Climate- and technology-specific PUE and WUE estimations for U.S. data centers using a hybrid statistical and thermodynamics-based approach
Resources, Conservation and Recycling (Elsevier BV) · Nuoa Lei, Eric Masanet
A physics-based facility model validated against reported operator data predicts annual PUE and WUE together for ten US data-centre archetypes covering size classes and cooling systems, run across 16 ASHRAE climate zones.
CC BY 4.0 — share with attribution
On this page
Overview
Data centres' on-site water use is becoming an important consideration for policy and energy analysis communities, but lack of operator-reported water usage effectiveness (WUE) values made it hard to quantify in macro-level models. The study fills this gap with thermodynamically compatible PUE and WUE values for a wide range of US data-centre archetypes and climate zones, using a physics-based model validated with real-world data. Archetypes cover size classes and cooling systems: airside economiser with or without adiabatic cooling, waterside economiser, water-cooled and air-cooled chillers and DX. Monte Carlo sampling of setpoints, equipment efficiencies and cooling-tower parameters gives ranges rather than single values.
Predicted median PUE ranges are 1.12-1.25 for large-scale data centres (cases 1-2), 1.39-1.98 for midsize (cases 3-7) and 1.71-2.22 for small (cases 8-10). The highest PUE generally occurs in climate zone 1A (hot moist) and the lowest in zone 8 (subarctic); airside-economiser-only cases have their lowest PUE in 4C (marine), and waterside-economiser cases in 3C.
Water-cooled chiller data centres with no economiser (cases 5 and 8) have the highest WUE because of cooling-tower water use. WUE falls only weakly in cooler climates because most rejected heat is the IT load itself, which does not depend on climate. Airside economisers with adiabatic cooling (case 1) use less water than airside economisers alone (case 3), because they reduce running hours of the more water-intensive supplemental cooling. Air-cooled chillers and DX systems have very small direct water use but are less energy-efficient, so their total footprint including indirect water may be significantly higher. WUE variance is largest for cooling-tower cases, with levers including more efficient chillers, windage drift eliminators and higher cycles of concentration within acceptable limits.
Limits: the facts reported come from the preprint version; the model is limited to US climate zones and ten archetypes, and results should be read as ranges and not transferred directly to other countries' climates and grids.
Key points
- Predicted median PUE ranges: 1.12-1.25 for large-scale (cases 1-2), 1.39-1.98 for midsize (cases 3-7) and 1.71-2.22 for small (cases 8-10).
- The highest PUE generally occurs in climate zone 1A (hot moist) and the lowest in zone 8 (subarctic); airside-economiser-only cases have their lowest PUE in 4C (marine) and waterside-economiser cases in 3C.
- Water-cooled chiller data centres with no economiser (cases 5 and 8) have the highest WUE; WUE falls only weakly in cooler climates because most rejected heat is the climate-independent IT load.
- Airside economisers with adiabatic cooling (case 1) use less water than airside economisers alone (case 3).
- Air-cooled chillers and DX have very small direct water use but are less energy-efficient; their total footprint including indirect water may be significantly higher.
- WUE variance is largest for cooling-tower cases; levers include more efficient chillers, windage drift eliminators and higher cycles of concentration within acceptable limits.
Using it in design
- In early data-centre design, set PUE and WUE targets by size class, cooling system and climate zone using this study's ranges (for example 1.71-2.22 for small rooms, 1.12-1.25 for large scale).
- For cooling-tower designs, evaluate more efficient chillers, drift eliminators and higher cycles of concentration as WUE levers.
- When choosing air-cooled chillers or DX, weigh low direct water use against the increase in energy and indirect water.
Monthly newsletter · free
Keep your reading list current
Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.
SoSo CAD
Check cooling capacity alongside your design
Review zone heat loads, available capacity and the capacity balance after the largest unit is lost in SoSo CAD.
Request a demo
Who should read it
Energy analysts and designers modelling data-centre energy and water use by size, cooling system and climate.
Document contents
- 1. Introduction
- 2. Previous WUE analyses
- 3. Methodology (3.1 Modeling scope and system definitions, 3.2 DC PUE and WUE model, 3.3 Model inputs and data sources, 3.4 Uncertainty and sensitivity analysis)
- 4. Results and discussion (4.1 Model validation, 4.2 On-site PUE and WUE simulation results, 4.3 Climate dependent practical minimum PUE and WUE values, 4.4 Sensitivity analysis results)
- 5. Conclusions
Related standards
- ASHRAE TC9.9 Thermal Guidelines
- ASHRAE 90.4
- ISO/IEC 30134-9 (WUE)
Read the document
lei-masanet-climate-pue-wue-us-2022.pdf
CC BY 4.0 — share with attribution
The document is provided unaltered because its licence permits redistribution.
Publication details
- Authors
- Nuoa Lei; Eric Masanet
- Publisher
- Resources, Conservation and Recycling (Elsevier BV)
- Year
- 2022
- Volume
- 182
- Pages
- 106323
- Document language
- English
- Source type
- Scientific
- Access
- Open licence — downloadable
- Licence
- CC BY 4.0 — share with attribution
- Licence evidence
- www.researchsquare.com
Original licence note
Downloaded file is the Research Square preprint (DOI 10.21203/rs.3.rs-769999/v1, titled 'Climate- and Technology-Specific PUE and WUE Predictions for U.S. Data Centers using a Physics-Based Approach'). Its cover page states it is licensed under CC BY 4.0. The journal version is also CC BY, but numbers in it may differ from this preprint.
Citation
Nuoa Lei; Eric Masanet (2022). Climate- and technology-specific PUE and WUE estimations for U.S. data centers using a hybrid statistical and thermodynamics-based approach. Resources, Conservation and Recycling (Elsevier BV). 182, 106323. https://doi.org/10.1016/j.resconrec.2022.106323