7520 Series Installation Guide: Revision AJ
Extreme Networks
Extreme Networks' 7520 Series guide gives separate idle and full-traffic power for three switch models: 48Y-8C 95.75-383.15 W, 48YE-8CE 174.84-480.20 W and 48XT-6C 119.42-398.30 W.
On this page
Overview
The guide covers installation, cabling, monitoring and technical specifications of the Extreme 7520-48Y-8C, 7520-48YE-8CE and 7520-48XT-6C data-centre switches. The 48Y-8C has 48 1/10/25 GbE SFP28 and 8 40/100 GbE QSFP28 ports, the 48YE-8CE has 48 10/25 GbE SFP28 and 8 QSFP28, and the 48XT-6C has 48 1/10 GbE 10GBaseT and 6 40/100 GbE QSFP28 ports. They use modular 800 W AC or DC power supplies (up to two) and six fan modules, with front-to-back or back-to-front airflow options.
The technical specification table gives mechanical and environmental values: 44.0 cm wide and 4.3 cm (1U) high; empty chassis weight is 7.58 kg for the 48Y-8C, 9.23 kg for the 48YE-8CE and 7.41 kg for the 48XT-6C (10.11, 11.90 and 9.47 kg with power supplies). Operating temperature is 0-50 °C at sea level with front-to-back airflow and 0-45 °C back-to-front, and 0-40 °C up to 3000 m. The 48YE-8CE does not support stacking.
The power consumption and heat dissipation table gives idle (no ports linked) and full-load conditions in separate columns. Minimum idle power is 95.75 W (326.71 BTU/hr) for the 48Y-8C, 174.84 W (596.58) for the 48YE-8CE and 119.42 W (407.48) for the 48XT-6C; with fans high and all ports at 100% traffic, maximum power is 383.15 W (1307.36 BTU/hr), 480.20 W (1638.51) and 398.30 W (1359.06) respectively. Acoustic noise ranges from 36.4 to 60.2 dB(A). The document is an installation and hardware guide. For the 48YE-8CE depth, the centimetre and inch values do not match (21.69 in against 53.95 cm), so exact geometry needs manufacturer confirmation.
Key points
- Idle (no ports linked) power: 48Y-8C 95.75 W, 48YE-8CE 174.84 W, 48XT-6C 119.42 W.
- Maximum power (fans high, all ports at 100% traffic): 48Y-8C 383.15 W, 48YE-8CE 480.20 W, 48XT-6C 398.30 W.
- Maximum heat dissipation is 1307.36 (48Y-8C), 1638.51 (48YE-8CE) and 1359.06 BTU/hr (48XT-6C).
- Modular 800 W AC (100-140 V and 200-240 V) or DC (-48 to -60 VDC) supplies, up to two; six fan modules; front-to-back or back-to-front airflow.
- Operating: 0-50 °C (front-to-back, sea level), 0-45 °C (back-to-front), 0-40 °C up to 3000 m; these ranges apply with one fan failed.
- Empty chassis weight: 48Y-8C 7.58 kg, 48YE-8CE 9.23 kg, 48XT-6C 7.41 kg.
- The 48YE-8CE does not support stacking; the other models have two stacking ports.
- Switching capacity is 4 Tbps for the 48Y-8C and 48YE-8CE and 2.16 Tbps for the 48XT-6C; typical latency is 800 ns and 2,400 ns.
- Acoustics with front-to-back airflow: 48YE-8CE 60.2 dB(A) (7.3 bels), 48Y-8C 52.2 dB(A) (6.8 bels), 48XT-6C 36.4 dB(A) (5.5 bels).
- The 48YE-8CE depth centimetre and inch values do not match; exact geometry needs manufacturer confirmation.
Using it in design
- Keep idle and maximum power rows separate for each model in the rack power budget; use the maximums (383.15, 480.20, 398.30 W) for load balancing.
- Add maximum heat dissipation in BTU/hr to the cooling calculation and choose airflow direction (front-to-back or back-to-front) to match the cold aisle layout.
- For the 48YE-8CE, do not fix rack depth and cable bend allowance until the depth is confirmed with the vendor.
- Select power supply type (AC 100-240 V or DC -48 VDC) to match site distribution and connect the two PSUs to separate feeds.
- Compare ambient temperature with the 50 °C front-to-back, 45 °C back-to-front and 40 °C high-altitude limits.
Who should read it
Network and facility engineers planning rack, power and cooling for data-centre switches.
Document contents
- Extreme 7520 overview (7520-48Y-8C, 48YE-8CE and 48XT-6C features)
- Fan modules and power supplies
- Build stacks
- Site preparation (operating environment, rack, cable and power requirements)
- Technical specifications (interfaces, acoustic noise, MTBF, power specifications, environmental, standards)
- Power consumption and heat dissipation
Publication details
- Authors
- Extreme Networks
- Publisher
- Extreme Networks
- Year
- 2026
- Document number
- 9037389-00 Rev AJ
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Extreme Networks (2026). 7520 Series Installation Guide: Revision AJ. Extreme Networks. 9037389-00 Rev AJ. https://documentation.extremenetworks.com/7520%20Series%20Installation%20Guide/downloads/7520_Series_Installation_Guide.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.