Research paperPDF2019

Cooling Effectiveness of a Data Center Room under Overhead Airflow via Entropy Generation Assessment in Transient Scenarios

Entropy (MDPI AG) · Luis Silva-Llanca, Marcelo del Valle et al.

An idealised, fully contained aisle cooled not by raised-floor tiles but by five overhead air-to-water heat exchangers above the aisle, comparing overhead downward flow with overhead upward flow.

CC BY 4.0 — share with attribution

On this page

Overview

The paper evaluates two strategies for delivering cold air into a data centre room with a dynamic modelling approach; the common method supplies air through perforated floor tiles from a centralised distribution system, which hinders flow management at aisle level. The idealised room has 10 racks of 10 servers (4U) each at a constant 1 kW per server, totalling 100 kW handled by five overhead heat exchangers, with a fully contained aisle and adiabatic room walls. In one case the exchangers force airflow downward into the aisle (ODF); in the other upward (OUF).

Servers and heat exchangers are compact differential-equation models in MATLAB (validated against experiments in earlier work) that include thermal mass, coupled to a transient k-epsilon Fluent model of the air side. The transient run reached steady state at t of about 3400 s, with the time step varied dynamically from 0.1 to 1 s. A mesh study found that only the finest mesh captured air-side entropy generation within 3%.

With containment, air-side entropy generation was only 0.15% (downward flow) and 0.03% (upward flow) of the total, compared with an earlier estimate of 34% for an uncontained legacy room. Overhead supply met less resistance than perforated-tile supply and gave a uniform distribution of cold air into the servers, with server temperatures uniform across the racks. Downward and upward flow gave nearly identical cooling performance, and a second-law analysis quantified the room cooling efficacy.

Limits: the geometry is idealised and the study gives no failure transients, so it is evidence for overhead and in-aisle cooling concepts and for compact-model coupling rather than for design values. The choice between upward and downward flow may depend on geometric, mechanical and economic aspects.

Key points

  1. Idealised room: 10 racks of 10 servers (4U) each at a constant 1 kW per server, totalling 100 kW handled by five overhead heat exchangers, with a fully contained aisle and adiabatic walls.
  2. Servers and heat exchangers are compact differential-equation models in MATLAB (validated against experiments in earlier work) coupled to a transient k-epsilon Fluent model of the air side.
  3. The transient run reached steady state at t of about 3400 s, with the time step varied dynamically from 0.1 to 1 s; only the finest mesh captured air-side entropy generation within 3%.
  4. With containment, air-side entropy generation was only 0.15% (downward flow) and 0.03% (upward flow) of the total, against an earlier estimate of 34% for an uncontained legacy room.
  5. Overhead supply met less resistance than perforated-tile supply and gave a uniform distribution of cold air into the servers.
  6. Downward and upward flow gave nearly identical cooling performance.

Using it in design

  • Use in the design rationale that aisle containment cut air-side entropy generation to negligible levels (0.15% and 0.03%), against 34% for an uncontained legacy room.
  • When comparing overhead or in-aisle heat exchanger concepts with perforated-tile supply, weigh that overhead supply gave less resistance and more uniform server inlet conditions; let geometry, mechanics and economics decide upward versus downward flow.
  • Include server and exchanger thermal mass through compact models in transient cooling models, and label results from an idealised geometry as concept evidence, not design values.

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Check cooling capacity alongside your design

Review zone heat loads, available capacity and the capacity balance after the largest unit is lost in SoSo CAD.

Request a demo
Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Who should read it

Cooling designers and researchers evaluating overhead and in-aisle cooling concepts and transient thermal models.

Document contents

  1. 1. Introduction
  2. 2. Motivation and Goals
  3. 3. Mathematical Model and Numerical Implementation (3.1 Airside, 3.2 Server Transient Model, 3.3 Heat Exchanger Transient Model, 3.4 Entropy Generation, 3.5 Numerical Procedure, 3.6 Grid Independence)
  4. 4. Steady State Analysis (4.1 Entropy Generation in an Idealized Case)
  5. 6. Conclusions

Read the document

overhead-airflow-transient-entropy-2019.pdf

PDF · 2.3 MB · English

CC BY 4.0 — share with attribution

The document is provided unaltered because its licence permits redistribution.

Publication details

Authors
Luis Silva-Llanca; Marcelo del Valle; Alfonso Ortega; Andrés J. Díaz
Publisher
Entropy (MDPI AG)
Year
2019
Volume
21
Issue
1
Pages
98
Document language
English
Source type
Scientific
Access
Open licence — downloadable
Licence
CC BY 4.0 — share with attribution
Licence evidence
www.mdpi.com
Original licence note

PDF p.1: open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license.

Citation

Luis Silva-Llanca; Marcelo del Valle; Alfonso Ortega; Andrés J. Díaz (2019). Cooling Effectiveness of a Data Center Room under Overhead Airflow via Entropy Generation Assessment in Transient Scenarios. Entropy (MDPI AG). 21(1), 98. https://doi.org/10.3390/e21010098

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.