Finding Sustainable Solutions to Data Center Power and Water Use

Nortek Air Solutions · Philip LePoudre, Pooya Navid

This Nortek paper on the StatePoint Liquid Cooling system argues for designing cooling for typical annual conditions instead of 20- or 50-year extremes. A 20 MW Frankfurt colocation case compares pPUE and water use across plant types.

On this page

Overview

StatePoint is an indirect evaporative chilled-water plant built around a membrane exchanger that keeps air and water separate. The paper proposes designing for typical annual conditions and accepting brief, allowed excursions in supply-air temperature (SAT). In 100% free-cooling applications the plant reaches pPUE 1.05-1.06 (1.025-1.03 excluding fan-coil wall energy), with annualised WUE below 0.1 L/kWh depending on climate. The manufacturer claims annual water and power reductions of up to 90% and 60% versus chiller/cooling-tower plants; the early development target was 20-30%.

The Frankfurt case is a 20 MW colocation with 12 StatePoint units at N+2, compared with hybrid fluid coolers and open cooling towers on annual pPUE/WUE versus SAT. Raising annual SAT from 23 to 29 C markedly improves pPUE and WUE. The peak design condition pairs ASHRAE N50 dry bulb 39.1 C with N20 wet bulb 23.9 C; letting SAT rise into the ASHRAE A1/A2 allowable range at that extreme greatly reduces trim-chiller capacity.

The peak numbers give a separate result for electrical sizing. At 100% IT load, the ASHRAE 50-year extreme and 1-2 units offline, peak pPUE is 1.23 for StatePoint, 1.28 for the hybrid cooler and 1.275 for the cooling tower, which is about 230 kW versus 275-280 kW of cooling power per 1,000 kW of IT. Peak hourly make-up water is about 41% below the hybrid cooler and 6% below the cooling tower. The paper also covers the membrane's water-quality and Legionella advantages and smaller on-site water storage. The comparisons come from the manufacturer's own case study.

Key points

  1. In 100% free cooling, pPUE 1.05-1.06 (1.025-1.03 excluding fan-coil wall energy); annualised WUE <0.1 L/kWh depending on climate.
  2. Manufacturer claim: up to 90% less annual water and 60% less power than chiller/tower plants; early target 20-30%.
  3. Frankfurt: 20 MW colocation, 12 StatePoint units at N+2.
  4. Raising annual SAT from 23 to 29 C markedly improves pPUE and WUE.
  5. Peak condition: ASHRAE N50 dry bulb 39.1 C coincident with N20 wet bulb 23.9 C.
  6. Peak pPUE: StatePoint 1.23, hybrid cooler 1.28, cooling tower 1.275 (~230 kW versus 275-280 kW per 1,000 kW IT).
  7. Peak hourly make-up water ~41% below a hybrid cooler and ~6% below a cooling tower.

Using it in design

  • Support peak pPUE (electrical sizing, with N-x units offline at ASHRAE N50/N20 extremes) separately from annual pPUE/WUE (energy) in the cooling plant model.
  • Take allowable SAT excursion hours and ASHRAE A1/A2 limits as inputs; they drive trim-chiller sizing.
  • Add an indirect evaporative chilled-water plant type to the catalog with a WUE curve versus SAT.
  • Size make-up water and storage in the water module from peak instantaneous evaporation, not the annual average.

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Check cooling capacity alongside your design

Review zone heat loads, available capacity and the capacity balance after the largest unit is lost in SoSo CAD.

Request a demo
Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Who should read it

Design engineers and investment decision makers choosing cooling plant for water- and power-constrained sites.

Related standards

  • ASHRAE TC 9.9 Thermal Guidelines
  • ISO/IEC 30134-2
  • ISO/IEC 30134-9

Publication details

Authors
Philip LePoudre; Pooya Navid
Publisher
Nortek Air Solutions
Year
2021
Document number
752F-0721
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only — the publisher’s terms apply to the original document

Citation

Philip LePoudre; Pooya Navid (2021). Finding Sustainable Solutions to Data Center Power and Water Use. Nortek Air Solutions. 752F-0721. https://www.nortekdatacenter.com/wp-content/uploads/2021/07/752F-0721-NDCC-StatePoint-Solutions-to-Power-Water-Use-wp-1.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.