC kVA per model in the generator catalog; where data is missing, use DCC ~0.9-0.94 x standby as a flagged estimate.
  • For Tier III/IV, require a rating with unlimited hours at design load (or prime at 70%, or a manufacturer letter).
  • Apply the site derate before the tier check.

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Review your power design in SoSo CAD

Inspect supply paths, equipment loads and UPS failure scenarios in one model.

Request a demo
Single-line diagram in the SoSo CAD power and capacity workspace

Who should read it

Electrical designers checking generator ratings against Tier requirements.

Related standards

  • ISO 8528-1
  • Uptime Institute Tier Standard: Topology

Publication details

Authors
Aksa Power Generation
Publisher
Aksa Power Generation
Year
2020
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only — the publisher’s terms apply to the original document

Citation

Aksa Power Generation (2020). Data Center Power Systems. Aksa Power Generation. https://dubai.aksa.com.tr/Content/Upload/Datacenter/Data_Center_Eng.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.