Technical guideFree to read2025

The Importance of Mutual Understanding Between IT and Facilities - Part 2: Specifying A1, A2, A3, or A4 Servers

Upsite Technologies blog · Ian Seaton

An Upsite blog post arguing that the ASHRAE class of servers that IT procures can affect mechanical efficiency more than the choice of cooling equipment.

On this page

Overview

Published on the Upsite Technologies blog in 2025, Ian Seaton's post is the second part of a series on mutual understanding between IT and facilities. Its central argument is that the ASHRAE class of the servers IT buys can affect mechanical efficiency more than the choice of cooling equipment. It is an expert opinion piece and is freely readable.

The author reviews allowable ranges by class. Most servers sold are Class A2; A4 is mainly ruggedized equipment and carries a significant price premium. For reliability analysis he uses the X-factor method with a Chicago example: in the Chicago air-side economizer case, server reliability improved by about 1% compared with a constant 68 F baseline. He recommends translating percentages into counts: a 0.5% failure rate on 1,000 servers is about 5 failures, and a 5% increase adds roughly one failure per 1,000 servers over four years.

The post lists cities where Class A2 or A3 servers can be cooled year-round without refrigerant-based cooling. For Class A2, year-round free cooling is possible in, for example, Albuquerque, Boston, Chicago, Denver, Frankfurt, Phoenix and San Jose; A3 adds Austin, Dubai, Las Vegas and Sydney. Free cooling may cover roughly 80-90% of the year depending on bin data and can back up chillers to reduce redundant plant.

The author weighs the higher procurement cost of A3 servers against the chiller plant avoided, and notes that free cooling can add a layer of redundancy behind the mechanical plant. The limit of the post is that it is a blog article and the results depend on the chosen cities and hourly temperature data. The related document is ASHRAE Thermal Guidelines.

Key points

  1. Most servers sold are Class A2; A4 is mainly ruggedized equipment with a significant price premium.
  2. Chicago air-side economizer case: server reliability improved about 1% versus a constant 68 F baseline.
  3. Translate percentages to counts: a 0.5% failure rate on 1,000 servers is about 5 failures; a 5% increase adds roughly one failure per 1,000 servers over four years.
  4. Class A2 allows year-round free cooling in e.g. Albuquerque, Boston, Chicago, Denver, Frankfurt, Phoenix, San Jose; A3 adds Austin, Dubai, Las Vegas, Sydney.
  5. Free cooling may cover roughly 80-90% of the year depending on bin data, and can back up chillers to reduce redundant plant.
  6. Server ASHRAE class can affect mechanical efficiency more than the choice of cooling equipment.
  7. The higher A3 procurement cost is weighed against chiller-plant avoidance.

Using it in design

  • Expose server ASHRAE class as a project-level design input that drives economizer hours, chiller sizing and redundancy credit.
  • Provide a per-site check of whether year-round compressor-free operation is possible for the selected class.
  • Show the extra A3 procurement cost alongside the chiller plant avoided.
  • Evaluate free cooling separately as a redundancy layer behind the mechanical plant.

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Check cooling capacity alongside your design

Review zone heat loads, available capacity and the capacity balance after the largest unit is lost in SoSo CAD.

Request a demo
Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Who should read it

IT managers, facility engineers and designers who make server procurement class and mechanical design decisions together.

Related standards

  • ASHRAE Thermal Guidelines for Data Processing Environments

Publication details

Authors
Ian Seaton
Publisher
Upsite Technologies blog
Year
2025
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only — the publisher’s terms apply to the original document

Citation

Ian Seaton (2025). The Importance of Mutual Understanding Between IT and Facilities - Part 2: Specifying A1, A2, A3, or A4 Servers. Upsite Technologies blog. https://www.upsite.com/blog/the-importance-of-mutual-understanding-between-it-and-facilities-part-2-specifying-a1-a2-a3-or-a4-servers/

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.