Preventing arc flash incidents by design
Consulting-Specifying Engineer · Bruce W. Young
Bruce W. Young's article explaining the drivers of arc-flash incident energy and how labelling, maintenance settings and design choices reduce the hazard in critical facilities.
On this page
Overview
In this 2012 article in Consulting-Specifying Engineer, Bruce W. Young explains the drivers of arc-flash incident energy: available fault current and protective device characteristics. He then shows how labelling, maintenance settings and design choices reduce the hazard in critical facilities. The article is practice-oriented engineering writing, not a standard. The article therefore offers designers a way to reduce the hazard at design stage rather than after the calculation.
It starts from hazard and injury data: incident energy above 1.2 cal/cm2 can cause second-degree burns, and IEEE 1584 suggests a 2 s maximum arcing exposure time. Higher available fault current can reduce hazard because it shortens device clearing time. A main device may need separate line-side and load-side labels because its line side stays energized when open. Dual power paths let equipment be fully de-energized for work while operations continue.
The worked example is a 1,600 A, 480 V solid-state trip breaker. With coordinated settings, clearing takes about 13-19 s, the boundary is 105 in. and incident energy is 22 cal/cm2 (Category 3); with temporary maintenance settings it falls to 0.02 s, 15 in. and 0.86 cal/cm2. The author cautions that changing settings can nuisance-trip critical loads. A field incident on a 20-year-old switchboard illustrates the danger of forcing equipment that will not operate.
Key points
- Incident energy above 1.2 cal/cm2 can cause second-degree burns; IEEE 1584 suggests a 2 s maximum arcing exposure time.
- Higher available fault current can reduce hazard because it shortens device clearing time.
- A main device may need separate line-side and load-side labels because its line side stays energized when open.
- 1,600 A/480 V example: coordinated settings give about 13-19 s clearing, 105 in. boundary, 22 cal/cm2 (Category 3); maintenance settings give 0.02 s, 15 in., 0.86 cal/cm2.
- Dual power paths let equipment be fully de-energized for work while operations continue.
- Changing settings can nuisance-trip critical loads.
Using it in design
- Arc-flash outputs should label both line and load sides of mains and compare normal versus maintenance-mode settings.
- Recommend maintenance switches or ERMS on large LV mains.
- Recommend dual-path topologies so work can be done de-energized.
- Record in the report the risk that maintenance settings may nuisance-trip critical loads.
Monthly newsletter · free
Keep your reading list current
Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.
SoSo CAD
Review your power design in SoSo CAD
Inspect supply paths, equipment loads and UPS failure scenarios in one model.
Request a demo
Who should read it
Data centre electrical designers, engineers who run protection and selectivity studies and maintenance managers.
Related standards
- NFPA 70E
- IEEE 1584
Publication details
- Authors
- Bruce W. Young
- Publisher
- Consulting-Specifying Engineer
- Year
- 2012
- Document language
- English
- Source type
- Expert / community
- Access
- Free to read
- Licence
- Copyright retained; citation only — the publisher’s terms apply to the original document
Citation
Bruce W. Young (2012). Preventing arc flash incidents by design. Consulting-Specifying Engineer. https://www.csemag.com/articles/preventing-arc-flash-incidents-by-design/
Events on this subject
Browse the events calendarAll content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.