Report: Field Pilot of Low Carbon Concrete
Original title Report: Field Pilot of Low Carbon Concrete (OCP DCF Sustainability), July 2026
Open Compute Project Foundation · Chhiba, P. (Google), Kusuma, J. (Meta) et al.
A report backed by Google, Meta and Microsoft that compares four concrete mixes for data centre slabs-on-ground in the laboratory and in full-scale placement. It shows, with numbers, what the mixes with 30%, 43% and 57% lower embodied carbon cost in performance and constructability.
CC BY-SA 4.0 — share with attribution under the same licence
On this page
Overview
The OCP-supported project aims to de-risk the adoption of low embodied carbon concrete in data centre slabs, an application treated as high risk. The July 2026 report describes four full-scale slabs placed on July 31 and August 1, 2024 at Wiss, Janney, Elstner Associates' campus in Northbrook, IL. A contractor, a ready-mix supplier and consultants took part, and the mixes were judged against a collective hyperscaler specification.
The four mixes: Mix 1 (control) is a typical data centre mix with ASTM C595 Type IL cement at 517 lb/yd3 and w/cm 0.50, with embodied carbon of 214 kg CO2e/yd3. Mix 2 keeps w/cm 0.50, cuts total cementitious content to 491 lb/yd3 and replaces 40% of the Type IL cement with ASTM C989 slag cement (149 kg, 30% lower). Mix 3 is about 80% ASTM C1157 performance cement and 20% Type IL at 605 lb/yd3 and w/cm 0.35 (121 kg, 43% lower). Mix 4 is C1157 alone at 750 lb/yd3 and w/cm 0.34 (92 kg, 57% lower).
The laboratory programme covered fresh and hardened properties: slump, air, unit weight, bleed, heat of hydration, setting, compressive and flexural strength, drying shrinkage, cracking resistance, coefficient of thermal expansion and bulk resistivity. All mixes met the typical specification limits of maximum 3.0% air, 5 to 9 in slump and at least 4,000 psi at 28 days. Mixes 3 and 4, however, were extremely thixotropic, lost workability quickly and produced almost no bleed water, which raises early-age plastic shrinkage risk and complicates finishing timing.
In the field all four mixes were pumped, placed, finished and reached design strength. Mixes 3 and 4, the lowest-carbon options, lost workability within 15 to 20 minutes of placement, making surface closing, screeding, floating and troweling difficult. The report concludes that, as formulated, they cannot be used effectively for traditional slab-on-ground construction without changes that improve workability or adjustments to construction practice. The scale is small and rests on a single placement event.
Key points
- Embodied carbon (kg CO2e/yd3): Mix 1 control 214; Mix 2 149 (30% lower); Mix 3 121 (43%); Mix 4 92 (57%). Against the national 236 kg and regional 231 kg benchmarks Mix 4 is 61% and 60% lower.
- Mix 2 (40% slag cement) behaved closest to the control and was judged the best performer by the contractor and WJE observation.
- Mixes 3 and 4 were extremely thixotropic and lost workability quickly; in the field workability dropped 15 to 20 minutes after placement.
- Mix 3 set very fast (accelerator was reduced) and Mix 4 had a delayed final set; both showed little to no bleed water.
- 28-day laboratory compressive strength: Mix 1 5,870 psi, Mix 2 5,750, Mix 3 8,100, Mix 4 4,140 psi against the 4,000 psi minimum; Mix 4 has a very thin margin.
- Drying shrinkage met the specification in all four mixes, with markedly lower shrinkage in Mixes 3 and 4. Restrained-shrinkage cracking potential is moderate to high for Mixes 1, 2 and 3 and low for Mix 4.
- Floor flatness FF: Mix 1 44.6; Mix 2 44.9; Mix 3 33.5; Mix 4 34.1. Most hyperscalers require overall FF 35 and one requires 25; Mixes 3 and 4 fell slightly short of some requirements.
- Abrasion testing showed very little abrasion depth for Mixes 2, 3 and 4, so a densified, abrasion-resistant surface is achievable with lower-carbon mixes.
- Heat of hydration is lower in Mixes 3 and 4, which matters little for this indoor project but helps mass concrete.
Using it in design
- Write the slab embodied-carbon target into the specification together with an EPD requirement and tie it to national or regional benchmarks as a percentage; a 30% reduction against the control is a low-risk starting point.
- When proposing slag cement replacement (for example 40%), require control-like w/cm and strength behaviour as in Mix 2; require a laboratory trial before moving to C1157-heavy mixes.
- Ask for a pre-construction laboratory package beyond standard tests: setting times, bleed, heat of hydration, drying and restrained shrinkage, thermal expansion and workability loss over time.
- Review the floor flatness requirement (FF 35 or 25) alongside lower-carbon mixes, and plan finishing time, crew size and measures such as evaporation retarder for high-binder, thixotropic mixes.
- Leave a strength margin for site variability on borderline mixes such as Mix 4, and for over-strength mixes such as Mix 3 consider cutting binder content to lower carbon further.
- Verify with the structural and construction consultant whether the reduced shrinkage cracking can support wider joint spacing.
Monthly newsletter · free
Keep your reading list current
Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.
SoSo CAD
Compare the cost of design decisions
Evaluate equipment costs, energy expenses and total cost of ownership (TCO) using your inputs and assumptions in SoSo CAD.
Request a demo
Who should read it
Data centre structural and construction engineers, sustainability managers, concrete suppliers and contractors.
Document contents
- Executive Summary
- Introduction
- Compliance with Open Compute Project Tenets
- Laboratory Evaluations
- Raw Materials Characterization Results
- Concrete Physical Testing Results
- Field Placement
- Concrete Placement
- Field Quality Control Testing
- Field Abrasion Testing
- Appendix A. Environmental Product Declarations
- Appendix B. Raw Material Characterization
- Appendix C. Lab Testing - Plastic Concrete Properties
- Appendix D. Lab Testing - Physical Testing Results
- Appendix E. Slab Design Drawings and Locations
- Appendix F. Field Testing - Physical Testing Results
- Appendix G. Field Abrasion Testing
Related standards
- ASTM C595
- ASTM C989
- ASTM C1157
- ACI 302.1R
- OCP Embodied Carbon Disclosure Base Specification
Read the document
ocp-dcf-low-carbon-concrete-pilot.pdf
CC BY-SA 4.0 — share with attribution under the same licence
The document is provided unaltered because its licence permits redistribution.
Publication details
- Authors
- Chhiba, P. (Google); Kusuma, J. (Meta); Masri, F. (Google); Stanley, B. (Microsoft); key contributor Kim, J. (WJE)
- Publisher
- Open Compute Project Foundation
- Year
- 2026
- Document language
- English
- Source type
- Industry body
- Access
- Open licence — downloadable
- Licence
- CC BY-SA 4.0 — share with attribution under the same licence
- Licence evidence
- www.opencompute.org
Original licence note
Pages 2-3 and the footer of each page state the work is licensed under a Creative Commons Attribution-ShareAlike 4.0 International License.
Citation
Chhiba, P. (Google); Kusuma, J. (Meta); Masri, F. (Google); Stanley, B. (Microsoft); key contributor Kim, J. (WJE) (2026). Report: Field Pilot of Low Carbon Concrete (OCP DCF Sustainability), July 2026. Open Compute Project Foundation. https://www.opencompute.org/documents/dcf-sustainability-field-pilot-of-low-carbon-concrete-final-pdf/
Events on this subject
Browse the events calendarAll content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.