Properly Accounting for Scope 2 Emissions in the Age of Flexible Data Centers
Schneider Electric · Stuart Sheehan
A Schneider Electric white paper (WP 267, 2025) arguing that annual-average location-based Scope 2 accounting can misstate emissions as grids decarbonize and data centers operate flexibly, and why hourly or sub-hourly emission factors are needed.
On this page
Overview
The paper argues that annual-average location-based Scope 2 accounting misleads in two situations: when the grid decarbonizes, and when a data center can shift its load in time. An annual-average factor cannot tell whether load fell in a low-carbon hour or a high-carbon one. The author therefore proposes time-resolved accounting with hourly or sub-hourly emission factors.
In the example grid, the emission factor varies widely across hours: the lowest-decile hours are about 40% below the average and the highest-decile hours about 24% above it. That spread explains why shifting load toward cleaner hours changes real emissions while the annual average cannot see it. In the examples, annual-average and time-resolved estimates differ by up to about 15%.
The methodology section recommends 15-minute or hourly factors for flexible sites. Time-resolved accounting can reward load flexibility and can align carbon reduction with energy-cost reduction. The record shows percentages from one example grid, so the 15% and the 40%/24% figures should not be carried to other grids; they illustrate why the method is needed.
Key points
- Annual-average and time-resolved Scope 2 estimates can differ by up to about 15% in the examples.
- In the example grid, lowest-decile hours sit about 40% below the average emission factor.
- Highest-decile hours sit about 24% above the average.
- 15-minute or hourly emission factors are recommended for flexible sites.
- Load shifting creates real emission changes that annual averages do not show.
- Time-resolved accounting can reward flexibility and align carbon and energy-cost reduction.
Using it in design
- Allow an hourly (8760 h) emission-factor profile input in the carbon calculator, falling back to the annual average.
- When BESS or workload shifting is modelled, compute Scope 2 hour by hour.
- Show annual-average and time-resolved results side by side in the report.
Monthly newsletter · free
Keep your reading list current
Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.
SoSo CAD
Compare the cost of design decisions
Evaluate equipment costs, energy expenses and total cost of ownership (TCO) using your inputs and assumptions in SoSo CAD.
Request a demo
Who should read it
Sustainability specialists doing carbon reporting and designers modelling flexible load and batteries.
Related standards
- GHG Protocol Scope 2 Guidance
Publication details
- Authors
- Stuart Sheehan
- Publisher
- Schneider Electric
- Year
- 2025
- Document number
- WP 267
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only — the publisher’s terms apply to the original document
Citation
Stuart Sheehan (2025). Properly Accounting for Scope 2 Emissions in the Age of Flexible Data Centers. Schneider Electric. WP 267. https://download.schneider-electric.com/files?p_Doc_Ref=SPD_WP267_EN
Events on this subject
Browse the events calendarAll content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.