Technical guideFree to read2026

Liquid cooling in African data centres: A turning point in efficiency, resilience and future-ready design

WSP · Leon Kleyn, Floris van der Walt

WSP mechanical engineers' practical lessons from introducing liquid cooling in African data centres for GPU-based AI loads.

On this page

Overview

This article by Leon Kleyn and Floris van der Walt of WSP shares practical lessons from introducing liquid cooling in African data centres for GPU-based AI loads. The authors state that liquid has roughly three to four times the cooling capacity of air. The article recommends air cooling where it still works and liquid cooling where GPU loads require it, and says hot climates do not restrict liquid cooling.

Several concrete design and operations topics stand out. Cold-plate loops use demineralised water, since potable-water minerals can block microchannels, and a propylene glycol mix inhibits scaling and biofilm. The closed loop is filled once at commissioning and should use no make-up water; measurable consumption indicates a leak. The article also covers leak detection and the need for specialist operations training.

Supply chain is another risk it highlights: CDUs are not manufactured in Africa, so global lead times are a project risk and procurement queues can affect the schedule. Among design lessons, industrial-type buildings with generous volume and structural flexibility are said to suit liquid-cooled retrofits if site power is sufficient. As a limit, the article is a consultancy opinion piece; it gives no measurement data or calculation method and its conclusions rest on the authors' experience.

Key points

  1. Liquid has roughly three to four times the cooling capacity of air (as stated by the authors).
  2. Cold-plate loops use demineralised water, since potable-water minerals can block microchannels; a propylene glycol mix inhibits scaling and biofilm.
  3. The closed loop is filled once at commissioning and should use no make-up water; measurable consumption indicates a leak.
  4. CDUs are not manufactured in Africa, so global lead times are a project risk.
  5. Industrial-type buildings with generous volume and structural flexibility suit liquid-cooled retrofits if site power is sufficient.
  6. The article recommends air cooling where it works and liquid cooling where GPU loads require it.

Using it in design

  • For TCS loops, add coolant fields (demineralised water, PG percentage).
  • Treat any make-up water on a closed loop as a leak alarm in the monitoring design.
  • Flag long-lead items such as CDUs in the procurement and BOM output.
  • In retrofit projects, check building volume, structural flexibility and site power early.

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Check cooling capacity alongside your design

Review zone heat loads, available capacity and the capacity balance after the largest unit is lost in SoSo CAD.

Request a demo
Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Who should read it

Data centre designers moving to liquid cooling, project managers and decision makers managing procurement risk in emerging markets.

Related standards

  • ASHRAE TC 9.9 Liquid Cooling Guidelines

Publication details

Authors
Leon Kleyn; Floris van der Walt
Publisher
WSP
Year
2026
Document language
English
Source type
Expert / community
Access
Free to read
Licence
Copyright retained; citation only — the publisher’s terms apply to the original document

Citation

Leon Kleyn; Floris van der Walt (2026). Liquid cooling in African data centres: A turning point in efficiency, resilience and future-ready design. WSP. https://www.wsp.com/en-za/insights/liquid-cooling-in-african-data-centres

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.