Improving Thermal Performance in Data Centers Based on Numerical Simulations

Buildings (MDPI AG) · Yinjie Guo, Chunyu Zhao et al.

A 6SigmaDC study of a 552 m² cold-aisle-contained raised-floor hall (0.8 m floor, 226 cabinets at 6.3 kW, eleven 175 kW chilled-water units on one side): cabinets in the rows nearest the cooling units run hot because high-velocity plenum flow starves the nearest tiles.

CC BY 4.0 — share with attribution

On this page

Overview

The study asks how inappropriate temperature distribution when cooling servers with cold air aggravates the heat-dissipation problem, and how to correct it. The room is about 32.8 m × 16.9 m (552.38 m² including the AC room), 5 m high, with a 0.8 m raised floor and 50%-open grilles. It holds 226 cabinets of 6.3 kW (21 × 600 W 2U servers each) and eleven 175 kW chilled-water precision units, two of them redundant. The model was built from design data in 6SigmaDC.

Two fixes were tested: adjustable underfloor deflectors with adjusted grille openings in the near rows, and fan-assisted floor tiles in the nearest row. Underfloor deflectors under the grilles in rows O and N, with adjusted grille opening, raised airflow to near-side cabinets by 18.1% and cut airflow to far-side cabinets by 5.1%. Replacing the row-Q grilles with fan floor tiles raised near-side cabinet airflow by 4.9% and cut far-side airflow by 3.8%. The largest drop in average cabinet outlet temperature was 2.81 °C.

Both options balanced airflow between near and far cabinets, maximised cooling capacity and improved temperature uniformity. Because server racking is lengthy, data centres often do not run at full load; the study considered the most unfavourable case (full load) and showed both solutions keep server equipment within the normal temperature range even at full capacity.

Limits: the CFD model was not validated against measurements; the paper reports meshing but no measurement-based validation. Results depend on one hall geometry, and the cost, noise and control of fan tiles and deflectors were not assessed.

Key points

  1. The room is about 32.8 m × 16.9 m (552.38 m² including the AC room), 5 m high, 0.8 m raised floor, 50%-open grilles; 226 cabinets of 6.3 kW (21 × 600 W 2U servers) and eleven 175 kW chilled-water precision units, two redundant.
  2. Underfloor deflectors under the grilles in rows O and N, with adjusted grille opening, raised airflow to near-side cabinets by 18.1% and cut airflow to far-side cabinets by 5.1%.
  3. Replacing the row-Q grilles with fan floor tiles raised near-side cabinet airflow by 4.9% and cut far-side airflow by 3.8%.
  4. The largest drop in average cabinet outlet temperature was 2.81 °C.
  5. The model is built from design data in 6SigmaDC; the paper reports meshing but no measurement-based validation.

Using it in design

  • If cabinets in the rows nearest the cooling units run hot (high-velocity plenum flow starving the nearest tiles), consider adjustable underfloor deflectors and grille opening adjustment before fan-assisted tiles (18.1% and 4.9% airflow shift).
  • Verify the design at the full-load worst case, since racking is lengthy and the hall often runs at part load.
  • Label CFD results without measurement validation as indicative and compare them with tile airflow measurement at commissioning.

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Check cooling capacity alongside your design

Review zone heat loads, available capacity and the capacity balance after the largest unit is lost in SoSo CAD.

Request a demo
Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Who should read it

Cooling engineers balancing near- and far-side cabinets in raised-floor, cold-aisle-contained halls.

Document contents

  1. 1. Introduction
  2. 2. Fundamental Methods (2.1 Project Overview and Physical Model, 2.3 Post-Processing, 2.4 Transformation Process)
  3. 3. Comparison and Results (effect of the measures, CFD simulation analysis, CFD simulation analysis of cabinets at different heights)
  4. 4. Conclusions

Related standards

  • GB 50174 Code for design of data centers

Read the document

fan-floor-cabinet-airflow-balance-2024.pdf

PDF · 8.7 MB · English

CC BY 4.0 — share with attribution

The document is provided unaltered because its licence permits redistribution.

Publication details

Authors
Yinjie Guo; Chunyu Zhao; Hao Gao; Cheng Shen; Xu Fu
Publisher
Buildings (MDPI AG)
Year
2024
Volume
14
Issue
5
Pages
1416
Document language
English
Source type
Scientific
Access
Open licence — downloadable
Licence
CC BY 4.0 — share with attribution
Licence evidence
www.mdpi.com
Original licence note

PDF p.1: open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license.

Citation

Yinjie Guo; Chunyu Zhao; Hao Gao; Cheng Shen; Xu Fu (2024). Improving Thermal Performance in Data Centers Based on Numerical Simulations. Buildings (MDPI AG). 14(5), 1416. https://doi.org/10.3390/buildings14051416

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.