Canatec Smart In-Row (Chilled Water) 2025 (A)
Original title CANATEC Smart In-Row Chilled Water 2025 (A), PDF p.2
Canatec
The Canatec Smart In-Row chilled-water series gives 9.5-41.6 kW (18/26 °C water) and 16.6-58.9 kW (8/15 °C water) across 3 models; the SHR fields at the second condition conflict with total capacity.
On this page
Overview
Smart In-Row (Chilled Water) is a compact precision cooling unit placed between racks. The brochure states a 20-60 kW range and recommends it for high-density and production racks. It has a 2-way modulating valve, Co-Work main board linkage, upthrow configuration and a Modbus RTU interface.
The table gives three models (SRC035, 050, 075) at two conditions. At 36 °C return air and 18/26 °C water, total and sensible capacity are 9.5, 29.6 and 41.6 kW (SHR 1.00). At 30 °C return air and 8/15 °C water, capacity is 16.6, 41.5 and 58.9 kW, airflow 4,500, 9,000 and 13,000 m³/h and power input 1.2, 1.9 and 2.9 kW.
At the second condition, SRC050 and SRC075 show SHR of 0.90 and 0.91 while sensible capacity is printed equal to total capacity. These two fields conflict, so when using this table for net sensible capacity it needs confirmation from the manufacturer together with SHR. Water flow is 0.33-2.12 L/s, water connections DN32-DN40, unit width 300 or 600 mm, height 2,200 mm and weight 155-320 kg.
Key points
- Three models: SRC035, 050, 075 (20-60 kW class).
- 36 °C return air, 18/26 °C water: 9.5, 29.6, 41.6 kW (SHR 1.00).
- 30 °C return air, 8/15 °C water: 16.6, 41.5, 58.9 kW.
- At the second condition SRC050/075 print SHR 0.90/0.91 together with sensible equal to total capacity.
- Airflow 4,500-13,000 m³/h; power input 1.2-2.9 kW.
- Water flow is 0.33-1.33 L/s in the first condition and 0.62-2.12 L/s in the second.
- Width 300 or 600 mm, height 2,200 mm, weight 155-320 kg.
- External static pressure 5 Pa; EC plug fans, 2-6 per unit.
Using it in design
- Because the SHR and sensible fields conflict at the second condition, do not carry sensible capacity into a specification without written confirmation from the manufacturer.
- Match chilled water temperature (18/26 °C or 8/15 °C) to the plant design; higher water temperature lowers capacity markedly.
- For SRC035 check the 300 mm width and 6 fans in the row layout.
- Include water connection size (DN32-DN40) and flow in pump selection.
- Define Modbus RTU points in the BMS design.
Who should read it
Mechanical designers and specification engineers selecting precision cooling units for data halls and server rooms.
Document contents
- Features and benefits
- Specifications
Publication details
- Authors
- Canatec
- Publisher
- Canatec
- Year
- 2025
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Canatec (2025). CANATEC Smart In-Row Chilled Water 2025 (A), PDF p.2. Canatec. https://canatec.com.sg/wp-content/uploads/2025/11/CANATEC-SMART-IN-ROW-Chilled-Water-2025-A_compressed_r.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.