Research paperFree to read2020

Kalibre: Knowledge-based Neural Surrogate Model Calibration for Data Center Digital Twins

Proceedings of the 7th ACM International Conference on Systems for Energy-Efficient Buildings, Cities, and Transportation (ACM) · Ruihang Wang, Xin Zhou et al.

An ACM BuildSys 2020 paper that calibrates hard-to-measure parameters of data-hall CFD twins, especially per-server airflow, using a neural surrogate model and sensor data.

On this page

Overview

This paper, by Ruihang Wang and colleagues, was published in 2020 at ACM BuildSys (pages 200-209; DOI 10.1145/3408308.3427982, arXiv:2001.10681). It tackles the step that usually breaks data-hall CFD twins: parameters that are hard to measure, especially per-server airflow. This airflow depends on the server's internal fan control and is rarely in vendor specifications. The record rests only on the abstract and the paper's headline results.

The method is as follows: a neural surrogate is trained on CFD runs, the known thermophysics of the hall is embedded in the network, and parameters are searched on the surrogate against cold- and hot-aisle sensor readings. The best parameters are written back to the CFD model and re-checked against measurements, iterating until converged. According to the paper, manually built CFD models can give temperature prediction errors up to 5 C, citing prior work.

The results come from two production halls of hundreds of square metres hosting thousands of servers. The calibrated CFD achieved mean absolute errors (MAE) of 0.81 C and 0.75 C at tens of cold and hot aisle sensor positions, after about 5 hours on a 32-core VM. With the same compute budget, heuristic search and a plain neural surrogate reached MAEs of about 1.5-4 C, and manual calibration by a domain expert gave 1.32 C and 1.1 C (63% and 46% higher than Kalibre).

The paper also notes that sensors in the aisles mainly reflect nearby CRACs, and that inlet temperatures are often required to be between 15 C and 27 C. As a limit, the results are confined to two halls, and generalisation of the method to other hall types must be verified separately. It still offers a practical, measurable workflow for post-commissioning calibration of digital twins and a realistic accuracy target.

Key points

  1. Manually built CFD models can give temperature prediction errors up to 5 C (citing prior work), largely because per-server airflow is unknown and hard to measure at scale.
  2. Kalibre loop: (1) train a surrogate on CFD data, (2) search parameters by retraining the surrogate on sensor data, (3) write parameters back to CFD, (4) validate CFD against sensor ground truth.
  3. For two production halls of hundreds of square metres hosting thousands of servers, calibrated CFD achieved MAEs of 0.81 C and 0.75 C at tens of sensor positions, after about 5 hours on a 32-core VM.
  4. With the same compute budget, heuristic search and a plain neural surrogate reached MAEs of about 1.5-4 C, and manual expert calibration gave 1.32 C and 1.1 C (63% and 46% higher than Kalibre).
  5. Aisle sensors mainly reflect nearby CRACs, and inlet temperatures are often required to be between 15 C and 27 C.
  6. The method embeds physical knowledge in the neural network; the aim is to automate calibration.
  7. DOI 10.1145/3408308.3427982; arXiv:2001.10681.

Using it in design

  • Include a calibration workflow in the hand-over to operations: import aisle sensor data, mark per-server airflow (and bypass/recirculation) as calibration parameters with priors, and report MAE before and after calibration.
  • Use about 1 C MAE as a realistic twin-grade target.
  • Flag uncalibrated design models as possibly off by up to about 5 C.
  • Prefer vendor airflow-per-kW data in the server catalog to reduce unknowns.

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Check cooling capacity alongside your design

Review zone heat loads, available capacity and the capacity balance after the largest unit is lost in SoSo CAD.

Request a demo
Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Who should read it

Engineers and researchers building data-hall CFD models and digital twins and calibrating them in operation.

Related standards

  • ASHRAE TC 9.9 Thermal Guidelines for Data Processing Environments

Publication details

Authors
Ruihang Wang; Xin Zhou; Linsen Dong; Yonggang Wen; Rui Tan; Li Chen; Guan Wang; Feng Zeng
Publisher
Proceedings of the 7th ACM International Conference on Systems for Energy-Efficient Buildings, Cities, and Transportation (ACM)
Year
2020
Document number
arXiv:2001.10681
Pages
200-209
Document language
English
Source type
Scientific
Access
Free to read
Licence
arXiv distribution permission — reuse conditions remain with the rights holder
Original licence note

arXiv default licence; the ACM version carries an ACM copyright notice. Citation only.

Citation

Ruihang Wang; Xin Zhou; Linsen Dong; Yonggang Wen; Rui Tan; Li Chen; Guan Wang; Feng Zeng (2020). Kalibre: Knowledge-based Neural Surrogate Model Calibration for Data Center Digital Twins. Proceedings of the 7th ACM International Conference on Systems for Energy-Efficient Buildings, Cities, and Transportation (ACM). arXiv:2001.10681. 200-209. https://doi.org/10.1145/3408308.3427982

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.