Harmonics in HVAC applications - Surprisingly simple ways to reduce harmonic mitigation costs
Danfoss
A Danfoss Drives brochure on harmonic distortion from VFDs driving fans, pumps and compressors in HVAC plants, with three design rules.
On this page
Overview
The brochure explains the causes and effects of harmonics, then lists the main mitigation options: passive filters, multi-pulse, active front end (AFE) and active filters. Its three rules are to mitigate only as far as regulations require, to design to a THDv target at the point of common coupling (PCC) rather than a per-drive THDi, and to choose by lifecycle losses.
The second rule in practice: regulations set voltage distortion limits, so design to 5% THDv at the PCC rather than specifying THDi of 5% or 8% at each drive. As a rule of thumb, mitigation is usually not needed when drive load is below 40% of total transformer loading, though generator supply needs care.
The worked hospital-ventilation example has 50 drives totalling about 2,100 kW, two 2,500 kVA transformers and a 4,600 kVA backup generator, with IEC/EN 61000-2-4 Class 1 required. Unmitigated THDv is 4.42% in normal mode but 7.05% when one 2,500 kVA transformer feeds both subsystems, failing Class 1; adding a 715 A active filter gives compliance in all modes.
In the cost comparison a central active filter shows about 37% lower operating cost than AFE drives, about 250 kEUR over 10 years at 0.1 EUR/kWh and 80% utilisation. The SiC-based AAF 007 active filter is claimed to have 60% lower losses than comparable filters; that is a manufacturer claim and rests on a single example plant.
Key points
- Design to 5% THDv at the PCC rather than THDi <= 5% or 8% at each drive.
- Mitigation is usually not needed when drive load is below 40% of total transformer loading; take care on generator supply.
- Example: 50 drives, about 2,100 kW, two 2,500 kVA transformers, 4,600 kVA generator; IEC/EN 61000-2-4 Class 1.
- Unmitigated THDv is 4.42% in normal mode but 7.05% with one transformer feeding both subsystems; a 715 A active filter gives compliance in all modes.
- Central active filter shows about 37% lower operating cost than AFE drives, about 250 kEUR over 10 years (0.1 EUR/kWh, 80% utilisation).
- The SiC-based AAF 007 is claimed to have 60% lower losses than comparable filters.
Using it in design
- In the power-quality check compute THDv at the PCC for every supply mode (both transformers, one transformer, generator only); generator mode is usually the worst case.
- Use 5% THDv as the default target (IEC 61000-2-4 Class 1 for sensitive loads; IEEE 519 where applicable).
- Suggest mitigation when VFD load exceeds about 40% of source rating.
- Compare a central active filter against AFE drives on 10-year loss cost.
Monthly newsletter · free
Keep your reading list current
Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.
SoSo CAD
Review your power design in SoSo CAD
Inspect supply paths, equipment loads and UPS failure scenarios in one model.
Request a demo
Who should read it
Electrical and mechanical designers assessing the harmonic impact of cooling-plant drives on transformer and generator supplies.
Related standards
- IEC 61000-2-4
- IEEE 519
- IEC 61000-3-12
Publication details
- Authors
- Danfoss
- Publisher
- Danfoss
- Year
- 2024
- Document number
- AD439926801978en-US0202
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only — the publisher’s terms apply to the original document
Citation
Danfoss (2024). Harmonics in HVAC applications - Surprisingly simple ways to reduce harmonic mitigation costs. Danfoss. AD439926801978en-US0202. https://assets.danfoss.com/documents/260397/AD439926801978en-US0202.pdf