7520 Series Installation Guide: Revision AJ

Extreme Networks

Extreme Networks' 7520 Series guide gives separate idle and full-traffic power for three switch models: 48Y-8C 95.75-383.15 W, 48YE-8CE 174.84-480.20 W and 48XT-6C 119.42-398.30 W.

On this page

Overview

The guide covers installation, cabling, monitoring and technical specifications of the Extreme 7520-48Y-8C, 7520-48YE-8CE and 7520-48XT-6C data-centre switches. The 48Y-8C has 48 1/10/25 GbE SFP28 and 8 40/100 GbE QSFP28 ports, the 48YE-8CE has 48 10/25 GbE SFP28 and 8 QSFP28, and the 48XT-6C has 48 1/10 GbE 10GBaseT and 6 40/100 GbE QSFP28 ports. They use modular 800 W AC or DC power supplies (up to two) and six fan modules, with front-to-back or back-to-front airflow options.

The technical specification table gives mechanical and environmental values: 44.0 cm wide and 4.3 cm (1U) high; empty chassis weight is 7.58 kg for the 48Y-8C, 9.23 kg for the 48YE-8CE and 7.41 kg for the 48XT-6C (10.11, 11.90 and 9.47 kg with power supplies). Operating temperature is 0-50 °C at sea level with front-to-back airflow and 0-45 °C back-to-front, and 0-40 °C up to 3000 m. The 48YE-8CE does not support stacking.

The power consumption and heat dissipation table gives idle (no ports linked) and full-load conditions in separate columns. Minimum idle power is 95.75 W (326.71 BTU/hr) for the 48Y-8C, 174.84 W (596.58) for the 48YE-8CE and 119.42 W (407.48) for the 48XT-6C; with fans high and all ports at 100% traffic, maximum power is 383.15 W (1307.36 BTU/hr), 480.20 W (1638.51) and 398.30 W (1359.06) respectively. Acoustic noise ranges from 36.4 to 60.2 dB(A). The document is an installation and hardware guide. For the 48YE-8CE depth, the centimetre and inch values do not match (21.69 in against 53.95 cm), so exact geometry needs manufacturer confirmation.

Key points

  1. Idle (no ports linked) power: 48Y-8C 95.75 W, 48YE-8CE 174.84 W, 48XT-6C 119.42 W.
  2. Maximum power (fans high, all ports at 100% traffic): 48Y-8C 383.15 W, 48YE-8CE 480.20 W, 48XT-6C 398.30 W.
  3. Maximum heat dissipation is 1307.36 (48Y-8C), 1638.51 (48YE-8CE) and 1359.06 BTU/hr (48XT-6C).
  4. Modular 800 W AC (100-140 V and 200-240 V) or DC (-48 to -60 VDC) supplies, up to two; six fan modules; front-to-back or back-to-front airflow.
  5. Operating: 0-50 °C (front-to-back, sea level), 0-45 °C (back-to-front), 0-40 °C up to 3000 m; these ranges apply with one fan failed.
  6. Empty chassis weight: 48Y-8C 7.58 kg, 48YE-8CE 9.23 kg, 48XT-6C 7.41 kg.
  7. The 48YE-8CE does not support stacking; the other models have two stacking ports.
  8. Switching capacity is 4 Tbps for the 48Y-8C and 48YE-8CE and 2.16 Tbps for the 48XT-6C; typical latency is 800 ns and 2,400 ns.
  9. Acoustics with front-to-back airflow: 48YE-8CE 60.2 dB(A) (7.3 bels), 48Y-8C 52.2 dB(A) (6.8 bels), 48XT-6C 36.4 dB(A) (5.5 bels).
  10. The 48YE-8CE depth centimetre and inch values do not match; exact geometry needs manufacturer confirmation.

Using it in design

  • Keep idle and maximum power rows separate for each model in the rack power budget; use the maximums (383.15, 480.20, 398.30 W) for load balancing.
  • Add maximum heat dissipation in BTU/hr to the cooling calculation and choose airflow direction (front-to-back or back-to-front) to match the cold aisle layout.
  • For the 48YE-8CE, do not fix rack depth and cable bend allowance until the depth is confirmed with the vendor.
  • Select power supply type (AC 100-240 V or DC -48 VDC) to match site distribution and connect the two PSUs to separate feeds.
  • Compare ambient temperature with the 50 °C front-to-back, 45 °C back-to-front and 40 °C high-altitude limits.

Who should read it

Network and facility engineers planning rack, power and cooling for data-centre switches.

Document contents

  1. Extreme 7520 overview (7520-48Y-8C, 48YE-8CE and 48XT-6C features)
  2. Fan modules and power supplies
  3. Build stacks
  4. Site preparation (operating environment, rack, cable and power requirements)
  5. Technical specifications (interfaces, acoustic noise, MTBF, power specifications, environmental, standards)
  6. Power consumption and heat dissipation

Publication details

Authors
Extreme Networks
Publisher
Extreme Networks
Year
2026
Document number
9037389-00 Rev AJ
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Extreme Networks (2026). 7520 Series Installation Guide: Revision AJ. Extreme Networks. 9037389-00 Rev AJ. https://documentation.extremenetworks.com/7520%20Series%20Installation%20Guide/downloads/7520_Series_Installation_Guide.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.