Canatec Smart In-Row (Air-Cooled DX) 2025 (A)
Original title CANATEC Smart In-Row Air-Cooled 2025 (A), PDF p.2
Canatec
The Canatec Smart In-Row air-cooled DX series gives 23.5-61.4 kW across 4 models at 36 °C return air; the same models fall to 17.7-50.4 kW at 30 °C return air in a separate table.
On this page
Overview
Smart In-Row is a compact floor-standing precision cooling unit placed between server racks, offered as a space-efficient alternative to larger CRAC equipment. The brochure states a 20-60 kW range and recommends it for high-density and high-compute racks. Listed features are an electronic expansion valve, cold/hot aisle compatibility, upthrow configuration and a controller with Modbus RTU.
The table gives four models (SRA025V, 035V, 045V, 060V) at two return-air conditions with 40 °C condenser temperature. At 36 °C return air, total and sensible capacity are equal at 23.5, 38.5, 41.2 and 61.4 kW, power input is 8.0-25.3 kW and EER 2.9 down to 2.4. At 30 °C return air, capacity is 17.7, 31.5, 34.2 and 50.4 kW and EER 2.1-2.7. SHR is 1.00 throughout.
Refrigerant is R410A with one hermetic scroll compressor; condensing units measure 1,495-2,395 mm wide and weigh 135-234 kg. The indoor unit is 2,200 mm high, 1,200 mm deep, 300 or 600 mm wide and weighs 300-420 kg. External static pressure is 5 Pa. Because capacity and power are published separately at the two return-air conditions, models must be compared at the same condition.
Key points
- Models SRA025V, 035V, 045V, 060V; 20-60 kW class.
- 36 °C return air, 40 °C condenser: 23.5, 38.5, 41.2, 61.4 kW (SHR 1.00).
- 30 °C return air, 40 °C condenser: 17.7, 31.5, 34.2, 50.4 kW.
- EER at 36 °C is 2.9, 2.8, 2.7, 2.4; at 30 °C 2.1, 2.8, 2.7, 2.7.
- Power input 8.0-25.3 kW at 36 °C and 8.3-18.4 kW at 30 °C.
- Airflow 3,600-10,965 m³/h; R410A; one scroll compressor.
- Indoor unit 300 or 600 mm wide, 1,200 mm deep, 2,200 mm high.
- EC plug fans, 2-6 per unit; Modbus RTU interface.
Using it in design
- Compare models at the same return-air condition; do not mix the 36 °C and 30 °C tables.
- Read EER at the 40 °C condenser condition and ask the manufacturer for a correction at the site's summer ambient.
- For in-row placement plan the 300 or 600 mm width and the condensing unit location with refrigerant pipe lengths.
- In dense environments without raised floor, consider the upthrow configuration.
- Include the Modbus RTU points in the BMS design.
Who should read it
Mechanical designers and specification engineers selecting precision cooling units for data halls and server rooms.
Document contents
- Features and benefits
- Specifications
Publication details
- Authors
- Canatec
- Publisher
- Canatec
- Year
- 2025
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Canatec (2025). CANATEC Smart In-Row Air-Cooled 2025 (A), PDF p.2. Canatec. https://canatec.com.sg/wp-content/uploads/2025/11/CANATEC-SMART-IN-ROW-Air-Cooled-2025-A_compressed_r.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.