Fan Wall Unit FWU-2026-A: Built for Hyperscale
Original title Fan Wall Unit: CANATEC FWU 2026 (A)
Canatec
Canatec's two-page sheet gives a four-model fan wall range from 120 to 470 kW, rated at 36 °C return air and 18/26 °C chilled water, with EC fan energy as low as 0.16 W/CMH.
On this page
Overview
The document is Canatec's 2026 product sheet for a fan wall unit (FWU) aimed at hyperscale and high-density data halls. The manufacturer claims PUE of 1.25 to 1.28 through optimized design and up to 800 kW of cooling per unit; the models in the data table are 120, 240, 380 and 470 kW.
Features include EC fans with consumption as low as 0.16 W/CMH, smart valves that respond to fluctuating heat loads, an active harmonic filter keeping THDi below 5% at full load, dual power source with UPS-backed controller, integrated water leak detection and a fail-safe air damper preventing backward airflow and cool air short-circuiting. High-volume horizontal airflow reduces hotspots and supports hot and cold aisle containment.
The design is compact and modular: it reduces the need for raised floor, can be stacked vertically without side clearance, and rear door access to the EC fans simplifies maintenance. Standard accessories are a G4 filter, filter-dirty pressure switch, water leak sensor, service light and air damper; the active harmonic filter, ATS, battery backup, EPIV/energy valve, power meter, smoke detector and remote air sensor are optional.
The data table gives two rating conditions: return air 36 °C, supply air 24 °C with chilled water 18/26 °C, and return air 40 °C, supply air 28 °C with chilled water 20/30 °C. All capacity is sensible (SHR 1.00). The document is a manufacturer sheet, and the PUE figure is a manufacturer claim rather than a system measurement.
Key points
- Models FW120, FW240, FW380 and FW470; 120, 240, 380 and 470 kW at 18/26 °C water (RAT 36 °C, SAT 24 °C).
- At 20/30 °C water (RAT 40 °C, SAT 28 °C) capacity is 125, 255, 365 and 525 kW.
- Air volume 30,000, 60,000, 90,000 and 116,240 CMH (largest model 124,000 CMH at 40/28).
- Power input at 18/26 °C is 6.6, 11.3, 20.0 and 23.4 kW; water pressure drop below 85 kPa on all models.
- SHR 1.00; all capacity is sensible.
- EC fan energy as low as 0.16 W/CMH; fan quantity 2, 4, 6 and 8.
- Active harmonic filter keeps THDi below 5% at full load (optional accessory).
- Manufacturer claims PUE 1.25-1.28 and up to 800 kW per unit.
- External static pressure 75 Pa; supply 380-415 V 3P+1N 50/60 Hz.
Using it in design
- Compare capacity at both rating conditions (36/24 °C air with 18/26 °C water, and 40/28 °C air with 20/30 °C water) against your own design temperatures.
- Add unit weight (700 to 2,500 kg) and footprint (2,500 to 4,600 mm wide, 1,600 mm deep) to structural and layout checks.
- Verify hot aisle containment and fail-safe damper behaviour for high return air designs.
- State options such as UPS-backed controller, ATS and active harmonic filter explicitly in the specification.
- Recalculate the manufacturer PUE claim with your own climate and load profile.
Who should read it
Mechanical designers selecting fan wall CRAH units for hyperscale and high-density data halls.
Document contents
- Built for hyperscale
- Technology to maximize efficiency
- Protection for mission-critical infrastructure
- Practical design considerations
- High volume horizontal airflow
- Specifications
Publication details
- Authors
- Canatec
- Publisher
- Canatec
- Year
- 2026
- Document number
- FWU 2026 (A)
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Canatec (2026). Fan Wall Unit: CANATEC FWU 2026 (A). Canatec. FWU 2026 (A). https://canatec.com.sg/wp-content/uploads/2026/09/CANATEC-FWU-2026-A_compressed.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.