Proper Flow Across Cold Plates with the Belimo Energy Valve
Belimo
A two-page Belimo application leaflet on keeping cold-plate flow stable during server maintenance in liquid-cooled racks through differential-pressure control, maximum-flow limitation and monitoring.
On this page
Overview
The leaflet describes use of the Belimo Energy Valve on liquid-cooled racks with cold plates. Maintaining rack differential pressure is proposed to preserve cold-plate flow during server maintenance, so that removing one server does not disturb flow to the remaining servers.
Maximum-flow limitation is presented as protection against excess flow and against erosion of cold-plate channels. The leaflet also covers monitoring of flow and related data through the valve.
Key points
- The leaflet covers differential-pressure control for liquid-cooled racks with cold plates.
- Rack differential pressure is held constant to preserve cold-plate flow during server maintenance.
- Maximum-flow limitation is presented as protection against excess flow and cold-plate channel erosion.
- The valve also provides flow monitoring.
Using it in design
- Consider differential-pressure control at the rack inlet so removing one server for maintenance does not affect flow to other cold plates.
- Carry the maximum flow permitted by the cold plate maker into the valve limit and add erosion risk to design criteria.
- Connect flow and pressure difference data to the monitoring system to track rack-level flow deviations.
Who should read it
Mechanical and automation engineers designing hydraulics and control of liquid-cooled racks.
Publication details
- Authors
- Belimo
- Publisher
- Belimo
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Publisher landing page opened: https://www.belimo.com/belimo-master/en_GB/products-ap/solutions/data-centers . It links this application note but provides no open reuse licence. PDF returned HTTP 200 application/pdf via requests after browser tools failed. Metadata and original summary only; publication date not stated.
Citation
Belimo Proper Flow Across Cold Plates with the Belimo Energy Valve. Belimo. https://www.belimo.com/mam/asia-pacific/marketing_communication/leaflets/flyer_ev-cold-plate_en-AP.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.