Canatec Fan Wall Array 2025 B
Original title Fan Wall Array 2025 B
Canatec
Canatec's Fan Wall Array is a modular fan wall integrated into equipment corridors; six models give 65-289 kW total capacity at 18/26 °C water with 100 Pa external static pressure.
On this page
Overview
The Fan Wall Array is a modular fan wall for high-density data centres, integrated into equipment corridors and separating hot and cold airflow. The brochure highlights reduced equipment footprint and more white space, lower PUE and operating cost, rear-access EC fans and uniform horizontal airflow that reduces hotspots. A stacked arrangement saves floor space.
Six models (070S, 150S, 230S and 100D, 230D, 300D) are given at two conditions. At 36 °C return air, 24 °C supply air and 18/26 °C water, total capacity is 65-220 kW (S models) and 92-289 kW (D models). At 40 °C return, 28 °C supply and 20/30 °C water, capacity rises to 68-225 kW and 100-325 kW. SHR is 1.00 throughout and total and sensible capacity are printed equal.
Airflow is 16,000-79,200 m³/h, power input 2.3-11.6 kW and water-side pressure drop below 85 kPa. Physical data: width 1,000, 2,000 or 3,000 mm, depth 800 mm, height 5,000 mm (S) or 5,600 mm (D), weight 1,500-3,400 kg and water connections DN50-DN80. External static pressure is 100 Pa. The equal total and sensible values are not labelled as net capacity.
Key points
- Six models: 070S, 150S, 230S and 100D, 230D, 300D.
- Condition 1: return 36 °C, supply 24 °C, water 18/26 °C; capacity 65, 145, 220 kW (S) and 92, 214, 289 kW (D).
- Condition 2: return 40 °C, supply 28 °C, water 20/30 °C; capacity 68, 145, 225 kW (S) and 100, 224, 325 kW (D).
- SHR is 1.00 on all rows; total and sensible capacity are equal.
- Airflow 16,000-79,200 m³/h; power input 2.3-11.6 kW; external static pressure 100 Pa.
- Water-side pressure drop below 85 kPa.
- Width 1,000-3,000 mm, depth 800 mm, height 5,000 or 5,600 mm; weight 1,500-3,400 kg.
- Standard accessories are a G4 filter, dirty-filter switch, water leak sensor and service light.
Using it in design
- Design the fan wall in the equipment corridor with 5,000-5,600 mm height and 800 mm depth; check floor-to-floor height and the junction with containment.
- Read capacity from whichever condition is closer to the project's supply and water temperatures; the warmer-water condition gives higher capacity.
- Since there is no net capacity label, confirm net values and the scope of fan power with the manufacturer.
- Add the water-side pressure drop (below 85 kPa) to pump selection.
- Plan the maintenance aisle width for the rear-access EC fans.
Who should read it
Mechanical engineers designing cooling infrastructure for high-density data centres.
Document contents
- Features and benefits
- Configurations
- Specifications
Publication details
- Authors
- Canatec
- Publisher
- Canatec
- Year
- 2025
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Canatec (2025). Fan Wall Array 2025 B. Canatec. https://www.canatec.com.sg/wp-content/uploads/2025/11/CANATEC-FAN-WALL-ARRAY-2025-B_compressed.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.