Comino Grando Server and Rackable Workstation, Datasheet Version 2.3

Original title Comino Grando Server & Rackable Workstation Datasheet v2.3

Comino

Comino's Grando liquid-cooled 4U server datasheet: up to 8 GPUs, 6.5 kW cooling capacity, 8.0 kW power from 4 x 2000 W CRPS, and maximum performance at 20 °C intake air.

On this page

Overview

The document is version 2.3 of Comino's datasheet for the Grando server and rackable workstation. The unit is a 4U, rack-mountable or desktop system with up to 8 GPUs and 2 CPUs, with liquid cooling on the GPUs, CPUs and VRMs. Target uses are AI research, content creation, rendering and password recovery. The vendor states that thermal throttling is fully avoided and that the unit can run 24/7 at up to 38 °C.

For power, up to 4 hot-swap CRPS modules are used: 4 x 2000 W at 180-264 V (8.0 kW capacity) or 4 x 1000 W at 90-140 V (4 kW); redundancy modes are 4+0, 3+1 and 2+2. Cooling capacity is 6.5 kW, and the maximum is ensured at 20 °C intake air in the cooling system's performance mode. Airflow is front to back, with the motherboard in the front of the chassis.

The performance chart relates total device power (for example 1 CPU + 8 x 600 W GPU) to airflow rate (100-1000 m3/h) and ambient temperature (20-35 °C); noise ranges from 39 dB to 70 dB. The configuration examples show which class suits which ambient temperature for a given GPU TDP and count: an 8-GPU server is high noise and for 15-20 °C ambient, for example. The datasheet contains vendor estimates and asks readers to contact the vendor for clarification.

Mechanically, size is 439 x 681 x 177 mm, and weight is 49 kg net (67 kg gross) with 4 GPUs and 52 kg net (70 kg gross) with 6 GPUs. Quick disconnect couplings (TheQ) on each GPU and CPU simplify maintenance, and the vendor states a service interval of up to 3 years.

Key points

  1. Up to 8 GPUs and 2 CPUs, 4U, 19-inch rack or desktop.
  2. Cooling capacity 6.5 kW; maximum at 20 °C intake air and performance mode.
  3. 4 x 2000 W CRPS: 8.0 kW at 180-264 V, 4 kW at 90-140 V (4 x 1000 W); modes 4+0, 3+1, 2+2.
  4. Size 439 x 681 x 177 mm; 49 kg net (67 kg gross) with 4 GPUs, 52 kg net (70 kg gross) with 6 GPUs.
  5. Liquid cooling on GPU, CPU and VRM; custom 450 ml Comino reservoir with integrated pumps.
  6. Fans are 3 x 6200 RPM (high noise) or 3 x 3000 RPM (low noise); noise level 39-70 dB.
  7. The vendor states 24/7 operation up to 38 °C (100 °F) ambient; by configuration an 8-GPU server falls in the 15-20 °C ambient class.
  8. Supported GPUs include NVIDIA A100, H100, H200, L40S and RTX PRO 6000; RAM up to 2 TB.

Using it in design

  • In the rack power budget compute usable power by redundancy mode: in 3+1 mode at most 6 kW from 4 x 2000 W modules and the 180-264 V condition applies; capacity halves at 90-140 V.
  • In cooling planning remember the unit rejects heat from liquid to room air; compute the airflow and room temperature (20 °C for maximum performance) needed to reject 6.5 kW from a single 4U.
  • Compare the noise class (39-70 dB) with the work area; consider a separate room or acoustic measures for high-noise configurations.
  • Check rack load against 49-52 kg net weight and depth against 681 mm.
  • Set the upper ambient temperature limit by the class in the configuration example (15-20, 25-30 or 35-40 °C).

Who should read it

IT and data-centre engineers deploying rack-mounted multi-GPU systems in small-scale rooms.

Document contents

  1. Key Advantages
  2. Features
  3. System Overview
  4. Cooling System
  5. Performance Chart
  6. Configuration Examples
  7. Technical Specifications

Publication details

Authors
Comino
Publisher
Comino
Year
Year not stated
Document number
v2.3
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Comino Comino Grando Server & Rackable Workstation Datasheet v2.3. Comino. v2.3. https://faq.comino.com/datasheets/datasheet_comino_grando_server.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.