ModulA RED, ModulA-D RED, ModulA BLUE T2 M/L: Installation and Operating Instructions

Original title ModulA RED, ModulA-D RED, ModulA BLUE T2 M/L: Montaj ve Kullanım Kılavuzu

Biral AG

Biral's manual for ModulA circulation pumps with integrated frequency converter: RED for heating, BLUE for domestic hot water; fluid temperature +15 to +110 °C (BLUE +85 °C), glycol viscosity up to 50 mm²/s.

On this page

Overview

The manual covers installation, commissioning and operation of Biral ModulA circulation pumps with an integrated frequency converter; the English section starts on page 6 and the Turkish on page 36. Flow performance adjusts automatically or under control to the system's actual need, which reduces energy consumption in many systems and lowers flow noise. ModulA RED is for heating systems and ModulA BLUE for domestic drinking-water systems; both can also be used in geothermal heat pumps and thermal solar systems.

Fluid requirements: the pumps are for clean, thin, non-explosive, non-aggressive fluids free of solids and long fibres; heating water must meet current standards such as VDI 2035. In water-glycol mixtures the maximum permitted viscosity is 50 mm²/s (cSt), roughly 50% glycol at -10 °C, and the system must be cleaned and flushed before glycol is added. Permitted domestic hot water hardness is 35 °fH below 65 °C and 25 °fH below 85 °C; 25 °fH and below 65 °C is recommended to prevent scale. Flammable liquids and aggressive liquids such as acids or seawater are excluded.

Operating conditions: fluid temperature +15 to +110 °C for RED and +15 to +85 °C for BLUE (domestic hot water maximum 65 °C recommended); ambient 0 to 40 °C; maximum operating pressure of 6, 10 or 16 bar is on the nameplate. The minimum inlet pressure at 500 m altitude depends on fluid temperature and model, for example 0.1 to 0.7 bar at 75 °C and 1.0 to 1.7 bar at 110 °C; add ±0.01 bar per ±100 m and 0.1 bar for twin pumps. The rotor shaft must always be horizontal.

Before commissioning, the system must be filled and vented and sufficient inlet pressure available; the system cannot be vented through the pumps, which self-vent. The manual also covers control types (constant pressure, proportional pressure, constant speed), dry-run detection, Bluetooth and the Biral ONE app, a fault checklist and technical data.

Key points

  1. ModulA RED is for heating, ModulA BLUE for domestic drinking-water systems; also geothermal heat pumps and thermal solar systems.
  2. Fluid temperature +15 to +110 °C for RED, +15 to +85 °C for BLUE (domestic hot water maximum 65 °C); ambient 0 to 40 °C.
  3. Maximum operating pressure is 6, 10 or 16 bar on the nameplate.
  4. Water-glycol maximum viscosity 50 mm²/s (about 50% glycol at -10 °C); flush the system before adding glycol.
  5. Domestic hot water hardness maximum 35 °fH (below 65 °C) and 25 °fH (below 85 °C); recommended 25 °fH and below 65 °C.
  6. Minimum inlet pressure at 500 m: 0.1 to 0.7 bar at 75 °C, 0.35 to 1.2 bar at 95 °C, 1.0 to 1.7 bar at 110 °C; ±0.01 bar per ±100 m, +0.1 bar for twin pumps.
  7. The rotor shaft mounting position must always be horizontal.
  8. Before commissioning the system must be filled and vented; it cannot be vented through the pump.
  9. Control types are constant pressure, proportional pressure and constant speed.

Using it in design

  • When selecting a pump, verify fluid temperature, maximum operating pressure class (6, 10 or 16 bar) and ambient limits against the manual values.
  • In water-glycol loops keep viscosity within the 50 mm²/s limit and account for the head reduction caused by glycol density and viscosity.
  • Provide the minimum inlet pressure at the suction side for the fluid temperature and model, with altitude and twin-pump corrections.
  • Place the pump with the rotor shaft horizontal and include filling and venting in the commissioning procedure.
  • If a check valve is fitted, choose a control setting that keeps pump discharge pressure above the valve closing pressure.

Who should read it

Mechanical engineers and technicians selecting, installing and commissioning pumps for heating and circulation circuits.

Document contents

  1. Safety Information
  2. Symbols Used
  3. General Information: Intended Use, Fluid Requirements, Operating Conditions, Check Valve, Frost Protection, Thermal Insulation, Flow Direction
  4. Installation
  5. Electrical Connection
  6. Commissioning
  7. Settings
  8. Fault Overview and Checklist
  9. Sensor
  10. Accessories and Variants
  11. Technical Data
  12. End of Life and Warranty
  13. Parts List

Publication details

Authors
Biral AG
Publisher
Biral AG
Year
2022
Document number
2022-01_7800000042_01_M_EN_TR
Document language
Turkish
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Public source opened on the access date. No open redistribution licence established; metadata and original short summaries only. The declaration identifies Biral AG as manufacturer; Masdaf is the official host/distributor here, not the document author. The date is printed on p.68.

Citation

Biral AG (2022). ModulA RED, ModulA-D RED, ModulA BLUE T2 M/L: Montaj ve Kullanım Kılavuzu. Biral AG. 2022-01_7800000042_01_M_EN_TR. https://cms.masdaf.com/Files/tr/ModulA-D/Flan%C5%9Fl%C4%B1%20Tip%20Islak%20Rotorlu%20Pompa%20KBK.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.