Research paperPDF2025

Performance improvement of high-density data center via two-phase liquid immersion cooling

Journal of Thermal Analysis and Calorimetry (Springer Science and Business Media LLC) · Nada M. Mohammed, Wael M. El-Maghlany et al.

Alexandria University researchers use 3D ANSYS CFD to compare cooling for a high-density data hall of up to 1168 kW: raised-floor air cooling with hot-aisle containment versus two-phase immersion tanks using FC-72, with copper coatings of different thicknesses tested on server components in the immersion case.

CC BY 4.0 — share with attribution

On this page

Overview

The study introduces two approaches for efficiently cooling high-density data centres with a capacity of up to 1168 kW, aiming to find the optimal method for extracting heat from electronic servers: air-based cooling with modifications to hot-aisle containment, and liquid-based cooling using a two-phase immersion system. Three-dimensional CFD simulations were conducted, and the influence of copper coating on server components in liquid cooling was examined by varying thickness.

With the best air configuration (raised floor plus hot-aisle containment), low-power racks ran at 50-90 °C and higher-power racks at 65-122 °C, with prominent hot spots from non-uniform airflow. Two-phase immersion with FC-72 kept low-power server tanks at 56 °C to below 61 °C and high-power servers at 56-65 °C at maximum hot spots. Total power for all high-power tanks was about 8.5 kW and for low-power tanks 7.5 kW, giving a reported liquid-cooling PUE of about 1.01 versus 2 for air cooling.

Copper coating lowered maximum temperature by 3 °C for high-power and 1.5 °C for low-power servers, with maximum uniformity improvements of 13% and 8% respectively. It gave a 13% improvement in temperature distribution among high-power servers and eliminated most hot spots by decreasing the maximum temperature, against 8% for low-power servers.

Limits: the reported PUE of 1.01 counts only tank-level power and excludes the external heat-rejection loop (heat exchangers, pumps, pipes), which the authors leave for future work, so it is optimistic. The study is CFD only, with no experimental validation.

Key points

  1. The study considers high-density data centres with a capacity of up to 1168 kW.
  2. With the best air configuration (raised floor plus hot-aisle containment), low-power racks ran at 50-90 °C and higher-power racks at 65-122 °C, with prominent hot spots from non-uniform airflow.
  3. Two-phase immersion with FC-72 kept low-power server tanks at 56 °C to below 61 °C and high-power servers at 56-65 °C at maximum hot spots.
  4. Total power for all high-power tanks was about 8.5 kW and for low-power tanks 7.5 kW, giving a reported liquid-cooling PUE of about 1.01 versus 2 for air cooling.
  5. Copper coating lowered maximum temperature by 3 °C for high-power and 1.5 °C for low-power servers, with maximum uniformity improvements of 13% and 8%.
  6. Future work is stated to include the full liquid-cooling cycle (heat exchangers, pumps, pipes), so the system efficiency figures exclude that loop.

Using it in design

  • Verify two-phase immersion PUE claims so they include the external heat-rejection loop (exchangers, pumps, pipes) and not just tank-level power; the 1.01 figure excludes it.
  • Compare the air-cooling hot-spot risk in a high-density hall (65-122 °C) with the uniform temperature of two-phase immersion (56-65 °C).
  • Consider copper coating as a hot-spot reduction option for high-power servers (maximum temperature -3 °C, uniformity 13%).

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Check cooling capacity alongside your design

Review zone heat loads, available capacity and the capacity balance after the largest unit is lost in SoSo CAD.

Request a demo
Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Who should read it

Cooling designers comparing air and two-phase immersion cooling for high-density halls.

Document contents

  1. Introduction
  2. Methodology (air-based cooling configurations, two-phase immersion tanks, CFD model)
  3. Results (air-cooling temperatures, two-phase immersion temperatures, copper coating effect, PUE)
  4. Conclusion and future work

Read the document

two-phase-immersion-hd-dc-performance-2025.pdf

PDF · 4.3 MB · English

CC BY 4.0 — share with attribution

The document is provided unaltered because its licence permits redistribution.

Publication details

Authors
Nada M. Mohammed; Wael M. El-Maghlany; Mohamed Elhelw; Ahmed H. Abdelaziz
Publisher
Journal of Thermal Analysis and Calorimetry (Springer Science and Business Media LLC)
Year
2025
Volume
150
Issue
6
Pages
4279-4294
Document language
English
Source type
Scientific
Access
Open licence — downloadable
Licence
CC BY 4.0 — share with attribution
Licence evidence
doi.org
Original licence note

Article states it is open access under a Creative Commons Attribution (CC BY / CC BY 4.0) licence (verified in PDF text).

Citation

Nada M. Mohammed; Wael M. El-Maghlany; Mohamed Elhelw; Ahmed H. Abdelaziz (2025). Performance improvement of high-density data center via two-phase liquid immersion cooling. Journal of Thermal Analysis and Calorimetry (Springer Science and Business Media LLC). 150(6), 4279-4294. https://doi.org/10.1007/s10973-025-14006-0

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.