Research paperPDF2022

Techno-economic analysis of a PV/T waste heat–driven compound ejector-heat pump for simultaneous data centre cooling and district heating using low global warming potential refrigerants

Mitigation and Adaptation Strategies for Global Change (Springer Science and Business Media LLC) · Ali Khalid Shaker Al-Sayyab, Joaquín Navarro-Esbrí et al.

Universitat Jaume I researchers simulate a compound ejector heat pump that cools a data centre and at the same time delivers recovered heat to a district heating network, with waste heat from a PV/T array driving the ejector.

CC BY 4.0 — share with attribution

On this page

Overview

The study presents a comprehensive techno-economic evaluation of an innovative compound ejector-heat pump system for simultaneous data-centre cooling and waste-heat recovery for district heating. The new system avoids the ejector pump by combining PV/T waste heat with an evaporative condenser as the ejector driving force, and compares several low-GWP alternatives to R134a (R515B, R515A, R1234ze(E), R290 and others) on COP, PUE, ERE/ERF, cost rate, payback and CO2-eq.

Hourly performance used real ambient and solar data for Valencia (Spain). The DHN water temperature rise across the condenser was fixed at 20 °C and condensing temperature varied from 50 to 70 °C. Metrics used were ERE = (Total Energy - E_reused)/IT power and ERF = E_reused/Total Energy. With R515B the system raised COP by 54% in cooling mode and 49% in heating mode, the largest gain among the refrigerants studied.

The system improved the data-centre PUE index by 10 to 19%; R515B gave the largest PUE reduction (quantified at 1.48) and the highest electricity saving, 84.1 MWh per year. R290 gave the highest ERF of the refrigerants examined. The shortest payback, 6.3 years, came with R515B, followed by R515A and R1234ze(E); these three also cut CO2-eq emissions most, by 49%.

Limits: a simulation for Valencia's climate and one system configuration; the design suits heat-pump-based reuse of low-grade data-centre heat in warm climates and does not transfer directly to cold climates or different DH temperatures. Its ERE and ERF equations match the standard metric definitions.

Key points

  1. Hourly performance used real ambient and solar data for Valencia (Spain); the DHN water temperature rise across the condenser was fixed at 20 °C and condensing temperature varied from 50 to 70 °C.
  2. Metrics used were ERE = (Total Energy - E_reused)/IT power and ERF = E_reused/Total Energy.
  3. With R515B the system raised COP by 54% in cooling mode and 49% in heating mode, the largest gain among the refrigerants studied.
  4. The system improved the data-centre PUE index by 10 to 19%; R515B gave the largest PUE reduction (quantified at 1.48) and the highest electricity saving, 84.1 MWh per year.
  5. R290 gave the highest ERF of the refrigerants examined.
  6. The shortest payback, 6.3 years, came with R515B, followed by R515A and R1234ze(E); these three also cut CO2-eq emissions most, by 49%.

Using it in design

  • When combining data-centre cooling and heat recovery for district heating in one heat-pump system, select the refrigerant among low-GWP alternatives with COP, PUE, ERF and payback together.
  • Report heat reuse with ERE and ERF (ERE = (Total − E_reused)/IT power; ERF = E_reused/Total).
  • Set the condensing temperature from DH requirements (50-70 °C, 20 °C water rise) and label results with the warm-climate assumption.

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Compare the cost of design decisions

Evaluate equipment costs, energy expenses and total cost of ownership (TCO) using your inputs and assumptions in SoSo CAD.

Request a demo
CAPEX and TCO estimates in the SoSo CAD cost workspace

Who should read it

Engineers combining data-centre cooling and heat reuse with heat pumps, and researchers evaluating low-GWP refrigerant options.

Document contents

  1. 1 Introduction
  2. System description, thermodynamic and economic model
  3. Hourly simulation results: COP, PUE, ERE/ERF
  4. Cost rate, payback and CO2-eq
  5. Conclusions

Related standards

  • EN 50600-4-6 (ERF)
  • The Green Grid ERE

Read the document

pvt-ejector-heat-pump-dc-tea-2022.pdf

PDF · 3.0 MB · English

CC BY 4.0 — share with attribution

The document is provided unaltered because its licence permits redistribution.

Publication details

Authors
Ali Khalid Shaker Al-Sayyab; Joaquín Navarro-Esbrí; Angel Barragán-Cervera; Adrián Mota-Babiloni
Publisher
Mitigation and Adaptation Strategies for Global Change (Springer Science and Business Media LLC)
Year
2022
Volume
27
Issue
7
Pages
43
Document language
English
Source type
Scientific
Access
Open licence — downloadable
Licence
CC BY 4.0 — share with attribution
Licence evidence
doi.org
Original licence note

Article states it is open access under a Creative Commons Attribution (CC BY / CC BY 4.0) licence (verified in PDF text).

Citation

Ali Khalid Shaker Al-Sayyab; Joaquín Navarro-Esbrí; Angel Barragán-Cervera; Adrián Mota-Babiloni (2022). Techno-economic analysis of a PV/T waste heat–driven compound ejector-heat pump for simultaneous data centre cooling and district heating using low global warming potential refrigerants. Mitigation and Adaptation Strategies for Global Change (Springer Science and Business Media LLC). 27(7), 43. https://doi.org/10.1007/s11027-022-10017-6

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.