Technical guideFree to read2025

Canatec Fan Wall Array 2025 B

Original title Fan Wall Array 2025 B

Canatec

Canatec's Fan Wall Array is a modular fan wall integrated into equipment corridors; six models give 65-289 kW total capacity at 18/26 °C water with 100 Pa external static pressure.

On this page

Overview

The Fan Wall Array is a modular fan wall for high-density data centres, integrated into equipment corridors and separating hot and cold airflow. The brochure highlights reduced equipment footprint and more white space, lower PUE and operating cost, rear-access EC fans and uniform horizontal airflow that reduces hotspots. A stacked arrangement saves floor space.

Six models (070S, 150S, 230S and 100D, 230D, 300D) are given at two conditions. At 36 °C return air, 24 °C supply air and 18/26 °C water, total capacity is 65-220 kW (S models) and 92-289 kW (D models). At 40 °C return, 28 °C supply and 20/30 °C water, capacity rises to 68-225 kW and 100-325 kW. SHR is 1.00 throughout and total and sensible capacity are printed equal.

Airflow is 16,000-79,200 m³/h, power input 2.3-11.6 kW and water-side pressure drop below 85 kPa. Physical data: width 1,000, 2,000 or 3,000 mm, depth 800 mm, height 5,000 mm (S) or 5,600 mm (D), weight 1,500-3,400 kg and water connections DN50-DN80. External static pressure is 100 Pa. The equal total and sensible values are not labelled as net capacity.

Key points

  1. Six models: 070S, 150S, 230S and 100D, 230D, 300D.
  2. Condition 1: return 36 °C, supply 24 °C, water 18/26 °C; capacity 65, 145, 220 kW (S) and 92, 214, 289 kW (D).
  3. Condition 2: return 40 °C, supply 28 °C, water 20/30 °C; capacity 68, 145, 225 kW (S) and 100, 224, 325 kW (D).
  4. SHR is 1.00 on all rows; total and sensible capacity are equal.
  5. Airflow 16,000-79,200 m³/h; power input 2.3-11.6 kW; external static pressure 100 Pa.
  6. Water-side pressure drop below 85 kPa.
  7. Width 1,000-3,000 mm, depth 800 mm, height 5,000 or 5,600 mm; weight 1,500-3,400 kg.
  8. Standard accessories are a G4 filter, dirty-filter switch, water leak sensor and service light.

Using it in design

  • Design the fan wall in the equipment corridor with 5,000-5,600 mm height and 800 mm depth; check floor-to-floor height and the junction with containment.
  • Read capacity from whichever condition is closer to the project's supply and water temperatures; the warmer-water condition gives higher capacity.
  • Since there is no net capacity label, confirm net values and the scope of fan power with the manufacturer.
  • Add the water-side pressure drop (below 85 kPa) to pump selection.
  • Plan the maintenance aisle width for the rear-access EC fans.

Who should read it

Mechanical engineers designing cooling infrastructure for high-density data centres.

Document contents

  1. Features and benefits
  2. Configurations
  3. Specifications

Publication details

Authors
Canatec
Publisher
Canatec
Year
2025
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Canatec (2025). Fan Wall Array 2025 B. Canatec. https://www.canatec.com.sg/wp-content/uploads/2025/11/CANATEC-FAN-WALL-ARRAY-2025-B_compressed.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.